MODEL_6015
10-function multi-function installation tester

- Voltage Measuring Range
- 100 - 400V AC [50Hz]
- Fault Current Ranges
- 2000A and 20kA
- Rated Current
- >1mA
- Short Circuit Current
- >200mA DC
10-function multi-function installation tester
Installation and Earth Testers
Kyoritsu MODEL 6015 multi-function tester for verifying the safety of electrical installations, compliant with IEC 61557, with on-board memory and IrDA infrared port.
Overview. The Kyoritsu MODEL 6015 is a multi-function installation tester able to perform ten separate test functions, covering the tests generally required to verify the safety of electrical installations in compliance with IEC 61557.
Measurement functions. The instrument performs loop and fault current measurements with fault current ranges of 2000 A and 20 kA, 3- or 4-wire earth resistance measurements, insulation measurements at 250 V, 500 V and 1000 V DC, and mains voltage and frequency measurement. Resistance ranges are 20 Ω, 200 Ω and 2000 Ω with autoranging.
Residual current testing. RCD tests cover standard, selective, AC and A types, with trip current settings from 10 to 1000 mA depending on the selected ratio. D-Lok technology prevents tripping of most passive type RCDs during loop testing.
Memory and communication. Test results are stored in the on-board memory and downloaded to a computer or printer through the infrared communication port (IrDA), with the 8210 IrDA adaptor supplied as an accessory.
Power and environment. The instrument runs on 8 × 1.5 V R6 or LR6 batteries, offers auto power off and backlit display, and is rated IP54. It complies with IEC 61010-1 CAT III 300 V, pollution degree 2.
Use. The tester suits the verification of electrical installations, its software-driven interface guiding the user through the required test sequence, and it ships in a holdall with accessories including test leads, auxiliary earth spikes and an external earth probe.
No published question about this part yet. Questions are reviewed before publication.
Every characteristic recorded for MODEL_6015, with where it comes from. Use the filters to find one quickly.
| Characteristic | Value |
|---|---|
| Dimensions | 105(L) × 210(W) × 240(D)mm |
| Output voltage | 50V peak to peak square wave |
| Accessories | 7098 (Distribution board test leads for Loop/PSC/RCD testing ); 7099 (Moulded plug test leads(1 set) for Loop and RCD testing at sockets(EU plug) )*; 7025 (Lead for insulation and continuity testing); 7109 (Earth resistance test leads (1 set)); KSLP5 (external earth probe); 8032 (auxiliary earth spikes); 8210 (IrDA Adaptor); Durable Holdall; Accessory pouch; Battery 8 × 1.5V R6 or LR6; Instruction Manual |
| Accuracy | ±(1.5%rdg+3dgt) |
| Base Accuracy | 20Ω range; ±(2%rdg+2dgt) D-LOK OFF; ±(5%rdg+5dgt) D-LOK ON |
| Fault Current Ranges | 2000A and 20kA |
| Frequency | 720Hz ±5% |
| Impedance Ranges | 20/200/2000&Omega |
| Measuring ranges | 20/200/2000Ω Autoranging |
| Nominal Test Current | 25A (20Ω range) 1.2A (200Ω range) 1.2A (2000Ω range) |
| Open circuit voltage | >6V |
| Output voltage on open circuit | 250V+20%-0%; 500V+20%-0%; 1000V+20%-0% |
| Power Source | 8 × 1.5V R6 or LR6 |
| Product Catalog | MODEL 6015 Product Catalog (English)(1.43 MB) |
| PSC Ranges | 2000A and 20kA |
| Ranges | 20Ω /200Ω /2000&Omega |
| Rated Current | >1mA |
| Rated Voltage | 230V AC ±10% [50Hz] |
| Safety Standard | IEC 61010-1 CAT III 300V Pollution Degree 2 |
| Short Circuit Current | >200mA DC |
| Test Period | 1/2 cycle (10ms) |
