XMC0-503
3P 50 A power contactor for A2L refrigeration equipment

- Mounting Support
- Screw
- Number of Units in Package
- 1pcs 30pcs
- Package Height
- 85mm 225mm
- Package Length
- 110mm 462mm
3P 50 A power contactor for A2L refrigeration equipment
The Hongfa XMC0-503 is a 3-pole 3NO power contactor rated 50 A FLA for switching loads up to 600 V AC. Its W variant suits refrigeration and air-conditioning equipment using A2L refrigerants.
Hongfa XMC0-503 contactor. The XMC0-503 is a Hongfa power contactor from the XMC0 series, a definite purpose contactor with three poles and three normally open contacts (3NO). It is listed under power contactors.
Main characteristics. Full load ampere rating of 50 A, locked rotor ampere of 300 A at 240/277 V AC, 250 A at 480 V AC and 200 A at 600 V AC, resistive ampere of 63 A. Maximum horsepower of 10 hp at 240/277 V AC single phase, 15 hp at 240/277 V AC three phase, 25 hp at 480 V AC three phase and 25 hp at 600 V AC three phase. Maximum operating rate of 360 cycles/h electrical and 3600 cycles/h mechanical. Minimum switching load of 110 V AC, 1 A. The model is mercury free and has no built-in auxiliary contacts; additional auxiliary modules can be installed.
Coil supply. Control circuit voltage according to the Us voltage code: operational at 0.8 to 1.1 Us and drop-out at 0.2 to 0.75 Us, AC 50/60 Hz at 25 °C. Nominal inrush VA at 25 °C, for example 100 VA at 24 V 50 Hz or 90 VA at 24 V 60 Hz, 90 VA at 220 V 50 Hz, 85 VA at 415 V 50 Hz and 100 VA at 480 V 60 Hz. Nominal sealed VA at 25 °C, for example 16.5 VA at 24 V 50 Hz and 18.5 VA at 480 V 60 Hz. Power circuit rated operational voltage up to 600 V AC 50/60 Hz.
Operating conditions. Ambient temperature from -40 °C to 70 °C in operation and in storage, minimum operating temperature of -40 °C or lower. Screw mounting. Tightening torques of 45 lb-in on screw terminals and 50 lb-in on box lug terminals, 12 lb-in on the control circuit. Dimensions 80 mm deep, 102.6 mm high and 70 mm wide, net weight 0.67 kg. Conforms to EU RoHS, China RoHS and REACh.
Certifications and standards. UL and CCC certifications, standards UL 60947-4-1 and GB/T 14048.4. W variant with flame arrest-protected components for refrigeration and air-conditioning equipment employing A2L refrigerants.
Atlas Electronics offers this Hongfa contactor on quotation.
No published question about this part yet. Questions are reviewed before publication.
Every characteristic recorded for XMC0-503, with where it comes from. Use the filters to find one quickly.
| Characteristic | Value |
|---|---|
| A2L Application | Suffix w/ “W” : Flame Arrest-protected Components for Use in Refrigeration and Air-conditioning Equipment Employing A2L Refrigerants. |
| Auxiliary Contact Composition | W/o built-in auxiliary contacts.; Additional auxiliary contact modules can be installed if needed. |
| China RoHS Regulation | Conforming |
| Control Circuit Voltage Limits; @ 25℃ (Cold state) | 0.8...1.1 Us: operational AC 50/60 Hz; 0.2...0.75 Us: drop-out AC 50/60 Hz |
| Control Circuit Voltage [Us] | Code |
| Depth | 80 mm |
| Device Short Name | XMC0-503 |
| EU RoHS Directive | Conforming |
| Full Load Ampere [FLA] | 50 A |
| Height | 102.6 mm |
| Locked Rotor Ampere [LRA] | 300 A @ 240/277 V AC;250 A @ 480 V AC;200 A @ 600 V AC |
| Main Contact Terminals | C type: Slotted & Hex head washer w/ quick connect; D type:Box Lug w/ quick connect |
| Maximum Horse Power Rating | 10 hp 240/277 V AC, 1phase; 15 hp 240/277 V AC, 3phase; 25 hp 480 V AC, 3phase; 25 hp 600 V AC, 3phase |
| Maximum Operating Rate | Electrical: 360 cycs/h; Mechanical: 3600 cycs/h |
| Mercury Free | Yes |
| Minimum Switching Load | 110 VAC, 1A |
| Mounting Support | Screw |
| Net weight | 0.67 kg |
| Nominal Inrushed VA; @ 25℃ (Cold state) | E:100 VA @ 24V 50 Hz, 90 VA @ 24V 60Hz; F:100 VA @ 120V 50 Hz, 90 VA @ 120V 60Hz; I:90 VA @ 220V 50 Hz, 100 VA @ 240V 60Hz; L:90 VA @ 277V 60Hz; N:85 VA @ 415V 50 Hz, 100 VA @ 480V 60Hz |
| Nominal Sealed VA; @ 25℃ (Cold state) | E:16.5 VA @ 24V 50 Hz, 12.5 VA @ 24V 60Hz; F:17 VA @ 120V 50 Hz, 13 VA @ 120V 60Hz; I:15 VA @ 220V 50 Hz, 15 VA @ 240V 60Hz; L:14 VA @ 277V 60Hz; N:16.5 VA @ 415V 50 Hz, 18.5 VA @ 480V 60Hz |
| Number of Units in Package | 1pcs 30pcs |
| Package Height | 85mm 225mm |
| Package Length | 110mm 462mm |
| Package Weight | 0.7kg 21.1kg |
| Package Width | 80mm 372mm |
| Permissible Ambient Air; Temperature Around the Device | -40 °C…70 °C (-40 °F…158 °F) for normal operating; -40 °C…70 °C (-40 °F…158 °F) for storage |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | UL,CCC |
| Product or Component Type | Definite Purpose Contactors |
| Rated Operational Voltage (Ue) | Power circuit:≤ 600 V AC 50/60Hz |
| REACh Regulation | Conforming |
| Resistive Ampere [RES] | 63 A |
| RoHS Exemption Information | Yes |
| Standards | UL 60947-4-1,GB/T 14048.4, |
| Tightening torque | Power circuit: 45 lb-in - on screw terminals; Power circuit: 50 lb-in- on box lug terminals; Control circuit:12 lb-in |
| Unit Type of Package | 1 box 1 carton |
| Width | 70 mm |
No specification matches.
