CL-20A-C – Natural gas (methane) detector with CAN Bus interface

Natural gas (methane) detector with CAN Bus interface

Methane Sensors

  • -10 ~ 40°C
  • 4.5 W
  • Yes
  • -30 ~ +75°C
Manufacturer part number
CL-20A-C
Manufacturer
ICP DAS
Operating Temperature
-10 ~ 40°C
Consumption
4.5 W

Natural gas (methane) detector with a semiconductor sensor and CAN Bus interface, designed for early detection of methane concentration in the air.

Product overview

Overview. The ICP DAS CL-20A-C is a natural gas (methane) detector built around a semiconductor sensor. It measures the methane concentration in the air in real time and sounds an alarm when 3% to 20% of the Lower Explosive Limit (LEL) is reached.

Main characteristics. Response time of 20 seconds, sampling time of 1 second, warm-up time of 1 minute and a life time of 5 years. The alarm level is set at 3000 ppm, the module provides one dry contact output, and its buzzer alarm sound pressure is at least 85 dB at 3 metres.

Interfaces and connectivity. ISO-11898-2 CAN 2.0A communication interface, baud rate of 125 kbps, 120 Ω terminal resistor for CAN_H and CAN_L selectable by DIP switch. The module supports alarm system linkage with other gas detectors. Real-time clock and data logger with up to 450,000 records.

Power and environment. Powered from terminal block at 100 to 220 VAC, 50 Hz / 60 Hz, consumption 4.5 W. Operating temperature -10 to 40 °C, storage temperature -30 to +75 °C, humidity 0 to 80% RH non-condensing. IP20 protection rating, ceiling or wall mounting, dimensions Ø 130 x 49 mm. Follows the EN-50194 specifications according to the manufacturer.

Integration. The module connects to a CAN bus and fits into a gas safety supervision system. Non-isolated.

See all specifications

Highlights

  • Response time: 20 seconds
  • ALARM LEVEL: 3000 ppm
  • Baud rate: 125 kbps
  • Channels: 1
  • Consumption: 4.5 W
  • Data logger: Yes, up to 450,000 records

Good to know before integrating

  • Thermal: rated operating range -10 ~ 40°C — check it against the installation environment.

See also

Technical questions

Ask a question

No published question about this part yet. Questions are reviewed before publication.

Similar products

All Methane Sensors
Request a quote