Smart three-phase energy meter with direct connection, 4-wire, 5(100)A, approved to the IEC standard. It measures active and reactive energy and connects to a supervision system via RS485 or M-Bus.
Current5(100)A
Frequency50/60Hz
AccuracyActive Cl.1; Reactive Cl.2
Communicationoptical port, RS232, RS485, Mbus
DisplayLCD display with backlight
Optional CommunicationRF, GPRS, WIFI, LoRa
Product overview
Three-phase meter E3015. The Reallin E3015 smart three-phase energy meter is a direct-connected device for 4-wire three-phase networks, approved to the IEC standard. It is intended for energy measurement in three-phase installations.
Measurement and main functions. It measures active energy import and export and reactive energy import and export. It stores up to 12 months of energy and demand history, supports time-of-use tariffs, records load profiles and event logs, and allows remote connection and disconnection.
Technical characteristics. Voltage 3X220/380V to 3X240V/415V, frequency 50/60Hz, current 5(100)A. Accuracy Class 1 for active energy and Class 2 for reactive energy. LCD display with backlight.
Connectivity. Optical port, RS232, RS485 and M-Bus. Optional RF, GPRS, WIFI or LoRa modules are available.
Integration. The RS485 and M-Bus interfaces allow readings by a supervision or energy management system. The optional LoRa module enables data transmission over a LoRaWAN network.
Smart three-phase energy meter with direct connection, 4-wire, 5(100)A, approved to the IEC standard. It measures active and reactive energy and connects to a supervision system via RS485 or M-Bus.
Current5(100)A
Frequency50/60Hz
AccuracyActive Cl.1; Reactive Cl.2
Communicationoptical port, RS232, RS485, Mbus
DisplayLCD display with backlight
2. Datasheet extract (recorded values)
Parameter
Value
Accuracy
Active Cl.1; Reactive Cl.2
Communication
optical port, RS232, RS485, Mbus
Current
5(100)A
Display
LCD display with backlight
Frequency
50/60Hz
Optional Communication
RF, GPRS, WIFI, LoRa
Phase
Three Phase Four Wire
Type
E3015
Voltage
3X220/380V...3X240V/415V
Applications and use cases
Architectures in which 36058551 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
Solar production, storage and charging points on one site are often managed separately. Inverters, batteries, MPPT controllers, meters and chargers form a local energy system that shares production between users
To check
Regulatory framework for collective self-consumption in the country
Energy management system steering storage and charging
Metering accuracy for sharing between participants
Associated system blocks
ProductionStorageMeteringCharging
Need a complete solution?
Send a request for 36058551 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productReallin
36058551
Three-phase direct-connected 4-wire energy meter, Class 1 active
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details