MODEL_5406A
RCD tester for standard, selective, AC and A breakers

- Rated Tripping Current
- 10/20/30/200/300/500mA
- Trip Current Duration
- 1000ms, 200ms (×5)
- Trip Time Accuracy
- ±0.6%rdg±4dgt
- Dimension
- 167(L) × 186(W) × 89(D)mm
RCD tester for standard, selective, AC and A breakers
Installation and Earth Testers
The Kyoritsu MODEL 5406A is an RCD tester that checks tripping time and tripping current of standard, selective, AC and A residual current breakers. It complies with IEC 61557.
Kyoritsu MODEL 5406A RCD tester. The Kyoritsu MODEL 5406A is an RCD tester for checking electrical installations. It measures the tripping time and tripping current of residual current devices.
Main characteristics. The tester uses a custom microprocessor and constant current source circuitry, so that a fluctuating mains voltage does not affect measurement accuracy. Trip time accuracy is ±0.6%rdg ±4dgt, with a lowest resolution of 1 ms. Rated tripping currents are 10, 20, 30, 200, 300 and 500 mA, with trip current durations of 1000 ms and 200 ms (×5). Fault condition settings include × 1/2, × 1, × 5, × DC and AUTO RAMP. A 0 and 180 degree phase angle switch permits quick tests and consistent readings.
Tests and wiring check. The MODEL 5406A tests standard, selective, AC and A (DC sensitive) breakers. Three LEDs indicate the correct wiring status, and a visual indication shows reversed phase and neutral wiring at the socket. The tripping time is shown on a large digital readout.
Power, environment and standards. It operates on 230V +10 to 15% (195 to 253V) 50Hz. Its rating is IP54. It complies with IEC 61557-1 and -6, IEC 61010-1 (CAT III 300V, pollution degree 2), IEC 61010-2-031 and IEC 60529. Dimensions: 167 × 186 × 89 mm; weight approx. 800 g.
Accessories. The tester is supplied with a molded plug test lead, a shoulder strap (9121), a cord case (9147) and the instruction manual. Distribution board test leads (7121B) are available as an optional accessory. The instruction manual is offered in several languages, including English.
Use. This tester suits the maintenance and verification of electrical installations fitted with residual current devices. The product is available on quotation from Atlas Electronics.
No published question about this part yet. Questions are reviewed before publication.
Every characteristic recorded for MODEL_5406A, with where it comes from. Use the filters to find one quickly.
| Characteristic | Value |
|---|---|
| Accessories | Molded plug test lead; 9121 (Shoulder Strap); 9147 (Cord case); Instruction Manual |
| Applicable Standards | IEC 61557-1,-6; IEC 61010-1 CAT Ⅲ 300V Pollution Degree 2; IEC 61010-2-031; IEC 60529 (IP54) |
| Dimension | 167(L) × 186(W) × 89(D)mm |
| Fault Condition Settings | × 1/2, × 1, × 5, × DC,; AUTO RAMP |
| Lowest Resolution | 1ms |
| Operating Voltage | 230V+10 to 15%; (195 to 253V) 50Hz |
| Optional Accessories | 7121B (Distribution board test leads) |
| Rated Tripping Current | 10/20/30/200/300/500mA |
| Test of a large kind of RCDs | Standard, Selective, AC and A(DC sensitive breakers) |
| Trip Current Duration | 1000ms, 200ms (×5) |
| Trip Time Accuracy | ±0.6%rdg±4dgt |
| Weight | Approx. 800g |
No specification matches.
Last verification : 2026-11-03
Official documents and the technical data recorded for MODEL_5406A. For a missing document or a specific revision, our experts send it to you.
The Kyoritsu MODEL 5406A is an RCD tester that checks tripping time and tripping current of standard, selective, AC and A residual current breakers. It complies with IEC 61557.
| Parameter | Value |
|---|---|
| Accessories | Molded plug test lead; 9121 (Shoulder Strap); 9147 (Cord case); Instruction Manual |
| Applicable Standards | IEC 61557-1,-6; IEC 61010-1 CAT Ⅲ 300V Pollution Degree 2; IEC 61010-2-031; IEC 60529 (IP54) |
| Dimension | 167(L) × 186(W) × 89(D)mm |
| Fault Condition Settings | × 1/2, × 1, × 5, × DC,; AUTO RAMP |
| Lowest Resolution | 1ms |
| Operating Voltage | 230V+10 to 15%; (195 to 253V) 50Hz |
| Optional Accessories | 7121B (Distribution board test leads) |
| Rated Tripping Current | 10/20/30/200/300/500mA |
| Test of a large kind of RCDs | Standard, Selective, AC and A(DC sensitive breakers) |
| Trip Current Duration | 1000ms, 200ms (×5) |
| Trip Time Accuracy | ±0.6%rdg±4dgt |
| Weight | Approx. 800g |
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
RCD tester for standard, selective, AC and A breakers

MODEL 5402D

MODEL

KEW

Describe your application and constraints in a request.
What is recorded about the regulatory status and the life of this part.
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
| Current status | Status not stated |
| Key dates | Not recorded |
| Manufacturer part number | MODEL_5406A |
| Manufacturer | Kyoritsu |
Installation and Earth Testers
Single and three-phase ZigBee electrical metering module
Price on request
Installation and Earth Testers
Multifunction installation tester with loop and RCD testing · Ref. : KEW_6016
Price on request
Installation and Earth Testers
Advanced earth resistance and soil resistivity tester · Ref. : UT572
Price on request
Installation and Earth Testers
Residual current device (RCD) tester with trip time measurement · Ref. : KEW_5410
Price on request
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details