UEM5L-400
400 A molded case earth leakage circuit breaker

- Range
- UEM5L
- Network Frequency
- 50 Hz
- Ambient Air Temperature for Storage
- -40…70 °C
- Circuit Breaker Mounting Mode
- Fixed; Plug-in type; Withdrawable type
400 A molded case earth leakage circuit breaker
Hongfa UEM5L-400 molded case earth leakage circuit breaker for AC power distribution, rated 400 A at 400 V AC 50 Hz.
Manufacturer Hongfa, reference UEM5L-400: molded case earth leakage circuit breaker (MCCB) for power distribution. Main characteristics — Rated current from 225 A to 400 A depending on temperature, rated operational voltage 400 V AC, rated insulation voltage 800 V AC 50 Hz, available in three-pole 3P or four-pole 4P versions. Breaking capacity: M version with Icu of 65 kA and Ics of 50 kA, H version with Icu of 85 kA and Ics of 65 kA, at 400 V AC 50 Hz conforming to IEC 60947-2. Thermal-magnetic or magnetic trip unit, with instantaneous protection adjustable at 10 In for power distribution. Earth-leakage protection with sensitivity adjustable from 100 to 1000 mA depending on version, time-delay or non-time-delay type. Mounting and controls — Fixed, plug-in or withdrawable mounting, operated by handle, motorized operating mechanism or rotary operating mechanism. Electrical accessories available: alarm contact, shunt release, auxiliary contact and undervoltage release. Operating conditions — Ambient operating temperature -25 to 70 °C, operating altitude up to 2000 m without derating, pollution degree 3 conforming to IEC 60664-1, relative humidity 0 to 95 % at 25 °C. Typical uses — Protection and isolation of distribution feeders on 50 Hz AC networks, in accordance with EN/IEC 60947-2 and CCC and CB certifications. Integration — Horizontal or vertical flat mounting on the back, utilisation category A, arcing distance up to 50 mm, connection pitch 44 mm. This product is available on quotation from Atlas Electronics.
No published question about this part yet. Questions are reviewed before publication.
Every characteristic recorded for UEM5L-400, with where it comes from. Use the filters to find one quickly.
| Characteristic | Value |
|---|---|
| Ambient Air Temperature for Operation | -25…70 °C |
| Ambient Air Temperature for Storage | -40…70 °C |
| Arcing Distance (mm) | ≤50mm |
| Breaking Capacity | M、H |
| China RoHS Regulation | China RoHS declaration; Product out of China RoHS scope. Substance declaration for your information. |
| Circuit Breaker Mounting Mode | Fixed; Plug-in type; Withdrawable type |
| Connection Pitch | 44 mm |
| Control type | Operated by handle; Operated by motorized operating mechanism; Operated by rotary operating mechanism |
| Depth | 97 mm |
| Device Application | Distribution |
| Device Short Name | UEM5L-400 |
| Earth-Leakage Protection Class | V/W:Class AC,VA/WA:Class A |
| Electrical Accessory Types | Alarm contact; Shunt release; Auxiliary contact; Undervoltage release |
