R718N1100DE – Single-Phase Wireless Current Meter with 1000A Clamp

Single-Phase Wireless Current Meter with 1000A Clamp

Environmental Sensor Nodes

  • -20°C to +55 °C
  • -20 ℃ to +50 ℃
  • -40°C to +85°C
  • 10A – 1000A
Manufacturer part number
R718N1100DE
Manufacturer
Netvox
Ambient temperature range
-20°C to +55 °C
Operating Temperature
-20 ℃ to +50 ℃

Netvox R718N1100DE single-phase wireless current meter with a detachable 1000A clamp-on current transformer, measuring alternating current on a conductor and transmitting data over LoRaWAN.

Product overview

Overview. The Netvox R718N1100DE is a single-phase current meter that measures alternating current up to 1000A. The clamp-on current transformer is fitted around a conductor, measurement is made without direct contact, and data is sent to the gateway through an integrated LoRaWAN module.

Main characteristics. Measurement range from 10A to 1000A, accuracy of 0.5%, resolution of 1mA and saturation current of 1000A. The transformer ratio is 2000:1 with a rated secondary current of 500mA.

Interfaces and connectivity. SX1276 LoRaWAN-compatible module with built-in antenna and a communication range of 10 km line of sight. LoRa or FSK modulation, receiving sensitivity of -136dBm in LoRa, available bands EU863-870, US902-928, AU915-928, KR920-923, AS923, IN865-867 and CN470-510, to be configured before shipment. Third-party platforms Actility/ThingPark, TTN and MyDevices/Cayenne are supported.

Power and environment. DC 3.3V/1A power supply, power consumption of 0.5W or less. Main body rated IP53, sensor IP30. Operating temperature from -20 °C to +50 °C, ambient humidity below 90% RH without condensation, flame-retardant UL 94-V0 case material. RoHS compliant, CE and UL certified.

Mounting. Screw or magnet mounting, detachable sensor cable of about 1200mm, main body weight of about 141g. Main body dimensions 112 mm x 88.19 mm x 32 mm.

See all specifications

Highlights

  • Accuracy: 0.5%
  • Ambient Humidity Range: <90%RH (No condensation)
  • Ambient temperature range: -20°C to +55 °C
  • Antenna Type: Built-in antenna
  • Case Material: Flame Retardant Grade 94-V0 UL Material
  • Clamp-On CT Accuracy: 0.5%

Typical applications

Derived from the part category, not a compatibility statement.

Good to know before integrating

  • Thermal: rated operating range -20 ℃ to +50 ℃ — check it against the installation environment.
  • Thermal: rated operating range -20 ℃ to +50 ℃ — check it against the installation environment.

See also

Technical questions

Ask a question

No published question about this part yet. Questions are reviewed before publication.

Request a quote