XB6S-A40TM – 4-channel temperature input module for thermocouples and RTD sensors

4-channel temperature input module for thermocouples and RTD sensors

Temperature Input Modules

  • -20℃~+60℃
  • <2mA
  • 0.5W
  • -40℃~+80℃
Manufacturer part number
XB6S-A40TM
Manufacturer
Solidot
Operating Temperature
-20℃~+60℃
Excitation current
<2mA

The Solidot XB6S-A40TM is a 4-channel temperature acquisition module supporting thermocouples, RTD sensors and resistance inputs, designed for automation systems using the XB6S series X-bus.

Product overview

Overview. The Solidot XB6S-A40TM is a slice-type 4-channel temperature input module accepting thermocouples, RTD sensors and resistance measurements. It connects to the XB6S series coupler through the X-bus backplane bus.

Main characteristics. 16-bit resolution, sensitivity of 0.1 °C for thermocouples and RTD and ±0.1 Ω for resistance. Accuracy is ±0.1 % F.S. at 25 °C for RTD and resistance, and ±0.3 % F.S. at 25 °C for thermocouples. Conversion time is 29 ms per channel for thermocouples and 73 ms per channel for RTD and resistance, or 115 ms and 290 ms for 8 channels. Single-channel input filtering is configurable from level 1 to 10, and noise suppression can be set to 50 Hz, 60 Hz, 10 Hz or disabled.

Diagnostics and reliability. The module supports sensor disconnection detection, diagnostics, firmware upgrade and automatic module fault recovery. An alarm function and a green LED per channel support maintenance. Electrical isolation withstands 500 VAC.

Power and environment. 5 VDC supply (4.5 V to 5.5 V) with 0.5 W power consumption. Operating temperature from -20 °C to +60 °C, storage from -40 °C to +80 °C, 95 % relative humidity non-condensing, IP20 protection rating. Dimensions 106.4 × 25.7 × 72.3 mm, weight 110 g.

Typical uses. Temperature acquisition in automation control cabinets, with spring-clamp connection and integration on the XB6S series X-bus.

See all specifications

Highlights

  • Dimensions: 106.4*25.7*72.3mm
  • Alarm: Supported
  • Bus connection method: Spring-Clamp contact
  • Channel Indicator: Green LED
  • Data transmission medium: X-bus backplane bus
  • Diagnostics: Supported

Good to know before integrating

  • Thermal: rated operating range -20℃~+60℃ — check it against the installation environment.