XB6-A80TM – 8-channel RTD and thermocouple temperature input module

8-channel RTD and thermocouple temperature input module

Temperature Input Modules

  • -10~60℃
  • 80mA
  • -20~75℃
  • 106*73*25.7 mm
Manufacturer part number
XB6-A80TM
Manufacturer
Solidot
Operating Temperature
-10~60℃
Rated current consumption
80mA

Solidot XB6-A80TM 8-channel temperature input module for RTD and thermocouple sensors, powered by the X-bus of a Slice I/O system.

Product overview

Overview. The Solidot XB6-A80TM is an 8-channel temperature input module of the Slice I/O system, designed for measuring RTD and thermocouple sensors. It is a compact module measuring 106 x 73 x 25.7 mm.

Main characteristics. The module offers 16-bit resolution and an accuracy of ±0.5 % for thermocouples, ±1 °C for RTD and ±0.1 % for resistance measurement. The conversion time is 201 ms for thermocouples and 26 ms for RTD and resistance. Each channel has a green channel indicator LED.

Connectivity and power. The module communicates over the X-bus backplane bus at a transmission rate of 6 Mb/s and is powered via this bus. Its rated current consumption is 80 mA. The isolation withstand voltage is 500 Vrms, with no isolation between channels.

Environment. The module operates between -10 and 60 °C, is stored between -20 and 75 °C, tolerates 95 % relative humidity non-condensing and has an IP20 protection rating. Its weight is 120 g.

Typical uses. This module suits temperature measurement in automated installations built around a Slice I/O system, where acquisition of RTD or thermocouple sensors is required. Available on quotation from Atlas Electronics.

See all specifications

Highlights

  • Dimensions: 106*73*25.7 mm
  • Accuracy: ±0.5 % (thermocouple) / ±1 °C (RTD) / ±0.1 % (resistance)
  • Channel Indicator: Green LED
  • Conversion Time: 201 ms (thermocouple) / 26 ms (RTD, resistance)
  • Data transmission medium: X-bus backplane bus
  • Isolation Withstand Voltage: 500 Vrms, no isolation between channels

Good to know before integrating

  • Thermal: rated operating range -10~60℃ — check it against the installation environment.

See also

Technical questions

Ask a question

No published question about this part yet. Questions are reviewed before publication.

Request a quote