The Kyoritsu KEW 6516BT is a multifunction tester for low-voltage electrical installations, covering loop impedance, RCDs, earth, insulation, continuity and voltage.

Product overview

Overview. The Kyoritsu KEW 6516BT is a multifunction electrical installation tester, listed by the manufacturer as "KEW 6516BT", for electrical installation professionals. It combines the main verification measurements of an installation in a single instrument.

Loop and RCD measurements. ATT (Anti-Trip Technology, with 2 or 3 wire connection) allows loop L-PE testing on all RCDs without tripping, with 0.001 Ω resolution on the 2 Ω range. The Zs/Ra Limit function compares results with the values required by installation standards. AC, A, F, B, EV and variable RCD types are supported, with single, automatic, ramp and contact voltage tests.

Earth, insulation and continuity. Earth resistance can be measured in 2 or 3 wire mode with the accessories included. Insulation is testable at 100, 250, 500 and 1000 V with automatic discharge. Continuity is measured at 200 mA or 15 mA with a selectable buzzer. SPD testing for varistor-type devices and the PAT function for portable appliances complete the range.

Display, connectivity and safety. The 3.5-inch colour LCD shows all data together, with a help function indicating the connection for the selected function. Bluetooth 5.0 and USB communication is available through the KEW Smart Advanced app. The instrument complies with IEC 61010-1 in CAT IV 300 V / CAT III 600 V and with IEC 61557-1, 2, 3, 4, 5, 6, 7 and 10. It is powered by 8 LR6 (AA) batteries and weighs 1350 g with batteries.

Typical uses. Safety verification of low-voltage installations, RCD and fault loop checks, earth resistance measurement, insulation testing and portable appliance verification with the PAT function.

See all specifications

Highlights

  • Accuracy — ±3%rdg±6dgt — ±3%rdg±10dgt — ±3%rdg±4dgt — ±3%rdg±25m&Omega: ±3%rdg±4dgt
  • Accuracy — Frequency: ±0.5%rdg±2dgt
  • Accuracy — Trip; current — Ramp — -4 to +4%: -10 to +10%
  • Accuracy — Trip; current — x1 — +2 to +8%: 0 to +10%
  • Accuracy — Trip; time — x1 — 550ms(G):±1%rdg±2ms,1000ms(S):±1%rdg±2ms: 10.5s:±1%±2㎳
  • Accuracy — Volts: ±2%rdg±4dgt