Reallin D3132 three-phase three-wire DIN rail energy meter for active and reactive energy measurement on 3x230/400 V networks, with RS485 output.
Temperature rangeoperation:-40-70℃; storage:-40-85℃
Voltage Range70%un~140%un
Communication interfaceRS485 port,up to 38400 bps
Current circuit apparent power at Ib<1VA
Maximum current Imax80A
Minimum Current (Imin)0.25A
Product overview
Overview. The Reallin D3132 is a three-phase three-wire DIN rail energy meter from Reallin, designed to measure active and reactive energy on a 3x230/400 V, 50 Hz three-phase network, with a reference current Ib of 5 A and a maximum current Imax of 80 A.
Main characteristics. The meter offers class B/1.0 accuracy for active energy and class 2.0 for reactive energy, a starting current Ist of 0.4% Ib and a voltage range of 70% Un to 140% Un. Its dimensions are 90 × 52.5 × 62 mm and it weighs about 0.3 kg. The dot matrix LCD display supports backlighting, and an LED pulsating indicator shows a meter constant of 1000 imp/kWh and 1000 imp/kvarh.
Interfaces and connectivity. The meter provides an RS485 port with communication up to 38400 bps.
Power and environment. Voltage circuit consumption is at most 1.5 W / 8 VA and current circuit apparent power at Ib is below 1 VA. The meter operates between -40 °C and 70 °C and can be stored between -40 °C and 85 °C. Its protection degree is IP51 in a protective enclosure and its insulation class is II.
Standards. The D3132 complies with EN 50470-3:2022, IEC 62053-21/23:2020, IEC 62052-31:2015, UL61010-1 and UL61010-2-030.
Typical uses and integration. Thanks to its RS485 port, the meter can be connected to a supervision system or a PLC to transmit energy measurements. Its DIN rail mounting simplifies integration into electrical cabinets. This product is available on quotation from Atlas Electronics.
Reallin D3132 three-phase three-wire DIN rail energy meter for active and reactive energy measurement on 3x230/400 V networks, with RS485 output.
Temperature rangeoperation:-40-70℃; storage:-40-85℃
Voltage Range70%un~140%un
Communication interfaceRS485 port,up to 38400 bps
Current circuit apparent power at Ib<1VA
Maximum current Imax80A
2. Datasheet extract (recorded values)
Parameter
Value
Accuracy
class B/1.0 for active; class 2.0 for reactive
Communication interface
RS485 port,up to 38400 bps
Current circuit apparent power at Ib
<1VA
Dimension(L×W ×D)
90×52.5×62mm
Insulation Class
II
LCD display
Dot Matrix type,backlight supported
Maximum current Imax
80A
Minimum Current (Imin)
0.25A
port ection Degree
IP51 in protective enclosure
Pulsating Indicator
LED
Pulsating(meter constant)
1000 imp/kwh; 1000 imp/kvarh
Rated Frequency Fn
50HZ
Rated Voltage Un
3x230/400v
Reference current Ib
5A
Standards
EN 50470-3:2022,IEC 62053-21/23:2020,IEC 62052-31:2015,UL61010-1,UL61010-2-030
Starting Current (Ist)
0.4%Ib
Temperature range
operation:-40-70℃; storage:-40-85℃
Type
Three phase Three wire DIN Rail Meter--D3132
voltage circuit active lap parent power atun
≤ 1.5W/8VA
Voltage Range
70%un~140%un
Weight Of Meter
About 0.3kg
Applications and use cases
Architectures in which 271507676 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
A building’s energy, comfort and occupancy data sit in separate systems. Sensors, meters and gateways feed one model of the building, room by room, to compare scenarios and steer the installations
To check
Data model and building plans available
Software platform hosting the twin
Sensor density needed for a useful model
Associated system blocks
SensorsMetersGateways
Need a complete solution?
Send a request for 271507676 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productReallin
271507676
Three-phase three-wire DIN rail energy meter with RS485 output
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details