| CAN baud rate | 5K ~ 1000Kbps, |
| CAN — Pin | H: CAN_H signal; L: CAN_L signal; GND: CAN ground signal |
| Catalog — Parameters | Value |
| Ethernet Port — Default IP | 192.168.0.7 |
| Ethernet Port — EtherCAT | 2× EtherCAT ports (IN/OUT), 10/100Mbps auto-negotiation, integrated switch functoin |
| Ethernet Port — Ethernet | 1× RJ45 port (10/100Mbps, auto MDI/MDIX) |
| Ethernet Port — Gateway IP | 192.168.0.1 |
| Ethernet Port — PROFINET | 2×PROFINET (P1, P2), 10/100Mbps auto-negotiation, integrated switch function |
| Other Interface — Indicators | PWR, WORK, 485, ECAT |
| Other Interface — Reload Button | Press for 3–15s to restore factory settings |
| Other Interface — Type-C | Debugging interface for troubleshooting |
| Physical Parameters — Dimension | 120×85×30mm (without terminals/rail); 137.3×30×109.3mm (with terminals/rail) |
| Physical Parameters — EMC Protection | IEC 61000-4-2(ESD): 6kV contact, 8kV air; IEC 61000-4-5(Surge): 2kV common mode, 1kV differential mode for power; 2kV for Ethernet/RS485; IEC 61000-4-4(EFT): 2kV for power, 1kV for Ethernet/RS485 |
| Physical Parameters — Installation | DIN rail mounting, aluminum housing |
| Physical Parameters — Isolation | Isolation for both serial, Ethernet, CAN, and power |
| Physical Parameters — Operating Humidity | 5%–95% (non-condensing) |
| Physical Parameters — Operating Temperature | -40°C to +85°C |
| Physical Parameters — Storage Temperature | -40°C to +105°C (non-condensing) |
| Power Supply — Connector | 5.08×2P pluggable terminal block with anti-reverse and screw lock |
| Power Supply — Power Input | 9-36V DC, 12V/1A is recommended |
| Power Supply — Working Current | Idle: 158mA/12V (avg), 163mA/12V (max); Full load: 162mA/12V (avg), 165mA/12V (max) |
| RS485 Interface — Baud Rate | 600~230.4K bps |
| RS485 Interface — Connector | 3.81×3P pluggable terminal block with screw lock |
| RS485 Interface — Parity bit | None, Odd, Even |
| RS485 Interface — Pin | A (RS485 A), B (RS485 B), G (GND) |
| RS485 interface — Stop bit | 1, 2 |
| Software — CAN | Supports up to 127 CANopen slave devices, supporting up to 128 configurable SDO groups |
| Software — EtherCAT protocol | Up to 128 TXPDO and 128 RXPDO groups in EtherCAT, with 128 variables per group |
| Software — FROFINET | 16 slot, up to 1400 input bytes and 1400 output bytes |
| Software — Modbus | Supports custom slave devices and point table information, edge data collection and computation for up to 2,000 data points |
| Software — Modbus protocol | Edge data collection and computation for up to 2,000 data points |
| Software — PROFINET protocol | Supports 16 slots, up to 1400 input/output bytes |
| Software — Protocol | EtherCAT slave to Modbus RTU/TCP master |
| Software — Setup | Setup tool on PC |