Macnman LCO2. LoRaWAN NDIR CO₂, temperature and humidity sensor — The Macnman LCO2 is a LoRaWAN NDIR sensor that measures CO₂, temperature and humidity at the same point and instant, over a single LoRaWAN connection.
Measurement. CO₂ ranges of 400–2,000 ppm (X1) or 400–5,000 ppm (X2), accuracy ±(50 ppm + 5 %), repeatability ±10 ppm, T90 response time ≤60 s. Temperature and humidity measured to ±0.3 °C (0–70 °C) and ±3 % RH.
Thresholds and reporting. Configurable CO₂ threshold triggering an immediate uplink, sampling interval from 1 minute to 24 hours and periodic, event-based or hybrid reporting modes, set through the Maya app over BLE or by downlink.
LoRaWAN. LoRaWAN v1.0.4 Class A by default, Class C selectable, OTAA activation, IN865 band and six other regional bands, compatible with TTN, ChirpStack, MQTT, Orbiwise, Netmore or private network servers.
Power and environment. 19 Ah Li-SOCl₂ battery (about 7 years at hourly reporting, estimate) or 9–36 V DC supply. IP65 enclosure (IP67 option), enclosure operating range −40 °C to +80 °C, weight about 175 g. WPC and RoHS compliant, designed and made in Pune, India.
Uses. Offices, classrooms, hospitals, warehouses, plant rooms and stores where CO₂ serves as the ventilation signal. The sensor is not a certified gas detector and is not suited to life-safety detection or to controlled-atmosphere fruit stores at 2–4 % CO₂.