| Electrical Durability | 1000 cycles at 400 V In |
| Height | 257 mm |
| Instantaneous Protection; Pick-up Adjustment Range [Ii] | 10In(For power distribution); 12In(For motor protection) |
| Mechanical Durability | 4000 cycles |
| Mounting Position | Horizontal and vertical flat on the back |
| Net weight | 6.2kg(3P)/8.0 kg(4P) |
| Network Frequency | 50 Hz |
| Network type | AC |
| Non-Time Delay Type; Earth-Leakage Protection Sensitivity Adjustment Range[IΔn] | 100/300/500/1000mA Adjustable |
| Non-Time Delay Type; Earth-Leakage Protection Time Delay 5I△n Max. Opening Time (s) | 0.04s |
| Operating Altitude | 0...2000 m without derating; 2000 m...4000 m with derating |
| Package — 3P | 4P |
| Package Height 1 | 18.5cm |
| Package Height 2 | 19.5cm |
| Package Length 1 | 37.8cm |
| Package Length 2 — 45.5cm | 54.5cm |
| Package Weight 1 — 6.86kg | 8.76kg |
| Package Weight 2 — 13.72kg | 17.52kg |
| Package Width 1 — 22cm | 26.5cm |
| Package Width 2 | 38.5cm |
| Poles Description | 3P(1)、4P |
| Pollution Degree | 3 conforming to IEC 60664-1 |
| Product Certifications | CCC; CB |
| Product Name | UEM5L |
| Product or Component Type | Earth leakage circuit breaker |
| Range | UEM5L |
| Rated Current (In) | 225 A at 40 °C; 250 A at 40 °C; 315 A at 40 °C; 350 A at 40 °C; 400 A at 40 °C |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated insulation voltage (Ui) | 800 V AC 50 Hz |
| Rated Operational Voltage (Ue) | 400 V AC |
| Rated Service Short-Circuit Breaking Capacity[Ics] | M:50 kA Ics at 400 V AC 50 Hz conforming to IEC 60947-2; H:65 kA Ics at 400 V AC 50 Hz conforming to IEC 60947-2 |
| Rated Ultimate Short-Circuit; Breaking Capacity [Icu] | M:65 kA Icu at 400 V AC 50 Hz conforming to IEC 60947-2; H:85 kA Icu at 400 V AC 50 Hz conforming to IEC 60947-2 |
| Relative humidity | 0…95 %(25℃) |
| Standards | EN/IEC 60947-2 |
| Suitability for Isolation | Yes conforming to IEC 60947-2 |
| Time Delay Type; Earth-Leakage Protection Sensitivity Adjustment Range[IΔn] | 300/500/1000mA Adjustable |
| Time Delay Type; Earth-Leakage Protection Time Delay 2I△n Max. Opening Time (s) | V:0.2, 0.5, 1.0/W:0.1, 0.3, 0.4; VA:0.2, 0.5, 1.0/WA:0.1, 0.3, 0.4 |
| Time Delay Type; Earth-Leakage Protection Time Delay I△n Max. Opening Time (s) | V:0.8, 2.0, 2.5/W:0.6, 1.0, 1.5; VA:0.8, 2.0, 2.5/WA:0.6, 1.0, 1.5 |
| Trip Unit Technology | Thermal-magnetic; Magnetic |
| Unit Type of Package 1 | PCE |
| Unit Type of Package 2 | Box |
| Utilisation Category | Category A |
| Width | 140mm(3P)、184mm(4P) |
No specification matches.
Last verification : 2026-11-02
Official documents and the technical data recorded for UEM5L-400. For a missing document or a specific revision, our experts send it to you.
Hongfa UEM5L-400 molded case earth leakage circuit breaker for AC power distribution, rated 400 A at 400 V AC 50 Hz.