| Test voltage | 250V, 500Vand 1000V DC |
| Trip Current Duration | RCD × 1/2 × 1: 2000ms; RCD × 5: 200ms fast trip 50ms |
| Trip Current Settings | RCD × 1/2 : 10,30,100,300,500,1000mA; RCD × 1 : 10,30,100,300,500,1000mA; RCD × 5 : 10,30,100mA |
| Voltage Measuring Range | 100 - 400V AC [50Hz] |
| Weight | 1924g approx. |
| Withstand Voltage | 3700V AC for 1 minute |
No specification matches.
Last verification : 2026-11-03
Official documents and the technical data recorded for MODEL_6015. For a missing document or a specific revision, our experts send it to you.
Kyoritsu MODEL 6015 multi-function tester for verifying the safety of electrical installations, compliant with IEC 61557, with on-board memory and IrDA infrared port.
| Parameter | Value |
|---|---|
| Dimensions | 105(L) × 210(W) × 240(D)mm |
| Output voltage | 50V peak to peak square wave |
| Accessories | 7098 (Distribution board test leads for Loop/PSC/RCD testing ); 7099 (Moulded plug test leads(1 set) for Loop and RCD testing at sockets(EU plug) )*; 7025 (Lead for insulation and continuity testing); 7109 (Earth resistance test leads (1 set)); KSLP5 (external earth probe); 8032 (auxiliary earth spikes); 8210 (IrDA Adaptor); Durable Holdall; Accessory pouch; Battery 8 × 1.5V R6 or LR6; Instruction Manual |
| Accuracy | ±(1.5%rdg+3dgt) |
| Base Accuracy | 20Ω range; ±(2%rdg+2dgt) D-LOK OFF; ±(5%rdg+5dgt) D-LOK ON |
| Fault Current Ranges | 2000A and 20kA |
| Frequency | 720Hz ±5% |
| Impedance Ranges | 20/200/2000&Omega |
| Measuring ranges | 20/200/2000Ω Autoranging |
| Nominal Test Current | 25A (20Ω range) 1.2A (200Ω range) 1.2A (2000Ω range) |
| Open circuit voltage | >6V |
| Output voltage on open circuit | 250V+20%-0%; 500V+20%-0%; 1000V+20%-0% |
| Power Source | 8 × 1.5V R6 or LR6 |
| Product Catalog | MODEL 6015 Product Catalog (English)(1.43 MB) |
| PSC Ranges | 2000A and 20kA |
| Ranges | 20Ω /200Ω /2000&Omega |
| Rated Current | >1mA |
| Rated Voltage | 230V AC ±10% [50Hz] |
| Safety Standard | IEC 61010-1 CAT III 300V Pollution Degree 2 |
| Short Circuit Current | >200mA DC |
| Test Period | 1/2 cycle (10ms) |
| Test voltage | 250V, 500Vand 1000V DC |
| Trip Current Duration | RCD × 1/2 × 1: 2000ms; RCD × 5: 200ms fast trip 50ms |
| Trip Current Settings | RCD × 1/2 : 10,30,100,300,500,1000mA; RCD × 1 : 10,30,100,300,500,1000mA; RCD × 5 : 10,30,100mA |
| Voltage Measuring Range | 100 - 400V AC [50Hz] |
| Weight | 1924g approx. |
| Withstand Voltage | 3700V AC for 1 minute |
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
10-function multi-function installation tester

MODEL 6011A

MODEL

KEW

Describe your application and constraints in a request.
What is recorded about the regulatory status and the life of this part.
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
| Current status | Status not stated |
| Key dates | Not recorded |
| Manufacturer part number | MODEL_6015 |
| Manufacturer | Kyoritsu |
Installation and Earth Testers
Single and three-phase ZigBee electrical metering module · Ref. : POPULAR-DESIGN-FOR-CHINA-DIGITAL-CLAMP-EARTH-RESISTANCE-TESTER-METER-PRICE-PRODU
Price on request
Installation and Earth Testers
Multifunction installation tester with loop and RCD testing · Ref. : KEW_6016
Price on request
Installation and Earth Testers
Advanced earth resistance and soil resistivity tester · Ref. : UT572
Price on request
Installation and Earth Testers
Residual current device (RCD) tester with trip time measurement · Ref. : KEW_5410
Price on request
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details