Single phase energy meter for 35 mm DIN rail, measuring active and reactive energy with an RS485 output for consumption monitoring.
Temperature rangeOperation:-30~70℃; Storage:-40~85℃
Voltage Range80%Un~120%Un
Current circuit apparent power at Ib<1VA
Maximum current Imax65A
Minimum Current (Imin)0.25A
Reference current Ib5A
Product overview
Reallin D1006-BF. single phase DIN rail smart energy meter for measuring active and reactive energy on single phase networks.
Main characteristics. Reference current Ib 5 A, maximum current Imax 65 A, minimum current 0.25 A and starting current 0.4% Ib. Accuracy class B/1.0 for active energy and class 2.0 for reactive energy. Rated voltage 230 V/240 V, voltage range 80% Un to 120% Un, rated frequency 50/60 Hz. 6+4 digit LCD display and LED pulse indicator, meter constant 1000 imp/kWh and 1000 imp/kvarh. Dimensions 90 × 35 × 62 mm, weight about 0.13 kg.
Interfaces and connectivity. RS485 communication interface with screw terminals, up to 115200 bps, suited to high-frequency meter reading systems and energy consumption monitoring platforms.
Power and environment. Voltage circuit consumption below 1.5 W / 8 VA at Un, current circuit apparent power below 1 VA at Ib. Operating temperature -30 to 70 °C, storage temperature -40 to 85 °C. Protection degree IP51 in protective enclosure, insulation class II.
Standards. EN 50470-3:2022, IEC 62053-21/23:2020, IEC 62052-11:2020, IEC 62052-31:2015, UL61010-1 and UL61010-2-030.
Typical uses. Monitoring of grid-connected photovoltaic production, consumption statistics for small loads and energy-saving renovation projects, thanks to the low starting current.
Single phase energy meter for 35 mm DIN rail, measuring active and reactive energy with an RS485 output for consumption monitoring.
Temperature rangeOperation:-30~70℃; Storage:-40~85℃
Voltage Range80%Un~120%Un
Current circuit apparent power at Ib<1VA
Maximum current Imax65A
Minimum Current (Imin)0.25A
2. Datasheet extract (recorded values)
Parameter
Value
Accuracy
Class B/1.0 for active; Class 2.0 for reactive
Communication interface
RS485 with screw type,maximum upto 115200bps
Current circuit apparent power at Ib
<1VA
Dimension(LxWxD)
90×35×62mm
Insulation Class
II
LCD display
6+4 digits
Maximum current Imax
65A
Minimum Current (Imin)
0.25A
Protection degree
IP51 in protectve enclosure
Pulsating Indicator
LED
Pulsating(meter constant)
1000imp/kWh; 1000imp/kvarh
Rated Frequency Fn
50/60Hz
Rated Voltage Un
230V/240V
Reference current Ib
5A
Standards
EN 50470-3:2022,IEC 62053-21/23:2020,IEC 62052-11:2020,; IEC 62052-31:2015,UL61010-1,UL61010-2-030
Starting Current (Ist)
0.4%Ib
Temperature range
Operation:-30~70℃; Storage:-40~85℃
Voltage circuit active/apparent power at Un
<1.5W/8VA
Voltage Range
80%Un~120%Un
Weight Of Meter
About 0.13kg
Applications and use cases
Architectures in which 286096131 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
A building’s energy, comfort and occupancy data sit in separate systems. Sensors, meters and gateways feed one model of the building, room by room, to compare scenarios and steer the installations
To check
Data model and building plans available
Software platform hosting the twin
Sensor density needed for a useful model
Associated system blocks
SensorsMetersGateways
Need a complete solution?
Send a request for 286096131 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productReallin
286096131
Single phase DIN rail energy meter, active and reactive measurement
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details