Three-phase energy meter for DIN rail mounting, class B/1.0 for active and 2.0 for reactive energy, with 80A maximum current and RS485 output for energy monitoring.
Temperature rangeoperation:-40-70℃
Voltage Range70%un~140%un
Communication interfaceRS485 port,up to38400 b ps
Current circuit apparent power at Ib<1VA
Maximum current Imax80A
Minimum Current (Imin)0.25A
Product overview
Overview. The Reallin 3 Phase Din Rail Meter is a three-phase DIN rail energy meter, class B/1.0 for active energy and 2.0 for reactive energy, designed to measure consumption in 3x230/400V installations at 50Hz.
Main characteristics. Reference current Ib of 5A, maximum current Imax of 80A and minimum current Imin of 0.25A. Starting current is 0.4% Ib and the permitted voltage range is 70% to 140% of Un. The dot matrix LCD display supports backlight and an LED indicates pulses. The meter constant is 1000 imp/kWh and 1000 imp/kvarh.
Interfaces and connectivity. The meter has an RS485 port up to 38400 bps, allowing connection to a supervision system or data collector.
Power and environment. Voltage circuit consumption is 1.5W/8VA or less and current circuit apparent power is less than 1VA at Ib. Operating temperature range from -40 to 70℃. Protection degree IP51 in a protective enclosure. Insulation class II. Weight about 0.3 kg, dimensions 90 x 52.5 x 62 mm.
Standards. Compliant with EN 50470-3:2022, IEC 62053-21/23:2020, IEC 62052-31:2015, UL61010-1 and UL61010-2-030.
Typical uses. Measurement and monitoring of electricity consumption in three-phase installations, and integration into an energy management system through the pulse output and the RS485 port.
Three-phase energy meter for DIN rail mounting, class B/1.0 for active and 2.0 for reactive energy, with 80A maximum current and RS485 output for energy monitoring.
Temperature rangeoperation:-40-70℃
Voltage Range70%un~140%un
Communication interfaceRS485 port,up to38400 b ps
Current circuit apparent power at Ib<1VA
Maximum current Imax80A
2. Datasheet extract (recorded values)
Parameter
Value
Accuracy
class B/1.0 for active; class 2.0 for reactive
Communication interface
RS485 port,up to38400 b ps
Current circuit apparent power at Ib
<1VA
Dimension(LXW XD)
90x52.5x62mm
Insulation Class
II
LCD display
Dot Matrix type,backlight supported
Maximum current Imax
80A
Minimum Current (Imin)
0.25A
port ect ion Degree
IP51 in protective enclosure
Pulsating Indicator
LED
Pulsating(meter constant)
1000 imp/kwh; 1000 imp/kvarh
Rated Frequency Fn
50HZ
Rated Voltage Un
3x230/400v
Reference current Ib
5A
Standards
EN 50470-3:2022,IEC 62053-21/23:2020,IEC 62052-31:2015,UL61010-1,UL61010-2-030
Starting Current (Ist)
0.4%Ib
Temperature range
operation:-40-70℃
voltage circuit active lap parent power atun
≤ 1.5W/8VA
Voltage Range
70%un~140%un
Weight Of Meter
About0.3kg
Applications and use cases
Architectures in which 274489035 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
A building’s energy, comfort and occupancy data sit in separate systems. Sensors, meters and gateways feed one model of the building, room by room, to compare scenarios and steer the installations
To check
Data model and building plans available
Software platform hosting the twin
Sensor density needed for a useful model
Associated system blocks
SensorsMetersGateways
Need a complete solution?
Send a request for 274489035 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details