Reallin three-phase smart energy meter for 3x230/400 V four-wire networks, measuring active and reactive energy in outdoor installations.
Storage Temperature-40℃ ~ +85℃
Altitude≤ 3000m
ApplicationOutdoor
Fn50Hz; Frequency Range: 0.98fn ~ 1.02fn
Ib5A
Imax100A
Product overview
Overview. The Reallin three-phase smart energy meter is a three-phase four-wire energy meter designed for 3x230/400 V networks. It measures active and reactive energy by sampling voltage and current on the three phases, without sampling the neutral.
Main characteristics. Nominal voltage 3x230/400 V with an operating voltage range of 80% to 115% of Un. Basic current Ib of 5 A and maximum current Imax of 100 A. Nominal frequency 50 Hz with a range of 0.98 fn to 1.02 fn. Meter constant of 1000 imp/kWh for active energy and 1000 imp/kvarh for reactive energy.
Accuracy. Class 1.0 for active power and Class 2.0 for reactive power. Insulation grade Class II.
Environment. IP54 protection and outdoor application. Operating temperature from -25 ℃ to +70 ℃ and storage temperature from -40 ℃ to +85 ℃. Operating humidity 95%. Altitude up to 3000 m. At -40 ℃, the effect of temperature error meets IEC standards; display and communication requirements are not considered at this temperature.
Installation. Wiring type BS, single-phase measurement not supported.
Typical uses. Energy metering on three-phase four-wire installations, with accuracy suited to billing and consumption monitoring.
Reallin three-phase smart energy meter for 3x230/400 V four-wire networks, measuring active and reactive energy in outdoor installations.
Storage Temperature-40℃ ~ +85℃
Altitude≤ 3000m
ApplicationOutdoor
Fn50Hz; Frequency Range: 0.98fn ~ 1.02fn
Ib5A
2. Datasheet extract (recorded values)
Parameter
Value
Accuracy
Active power Class 1.0; Reactive power Class 2.0
Altitude
≤ 3000m
Application
Outdoor
Fn
50Hz; Frequency Range: 0.98fn ~ 1.02fn
Ib
5A
Imax
100A
Insulation Grade
Class II
Measuring Unit
Three-phase four-wire, without neutral sampling
Meter constant
Active 1000 imp/kWh; Reactive 1000 imp/kvarh
Operating Humidity
95%
Operating Temperature
-25℃ ~ +70℃; At -40℃, the effect of temperature error shall meet IEC standards; display and communication requirements are not considered.
Protection Grade
IP54
Single-phase Measurement
No
Storage Temperature
-40℃ ~ +85℃
UN
3x230/400V; Operating Voltage Range: 80%Un ~ 115%Un
Wiring
BS
Applications and use cases
Architectures in which 282179554 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
Solar production, storage and charging points on one site are often managed separately. Inverters, batteries, MPPT controllers, meters and chargers form a local energy system that shares production between users
To check
Regulatory framework for collective self-consumption in the country
Energy management system steering storage and charging
Metering accuracy for sharing between participants
Associated system blocks
ProductionStorageMeteringCharging
Need a complete solution?
Send a request for 282179554 and the other parts of your project.
Answers to the questions that the recorded characteristics of 282179554 can answer. A question is not asked when nothing is recorded to answer it.
1What is the operating temperature range?
-25℃ ~ +70℃; At -40℃, the effect of temperature error shall meet IEC standards; display and communication requirements are not considered. (source: Operating Temperature).
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productReallin
282179554
Three-phase smart energy meter, 4-wire, no neutral sampling
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details