Last verification : 2026-11-02
Official documents and the technical data recorded for XMC0-503. For a missing document or a specific revision, our experts send it to you.
The Hongfa XMC0-503 is a 3-pole 3NO power contactor rated 50 A FLA for switching loads up to 600 V AC. Its W variant suits refrigeration and air-conditioning equipment using A2L refrigerants.
| Parameter | Value |
|---|---|
| A2L Application | Suffix w/ “W” : Flame Arrest-protected Components for Use in Refrigeration and Air-conditioning Equipment Employing A2L Refrigerants. |
| Auxiliary Contact Composition | W/o built-in auxiliary contacts.; Additional auxiliary contact modules can be installed if needed. |
| China RoHS Regulation | Conforming |
| Control Circuit Voltage Limits; @ 25℃ (Cold state) | 0.8...1.1 Us: operational AC 50/60 Hz; 0.2...0.75 Us: drop-out AC 50/60 Hz |
| Control Circuit Voltage [Us] | Code |
| Depth | 80 mm |
| Device Short Name | XMC0-503 |
| EU RoHS Directive | Conforming |
| Full Load Ampere [FLA] | 50 A |
| Height | 102.6 mm |
| Locked Rotor Ampere [LRA] | 300 A @ 240/277 V AC;250 A @ 480 V AC;200 A @ 600 V AC |
| Main Contact Terminals | C type: Slotted & Hex head washer w/ quick connect; D type:Box Lug w/ quick connect |
| Maximum Horse Power Rating | 10 hp 240/277 V AC, 1phase; 15 hp 240/277 V AC, 3phase; 25 hp 480 V AC, 3phase; 25 hp 600 V AC, 3phase |
| Maximum Operating Rate | Electrical: 360 cycs/h; Mechanical: 3600 cycs/h |
| Mercury Free | Yes |
| Minimum Switching Load | 110 VAC, 1A |
| Mounting Support | Screw |
| Net weight | 0.67 kg |
| Nominal Inrushed VA; @ 25℃ (Cold state) | E:100 VA @ 24V 50 Hz, 90 VA @ 24V 60Hz; F:100 VA @ 120V 50 Hz, 90 VA @ 120V 60Hz; I:90 VA @ 220V 50 Hz, 100 VA @ 240V 60Hz; L:90 VA @ 277V 60Hz; N:85 VA @ 415V 50 Hz, 100 VA @ 480V 60Hz |
| Nominal Sealed VA; @ 25℃ (Cold state) | E:16.5 VA @ 24V 50 Hz, 12.5 VA @ 24V 60Hz; F:17 VA @ 120V 50 Hz, 13 VA @ 120V 60Hz; I:15 VA @ 220V 50 Hz, 15 VA @ 240V 60Hz; L:14 VA @ 277V 60Hz; N:16.5 VA @ 415V 50 Hz, 18.5 VA @ 480V 60Hz |
| Number of Units in Package | 1pcs 30pcs |
| Package Height | 85mm 225mm |
| Package Length | 110mm 462mm |
| Package Weight | 0.7kg 21.1kg |
| Package Width | 80mm 372mm |
| Permissible Ambient Air; Temperature Around the Device | -40 °C…70 °C (-40 °F…158 °F) for normal operating; -40 °C…70 °C (-40 °F…158 °F) for storage |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | UL,CCC |
| Product or Component Type | Definite Purpose Contactors |
| Rated Operational Voltage (Ue) | Power circuit:≤ 600 V AC 50/60Hz |
| REACh Regulation | Conforming |
| Resistive Ampere [RES] | 63 A |
| RoHS Exemption Information | Yes |
| Standards | UL 60947-4-1,GB/T 14048.4, |
| Tightening torque | Power circuit: 45 lb-in - on screw terminals; Power circuit: 50 lb-in- on box lug terminals; Control circuit:12 lb-in |
| Unit Type of Package | 1 box 1 carton |
| Width | 70 mm |
Answers to the questions that the recorded characteristics of XMC0-503 can answer. A question is not asked when nothing is recorded to answer it.
Yes — recorded under "Auxiliary Contact Composition": W/o built-in auxiliary contacts.; Additional auxiliary contact modules can be installed if needed..
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
3P 50 A power contactor for A2L refrigeration equipment




Describe your application and constraints in a request.
What is recorded about the regulatory status and the life of this part.
| Current status | Status not stated |
| Key dates | Not recorded |
| Manufacturer part number | XMC0-503 |
| Manufacturer | Hongfa |
Power Contactors
1 Pole + Shunt 20A-40A Definite Purpose Contactor · Ref. : SA-1.5P
Price on request
Power Contactors
Three-pole power contactor 38 A AC-3 AC coil 50/60 Hz
Price on request
Power Contactors
Technical article: relay versus contactor differences
Price on request
Power Contactors
EPS box with integrated contactors for 1-phase/3-phase inverters · Ref. : X1/X3-EPS
Price on request
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details