| Parameter | Value |
|---|---|
| Ambient Air Temperature for Operation | -25…70 °C |
| Ambient Air Temperature for Storage | -40…70 °C |
| Arcing Distance (mm) | ≤50mm |
| Breaking Capacity | M、H |
| China RoHS Regulation | China RoHS declaration; Product out of China RoHS scope. Substance declaration for your information. |
| Circuit Breaker Mounting Mode | Fixed; Plug-in type; Withdrawable type |
| Connection Pitch | 44 mm |
| Control type | Operated by handle; Operated by motorized operating mechanism; Operated by rotary operating mechanism |
| Depth | 97 mm |
| Device Application | Distribution |
| Device Short Name | UEM5L-400 |
| Earth-Leakage Protection Class | V/W:Class AC,VA/WA:Class A |
| Electrical Accessory Types | Alarm contact; Shunt release; Auxiliary contact; Undervoltage release |
| Electrical Durability | 1000 cycles at 400 V In |
| Height | 257 mm |
| Instantaneous Protection; Pick-up Adjustment Range [Ii] | 10In(For power distribution); 12In(For motor protection) |
| Mechanical Durability | 4000 cycles |
| Mounting Position | Horizontal and vertical flat on the back |
| Net weight | 6.2kg(3P)/8.0 kg(4P) |
| Network Frequency | 50 Hz |
| Network type | AC |
| Non-Time Delay Type; Earth-Leakage Protection Sensitivity Adjustment Range[IΔn] | 100/300/500/1000mA Adjustable |
| Non-Time Delay Type; Earth-Leakage Protection Time Delay 5I△n Max. Opening Time (s) | 0.04s |
| Operating Altitude | 0...2000 m without derating; 2000 m...4000 m with derating |
| Package — 3P | 4P |
| Package Height 1 | 18.5cm |
| Package Height 2 | 19.5cm |
| Package Length 1 | 37.8cm |
| Package Length 2 — 45.5cm | 54.5cm |
| Package Weight 1 — 6.86kg | 8.76kg |
| Package Weight 2 — 13.72kg | 17.52kg |
| Package Width 1 — 22cm | 26.5cm |
| Package Width 2 | 38.5cm |
| Poles Description | 3P(1)、4P |
| Pollution Degree | 3 conforming to IEC 60664-1 |
| Product Certifications | CCC; CB |
| Product Name | UEM5L |
| Product or Component Type | Earth leakage circuit breaker |
| Range | UEM5L |
| Rated Current (In) | 225 A at 40 °C; 250 A at 40 °C; 315 A at 40 °C; 350 A at 40 °C; 400 A at 40 °C |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated insulation voltage (Ui) | 800 V AC 50 Hz |
| Rated Operational Voltage (Ue) | 400 V AC |
| Rated Service Short-Circuit Breaking Capacity[Ics] | M:50 kA Ics at 400 V AC 50 Hz conforming to IEC 60947-2; H:65 kA Ics at 400 V AC 50 Hz conforming to IEC 60947-2 |
| Rated Ultimate Short-Circuit; Breaking Capacity [Icu] | M:65 kA Icu at 400 V AC 50 Hz conforming to IEC 60947-2; H:85 kA Icu at 400 V AC 50 Hz conforming to IEC 60947-2 |
| Relative humidity | 0…95 %(25℃) |
| Standards | EN/IEC 60947-2 |
| Suitability for Isolation | Yes conforming to IEC 60947-2 |
| Time Delay Type; Earth-Leakage Protection Sensitivity Adjustment Range[IΔn] | 300/500/1000mA Adjustable |
| Time Delay Type; Earth-Leakage Protection Time Delay 2I△n Max. Opening Time (s) | V:0.2, 0.5, 1.0/W:0.1, 0.3, 0.4; VA:0.2, 0.5, 1.0/WA:0.1, 0.3, 0.4 |
| Time Delay Type; Earth-Leakage Protection Time Delay I△n Max. Opening Time (s) | V:0.8, 2.0, 2.5/W:0.6, 1.0, 1.5; VA:0.8, 2.0, 2.5/WA:0.6, 1.0, 1.5 |
| Trip Unit Technology | Thermal-magnetic; Magnetic |
| Unit Type of Package 1 | PCE |
| Unit Type of Package 2 | Box |
| Utilisation Category | Category A |
| Width | 140mm(3P)、184mm(4P) |
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
400 A molded case earth leakage circuit breaker




Describe your application and constraints in a request.
What is recorded about the regulatory status and the life of this part.
| Current status | Status not stated |
| Key dates | Not recorded |
| Manufacturer part number | UEM5L-400 |
| Manufacturer | Hongfa |
Molded Case Circuit Breakers
2-pole DC MCCB circuit breaker 320 A DC1500V · Ref. : UEM1E-320
Price on request
Molded Case Circuit Breakers
160 A molded case circuit breaker 3P/4P, 400 V AC · Ref. : UEM5-160
Price on request
Molded Case Circuit Breakers
800 A 3P/4P molded case circuit breaker for distribution
Price on request
Molded Case Circuit Breakers
Molded case circuit breaker 630 A 3P and 4P · Ref. : UEM5-630
Price on request
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details