MODEL 6015 – 10-function multi-function installation tester

10-function multi-function installation tester

Installation and Earth Testers

  • 100 - 400V AC [50Hz]
  • 2000A and 20kA
  • >1mA
  • >200mA DC
Manufacturer part number
MODEL_6015
Manufacturer
Kyoritsu
Voltage Measuring Range
100 - 400V AC [50Hz]
Fault Current Ranges
2000A and 20kA

Kyoritsu MODEL 6015 multi-function tester for verifying the safety of electrical installations, compliant with IEC 61557, with on-board memory and IrDA infrared port.

Product overview

Overview. The Kyoritsu MODEL 6015 is a multi-function installation tester able to perform ten separate test functions, covering the tests generally required to verify the safety of electrical installations in compliance with IEC 61557.

Measurement functions. The instrument performs loop and fault current measurements with fault current ranges of 2000 A and 20 kA, 3- or 4-wire earth resistance measurements, insulation measurements at 250 V, 500 V and 1000 V DC, and mains voltage and frequency measurement. Resistance ranges are 20 Ω, 200 Ω and 2000 Ω with autoranging.

Residual current testing. RCD tests cover standard, selective, AC and A types, with trip current settings from 10 to 1000 mA depending on the selected ratio. D-Lok technology prevents tripping of most passive type RCDs during loop testing.

Memory and communication. Test results are stored in the on-board memory and downloaded to a computer or printer through the infrared communication port (IrDA), with the 8210 IrDA adaptor supplied as an accessory.

Power and environment. The instrument runs on 8 × 1.5 V R6 or LR6 batteries, offers auto power off and backlit display, and is rated IP54. It complies with IEC 61010-1 CAT III 300 V, pollution degree 2.

Use. The tester suits the verification of electrical installations, its software-driven interface guiding the user through the required test sequence, and it ships in a holdall with accessories including test leads, auxiliary earth spikes and an external earth probe.

See all specifications

Highlights

  • Dimensions: 105(L) × 210(W) × 240(D)mm
  • Output voltage: 50V peak to peak square wave
  • Accuracy: ±(1.5%rdg+3dgt)
  • Fault Current Ranges: 2000A and 20kA
  • Frequency: 720Hz ±5%
  • Impedance Ranges: 20/200/2000&Omega

Technical questions

Ask a question

No published question about this part yet. Questions are reviewed before publication.