XMC0-401 – Definite purpose power contactor for refrigeration, 40 A, 1 NO

Definite purpose power contactor for refrigeration, 40 A, 1 NO

Power Contactors

  • 50 pcs
  • 17.5 cm
  • 46 cm
  • 11.9 kg
Manufacturer part number
XMC0-401
Manufacturer
Hongfa
Maximum Horse Power Rating
3 hp 240/277 V AC, 1phase
Number of Units in Package
50 pcs

The Hongfa XMC0-401 is a 40 A FLA power contactor with one NO contact, designed for switching AC loads, notably in refrigeration and air-conditioning equipment.

Product overview

Overview. The Hongfa XMC0-401 is a definite purpose power contactor from the XMC0 series, with one 1NO pole and a shunt. It is intended for switching AC loads up to 600 V AC, with a full load current of 40 A.

Main characteristics. Resistive current of 50 A, locked rotor current of 240 A at 240/277 V AC, 200 A at 480 V AC and 160 A at 600 V AC. Maximum rating of 3 hp at 240/277 V AC, single phase. Operating rate of 360 cycles/h electrical and 3600 cycles/h mechanical. Minimum switching load of 1 A at 110 V AC.

Coil supply. Available control voltages: 24 V AC 50/60 Hz, 110-120 V AC 50/60 Hz, 208-220 V AC 50 Hz / 208-240 V AC 60 Hz, 277 V AC 60 Hz and 380-415 V AC 50 Hz / 440-480 V AC 60 Hz. For the 24 V AC version, inrush of 27 VA at 50 Hz and 25 VA at 60 Hz, sealed consumption of 8.5 VA at 50 Hz and 6.5 VA at 60 Hz. Coil operating range of 0.8 to 1.1 Us.

Connection and mounting. Screw power terminals with washer and quick connect, vertical coil terminals. Tightening torque of 25 lb-in on screw or box lug terminals. Mounting by screw or on 35 mm DIN rail; rail mounting requires a DIN rail adapter, suffix "-123" added after the model name.

Environmental conditions. Ambient operating temperature from -40 °C to 70 °C. Dimensions: 52 mm wide, 81 mm high, 59 mm deep; weight 0.22 kg.

Compliance and integration. Suffix "W" for flame arrest-protected components for use in equipment employing A2L refrigerants. Certifications UL, CCC and TÜV; compliant with UL 60947-4-1, GB/T 14048.4, IEC 60947-4-1 and EN 60947-4-1, EU and China RoHS, REACh and mercury free. Sold in packs of 50 pieces.

See all specifications

Highlights

  • China RoHS Regulation: Conforming
  • Coil Terminals — Normal type terminal: Vertical type terminal
  • Control Circuit Voltage [Us] — Code: Voltage
  • Control Circuit Voltage [Us] — E: 24 V AC 50/60Hz
  • Control Circuit Voltage [Us] — F: 110-120 V AC 50/60Hz
  • Control Circuit Voltage [Us] — I: 208-220 V AC 50Hz 208-240 V AC 60Hz

Good to know before integrating

  • Power: plan for a supply compatible with 3 hp 240/277 V AC, 1phase.