M-7002-G remote I/O module. The ICP DAS M-7002-G is a DIN-rail remote I/O acquisition and control module for RS-485 networks, supporting the Modbus RTU and DCON protocols.
Analog inputs. Four differential inputs with 16-bit resolution and jumper-selectable ranges: ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V, ±20 mA, 0 ~ 20 mA and 4 ~ 20 mA. Accuracy is 0.1% in normal mode at a sampling rate of 10 Hz, and 0.5% in fast mode at 60 Hz. Each channel can be configured individually.
Digital inputs and outputs. Five digital inputs compatible with sink or source (NPN/PNP) wiring, with an ON level of +10 to +50 VDC and an OFF level of +4 VDC maximum. Four Form A relay outputs rated for 105 electrical operations and 2 x 10⁷ mechanical operations. Safe and power-on values are programmable.
Communication and watchdog. One RS-485 port, baud rates from 1200 to 115200 bps, data format (N, 8, 1), and a programmable dual watchdog covering the module and communication. A status LED indicates power and communication.
Power and environment. Supply from +10 to +30 VDC, power consumption of 1.8 W, 3750 VDC isolation, 2500 VDC intra-module isolation, 240 Vrms overvoltage protection and reverse polarity protection. Operating temperature from -25 to +75 °C, storage from -40 to +85 °C, humidity from 10 to 95% RH non-condensing. Dimensions 72 x 123 x 35 mm.
Typical uses. Acquisition of analog sensors and dry contacts, and switching of loads through relays from a PLC or supervisory system using Modbus RTU or DCON.
Integration. Available on quotation from Atlas Electronics.