Single phase two-wire energy meter in DIN rail format for measuring electricity consumption on single-phase 240 V circuits, 5 A reference current, 60 Hz.
Temperature rangeOperation:-30~70℃
Voltage Range80%Un~120%Un
Current circuit apparent power at Ib<1VA
Maximum current Imax100A
Minimum Current (Imin)0.25A
Reference current Ib5A
Product overview
Reallin single phase energy meter. The Single Phase Two Wire Din Rail Energy Meter from manufacturer Reallin is an active and reactive energy meter for single-phase two-wire AC circuits. It mounts on a DIN rail in distribution boxes.
Main characteristics. Accuracy class B/1.0 for active energy and class 2.0 for reactive energy. Rated voltage Un of 240 V, reference current Ib of 5 A, maximum current Imax of 100 A, minimum current of 0.25 A and rated frequency of 60 Hz. 6-digit LCD display and LED pulsating indicator. Meter constant of 1000 imp/kWh and 1000 imp/kvarh.
Interfaces and connectivity. RS485 communication port with screw terminals, up to 115200 bps. The pulse output allows connection to a PLC or collector for secondary data acquisition or automatic control.
Power and environment. The meter draws its power directly from the circuit under test, with no additional power supply. Operating voltage range of 80% to 120% of Un. Operating temperature from -30 to 70 °C. Protection degree IP51 in protective enclosure. Dimensions 98.1 × 36.6 × 65 mm, weight about 0.16 kg.
Standards. Compliant with EN 50470-3:2022, IEC 62053-21/23:2020, IEC 62052-11:2020, IEC 62052-31:2015, UL61010-1 and UL61010-2-030.
Typical uses. Energy measurement on single-phase circuits in residential, commercial and low-power industrial installations, with data reporting to a supervision system via RS485.
Single phase two-wire energy meter in DIN rail format for measuring electricity consumption on single-phase 240 V circuits, 5 A reference current, 60 Hz.
Temperature rangeOperation:-30~70℃
Voltage Range80%Un~120%Un
Current circuit apparent power at Ib<1VA
Maximum current Imax100A
Minimum Current (Imin)0.25A
2. Datasheet extract (recorded values)
Parameter
Value
Accuracy
Class B/1.0 for active; Class 2.0 for reactive
Communication interface
RS485 with screw type,maximum upto 115200bps
Current circuit apparent power at Ib
<1VA
Dimension(LxWxD)
98.1×36.6×65mm
Insulation Class
II
LCD display
6 digits
Maximum current Imax
100A
Minimum Current (Imin)
0.25A
Portection Degree
IP51 in protective enclosure
Pulsating Indicator
LED
Pulsating(meter constant)
1000imp/kWh; 1000imp/kvarh
Rated Frequency Fn
60Hz
Rated Voltage Un
240V
Reference current Ib
5A
Standards
EN 50470-3:2022,IEC 62053-21/23:2020,IEC 62052-11:2020,IEC 62052-31:2015,UL61010-1,UL61010-2-030
Starting Current (Ist)
0.4%lb
Temperature range
Operation:-30~70℃
Voltage circuit active/apparent power at Un
<1.5W/8VA
Voltage Range
80%Un~120%Un
Weight Of Meter
About 0.16kg
Applications and use cases
Architectures in which 274812819 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
A building’s energy, comfort and occupancy data sit in separate systems. Sensors, meters and gateways feed one model of the building, room by room, to compare scenarios and steer the installations
To check
Data model and building plans available
Software platform hosting the twin
Sensor density needed for a useful model
Associated system blocks
SensorsMetersGateways
Need a complete solution?
Send a request for 274812819 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details