The Kyoritsu MODEL 6050 is a multifunction installation tester performing loop impedance measurements and residual current device (RCD) tests, with built-in memory.
PSC / Earth Fault Current Ranges200/2000A/20kA
Memory300 memory locations
RCD Ramp TestFrom 20% to 110% of IΔ n (AC type)
RCD Test AC Type; (Standard and Selective) — Auto Ramp10, 30, 100, 300, 500mA
Loop Impedance Ranges; (Z reading)20/200/2000&Omega
PC Software, Connection Cableoptional with 8212-USB, 8212-RS232C
Product overview
Overview. The Kyoritsu MODEL 6050 is a multifunction installation tester (loop and RCD tester) with microprocessor technology, designed for electrical installation inspections. The manufacturer lists this product as discontinued.
Loop measurements. Loop impedance ranges of 20, 200 and 2000 Ω, with a resolution of 0.01 Ω on the 20 Ω range. Tests on the 200 and 2000 Ω ranges use a test current of 15 mA, which does not trip RCDs rated 30 mA or more. Maximum test current of 3 A on the 20 Ω range. Direct reading of prospective short-circuit current (PSC) and earth fault current, on the 200 A, 2000 A and 20 kA ranges. Contact voltage (UC) reading with two selectable limits, 50 V and 25 V.
RCD tests. Testing of AC, A, standard and selective RCD types. Test currents from 10 to 1000 mA depending on type and multiplier (× 1/2, × 1, × 5), RCD ramp test from 20% to 110% of IΔn to indicate the actual tripping current, and tests at 0° and 180° phase angle.
Memory and data transfer. 300 memory locations. Stored data can be transferred to a PC via the 8212-RS232C or 8212-USB optical adapter, with PC software available as an option.
Operating conditions. Designed to IEC 61010-1 (CAT III 300 V) and IEC 61557, protection degree IP54. Voltage test range of 100 to 260 V (50 Hz), working voltage of 230 V +10%/−15% for RCD tests, and 230 V or 400 V (+10%/−15%) for 200/2000 Ω loop tests.
Use. Intended for electrical installation inspections, including verification of fault loops, residual current devices and earth electrodes. Available on quotation from Atlas Electronics.
The Kyoritsu MODEL 6050 is a multifunction installation tester performing loop impedance measurements and residual current device (RCD) tests, with built-in memory.
PSC / Earth Fault Current Ranges200/2000A/20kA
Memory300 memory locations
RCD Ramp TestFrom 20% to 110% of IΔ n (AC type)
RCD Test AC Type; (Standard and Selective) — Auto Ramp10, 30, 100, 300, 500mA
Loop Impedance Ranges; (Z reading)20/200/2000&Omega
2. Datasheet extract (recorded values)
Parameter
Value
Loop Impedance Ranges; without tripping RCDs
200 and 2000Ω with 15mA of test current
Loop Impedance Ranges; (Z reading)
20/200/2000&Omega
Max test current on Loop ranges
3A (20Ω ) / 15mA (200 and 2000Ω )
Memory
300 memory locations
PC Software, Connection Cable
optional with 8212-USB, 8212-RS232C
Phase and Earth; (2 wires only) measurements
RCD (without DC); LOOP
Product Catalog
MODEL 6050 Product Catalog (English)(1.43 MB)
PSC / Earth Fault Current Ranges
200/2000A/20kA
RCD Ramp Test
From 20% to 110% of IΔ n (AC type)
RCD Test A Type; (Standard and Selective)
10, 30, 100, 300, 500mA
RCD Test AC Type; (Standard and Selective) — × 1
10, 30, 100, 300, 500, 1000mA
RCD Test AC Type; (Standard and Selective) — × 1/2
10, 30, 100, 300, 500, 1000mA
RCD Test AC Type; (Standard and Selective) — × 5
10, 30, 100mA
RCD Test AC Type; (Standard and Selective) — Auto Ramp
10, 30, 100, 300, 500mA
RCD Test Currents multipliers
× 1/2, × 1, × 5; (max 1000mA type AC); (max 500mA type A)
RCD Test Time Duration
1000ms: × 1/2, × 1, DC; 200ms: × 5, DC (500mA), and × 1 (1000mA)
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productKyoritsu
MODEL_6050
Multifunction installation tester for loop and RCD
PSC / Earth Fault Current Ranges
200/2000A/20kA
Memory
300 memory locations
RCD Ramp Test
From 20% to 110% of IΔ n (AC type)
RCD Test AC Type; (Standard and Selective) — Auto Ramp
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details