Reallin 3-phase intelligent energy meter for measuring active and reactive energy on 3x230/400V three-phase circuits, for outdoor installation.
Storage Temperature-40℃ ~ +85℃
Altitude≤ 3000m
ApplicationOutdoor
Fn50Hz; Frequency Range: 0.98fn ~ 1.02fn
Ib5A
Imax100A
Product overview
Overview. The Reallin 3-phase intelligent energy meter, reference 282179575, is an electricity consumption measuring device designed for three-phase four-wire circuits. It operates at a nominal voltage of 3x230/400V and a frequency of 50 Hz, with an operating voltage range of 80% to 115% of the nominal voltage.
Main characteristics. It measures active power with Class 1.0 accuracy and reactive power with Class 2.0 accuracy. Measurement is made without neutral sampling, with BS wiring, a base current Ib of 5 A and a maximum current Imax of 100 A. The meter constant is 1000 imp/kWh for active energy and 1000 imp/kvarh for reactive energy. Single-phase measurement is not supported.
Environmental conditions. The enclosure has an IP54 protection grade and insulation grade Class II. It is intended for outdoor installation at altitudes up to 3000 m. The operating temperature ranges from -25°C to +70°C and the storage temperature from -40°C to +85°C. The permissible operating humidity reaches 95%.
Typical uses. This device suits submetering and consumption monitoring on high-power three-phase installations in industrial and commercial environments. The collected data support electricity consumption analysis and energy usage optimisation.
Communication functions. The manufacturer describes remote meter reading, with data transmitted at set intervals or on demand to a concentrator or energy management platform. The specific interfaces and protocols are not listed in the technical data provided and should be confirmed before deployment.
Reallin 3-phase intelligent energy meter for measuring active and reactive energy on 3x230/400V three-phase circuits, for outdoor installation.
Storage Temperature-40℃ ~ +85℃
Altitude≤ 3000m
ApplicationOutdoor
Fn50Hz; Frequency Range: 0.98fn ~ 1.02fn
Ib5A
2. Datasheet extract (recorded values)
Parameter
Value
Accuracy
Active power Class 1.0; Reactive power Class 2.0
Altitude
≤ 3000m
Application
Outdoor
Fn
50Hz; Frequency Range: 0.98fn ~ 1.02fn
Ib
5A
Imax
100A
Insulation Grade
Class II
Measuring Unit
Three-phase four-wire, without neutral sampling
Meter constant
Active 1000 imp/kWh; Reactive 1000 imp/kvarh
Operating Humidity
95%
Operating Temperature
-25℃ ~ +70℃; At -40℃, the effect of temperature error shall meet IEC standards; display and communication requirements are not considered.
Protection Grade
IP54
Single-phase Measurement
No
Storage Temperature
-40℃ ~ +85℃
UN
3x230/400V; Operating Voltage Range: 80%Un ~ 115%Un
Wiring
BS
Applications and use cases
Architectures in which 282179575 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
A building’s energy, comfort and occupancy data sit in separate systems. Sensors, meters and gateways feed one model of the building, room by room, to compare scenarios and steer the installations
To check
Data model and building plans available
Software platform hosting the twin
Sensor density needed for a useful model
Associated system blocks
SensorsMetersGateways
Need a complete solution?
Send a request for 282179575 and the other parts of your project.
Answers to the questions that the recorded characteristics of 282179575 can answer. A question is not asked when nothing is recorded to answer it.
1What is the operating temperature range?
-25℃ ~ +70℃; At -40℃, the effect of temperature error shall meet IEC standards; display and communication requirements are not considered. (source: Operating Temperature).
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productReallin
282179575
3-Phase Intelligent Energy Meter, Class 1.0 Active Power
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details