KEW 6010B – Multi-function installation tester with earth and RCD testing

Multi-function installation tester with earth and RCD testing

Installation and Earth Testers

  • 20/2000&Omega
  • > 1mA
  • > 200mA
  • 150mA (50ms)
Manufacturer part number
KEW_6010B
Manufacturer
Kyoritsu
Impedance range
20/2000&Omega
Measuring Range
20/200Ω (Auto-Ranging)

The Kyoritsu KEW 6010B is a multi-function installation tester compliant with IEC 61557, designed for earth resistance measurement and testing of residual current devices.

Product overview

Kyoritsu KEW 6010B multifunction installation tester — the KEW 6010B is a multi-function installation tester designed to IEC 61010-1 and IEC 61557, covering earth resistance measurement and testing of residual current devices.

Main characteristics. Impedance measuring range of 20 and 2000 Ω with auto-ranging, test voltage of 500 V and 1000 V, open circuit voltage above 6 V and short circuit current above 200 mA. Accuracy of ±(3 % rdg + 3 dgt) on impedance and ±(1 % rdg + 3 dgt) on trip time. Data memory of 300 measured results.

Residual current device testing. Test currents of 5 mA for IΔn of 10 mA, 15 mA for 30 and 100 mA, 150 mA for 300 and 500 mA. Test modes x1/2, x1, DC, Fast and Auto Ramp, with accuracy of ±10 % in DC and ±4 % in Auto Ramp.

Power and environment. Powered by 8 R6/LR6 batteries, rated voltage 230 V +10 to 15 % (50 Hz). IP40 protection according to IEC 60529, dimensions 115 × 175 × 86 mm, weight approx. 840 g.

Accessories and communication. Test leads 7122B, test lead with IEC connector KAMP10, fuse 8923 0.5 A/600 V supplied with one spare, cord case 9092 and shoulder strap 9121. Results transfer to a PC through the optical RS-232C port using the optional 8212-USB adapter. Distribution board test leads 7133B available as an option.

Typical uses. Commissioning and inspection of low-voltage electrical installations, verification of continuity and earth resistance, testing of residual current circuit breakers. Available on quotation from Atlas Electronics.

See all specifications

Highlights

  • Accuracy: ±(3%rdg + 3dgt)
  • Accuracy — Trip Time: ±(1%rdg + 3dgt)
  • Data Memory: 300 measured results
  • Dimension: 115(L) × 175(W) × 86(D)mm
  • Impedance range: 20/2000&Omega
  • Open circuit voltage: > 6V

Technical questions

Ask a question

No published question about this part yet. Questions are reviewed before publication.