MODEL 6050 – Multifunction installation tester for loop and RCD

Multifunction installation tester for loop and RCD

Installation and Earth Testers

  • 200/2000A/20kA
  • 300 memory locations
  • 20/200/2000&Omega
  • RCD (without DC); LOOP
Manufacturer part number
MODEL_6050
Manufacturer
Kyoritsu
Memory
300 memory locations

The Kyoritsu MODEL 6050 is a multifunction installation tester performing loop impedance measurements and residual current device (RCD) tests, with built-in memory.

Product overview

Overview. The Kyoritsu MODEL 6050 is a multifunction installation tester (loop and RCD tester) with microprocessor technology, designed for electrical installation inspections. The manufacturer lists this product as discontinued.

Loop measurements. Loop impedance ranges of 20, 200 and 2000 Ω, with a resolution of 0.01 Ω on the 20 Ω range. Tests on the 200 and 2000 Ω ranges use a test current of 15 mA, which does not trip RCDs rated 30 mA or more. Maximum test current of 3 A on the 20 Ω range. Direct reading of prospective short-circuit current (PSC) and earth fault current, on the 200 A, 2000 A and 20 kA ranges. Contact voltage (UC) reading with two selectable limits, 50 V and 25 V.

RCD tests. Testing of AC, A, standard and selective RCD types. Test currents from 10 to 1000 mA depending on type and multiplier (× 1/2, × 1, × 5), RCD ramp test from 20% to 110% of IΔn to indicate the actual tripping current, and tests at 0° and 180° phase angle.

Memory and data transfer. 300 memory locations. Stored data can be transferred to a PC via the 8212-RS232C or 8212-USB optical adapter, with PC software available as an option.

Operating conditions. Designed to IEC 61010-1 (CAT III 300 V) and IEC 61557, protection degree IP54. Voltage test range of 100 to 260 V (50 Hz), working voltage of 230 V +10%/−15% for RCD tests, and 230 V or 400 V (+10%/−15%) for 200/2000 Ω loop tests.

Use. Intended for electrical installation inspections, including verification of fault loops, residual current devices and earth electrodes. Available on quotation from Atlas Electronics.

See all specifications

Highlights

  • Loop Impedance Ranges; (Z reading): 20/200/2000&Omega
  • Memory: 300 memory locations
  • PC Software, Connection Cable: optional with 8212-USB, 8212-RS232C
  • Product Catalog: MODEL 6050 Product Catalog (English)(1.43 MB)
  • PSC / Earth Fault Current Ranges: 200/2000A/20kA
  • RCD Test A Type; (Standard and Selective): 10, 30, 100, 300, 500mA

Technical questions

Ask a question

No published question about this part yet. Questions are reviewed before publication.

Request a quote