iWSN 433 MHz wireless data concentrator with RS-232/RS-485 serial port, receiving data from up to 31 iWSN sensors and exposing it over Modbus RTU slave.
Operating Temperature-25 ~ +75°C
Consumption1W Max
Radio Frequency433MHz
Storage Temperature-30 ~ +80°C
Channels0 ~ 15 (confi gured by rotary switch)
Dimensions (mm)10 x 108 (Ø x L)
Product overview
Overview. The iWSN-200U is an iWSN wireless data concentrator from ICP DAS. It receives and buffers the data of 31 iWSN sensors over a 433 MHz radio interface and makes them available on one serial interface, RS-232 or RS-485, the two interfaces cannot be used simultaneously.
Main characteristics. The module supports 16 radio channels, selected by rotary switch, and 8 groups of IDs. It has a 0 dBi omni-directional antenna with an RP-SMA male connector and an ANT-Base-02 extension cable of 1.5 metres. Line-of-sight range is 100 m, with a transmission power of 9±1 dBm (PA off) or 18±1 dBm (PA on).
Interfaces and connectivity. The Modbus RTU protocol in slave mode lets a PLC or supervisory system read sensor data through the RS-485 or RS-232 port. Baud rates range from 1200 to 115200 bps, format N81. Status indicators are one Power LED, one RF_Tx LED and one RF_Rx LED.
Power and environment. The module operates from +10 to +30 VDC, with a maximum consumption of 1 W. It mounts on DIN rail. Operating temperature is -25 to +75 °C and humidity tolerance is 10 to 90 % RH, non-condensing. It meets ESD (IEC 61000-4-2, ±4 kV contact), EFT (IEC 61000-4-4, ±1 kV) and surge (IEC 61000-4-5, ±1 kV) tests.
Typical uses. The iWSN-200U suits collecting wireless sensor measurements into a PLC or a Modbus RTU supervision system, for example for monitoring meters or sensors distributed across an installation.
Integration. It works with the iWSN sensor range from ICP DAS. Available on quotation from Atlas Electronics.
iWSN 433 MHz wireless data concentrator with RS-232/RS-485 serial port, receiving data from up to 31 iWSN sensors and exposing it over Modbus RTU slave.
ANT-Base-02, Antenna magnetic base with 1.5 meter cable (RP SMA Male Plug) (RoHS)
Humidity
10 ~ 90% RH, Non-condensing
Input Type
+10 ~ +30 VDC
Installation
DIN-Rail
iWSN-200U CR
iWSN data concentrator with RS-232/RS-485 serial port (RoHS)
Node Address
1 ~ 31
Operating Temperature
-25 ~ +75°C
Ports
1 x RS-485 1 x RS-232 (Cannot be used simultaneously)
PRODUCT SERIES
iWSN-200U CR
DESCRIPTION iWSN data concentrator with RS-232/RS-485 serial port (RoHS)
Protocol
Modbus RTU
Radio Frequency
433MHz
STATUS
1 x Power 1 x RF_Tx 1 x RF_Rx
Storage Temperature
-30 ~ +80°C
Surge (IEC 61000-4-5)
+/- 1kV
Transmission Distance (LoS)
100m (Line of sign, LoS)
Transmission Power
9±1dBm (PA Off ) / 18±1dBm (PA On)
Type
0 dBi, Omni-Directional
Integration
Points to check before using IWSN-200U in a design. They are derived from the recorded characteristics, not from the manufacturer's application circuits.
1Thermalrated operating range -25 ~ +75°C — check it against the installation environment.
Power and communication
Consumption
1W Max
Transmission Power
9±1dBm (PA Off ) / 18±1dBm (PA On)
Check the exact pin assignment and the application circuit in the datasheet, or ask our experts.
Implementation checklist
Thermal : rated operating range -25 ~ +75°C — check it against the installation environment.
Applications and use cases
Architectures in which IWSN-200U can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
A building’s energy, comfort and occupancy data sit in separate systems. Sensors, meters and gateways feed one model of the building, room by room, to compare scenarios and steer the installations
To check
Data model and building plans available
Software platform hosting the twin
Sensor density needed for a useful model
Associated system blocks
SensorsMetersGateways
Need a complete solution?
Send a request for IWSN-200U and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productICP DAS
IWSN-200U
433 MHz wireless data concentrator with RS-232/RS-485 port
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.