XB6S-A80TM – 8-channel temperature input module for thermocouples and RTD sensors

8-channel temperature input module for thermocouples and RTD sensors

Temperature Input Modules

  • -20℃~+60℃
  • <2mA
  • 0.55W
  • -40℃~+80℃
Manufacturer part number
XB6S-A80TM
Manufacturer
Solidot
Operating Temperature
-20℃~+60℃
Excitation current
<2mA

The Solidot XB6S-A80TM is a compact 8-channel temperature acquisition module for thermocouple, RTD and resistance measurement on XB6S series couplers.

Product overview

Overview. The Solidot XB6S-A80TM is a slice-type 8-channel temperature input module accepting thermocouples, RTD sensors and resistance measurements. It connects to the XB6S series coupler through the X-bus backplane bus.

Main characteristics. Accuracy of ±0.3 % F.S. at 25 °C for thermocouples and ±0.1 % F.S. at 25 °C for RTD and resistance. 16-bit resolution, sensitivity of 0.1 °C for thermocouples and RTD, and ±0.1 Ω for resistance. Input filter configurable over 10 levels and noise suppression at 50 Hz, 60 Hz or 10 Hz. Conversion time of 29 ms per channel for thermocouples and 73 ms per channel for RTD.

Interfaces and connectivity. X-bus backplane at 6 Mb/s, Spring-Clamp contact connection, green LED channel indicator. The module supports alarm, diagnostics, sensor disconnection detection, module fault auto-recovery and firmware upgrade.

Power and environment. 5 VDC supply (4.5 V to 5.5 V), power consumption of 0.55 W, electrical isolation with 500 VAC withstand voltage. Operating temperature -20 °C to +60 °C, storage -40 °C to +80 °C, relative humidity 95 % non-condensing, protection rating IP20. Dimensions 106.4 × 25.7 × 72.3 mm, weight 110 g.

Typical uses. Temperature acquisition on automation systems requiring several measurement points in a small footprint, with simplified field wiring.

Integration. The module is used with XB6S series couplers and fits the manufacturer's slice I/O architecture.

See all specifications

Highlights

  • Dimensions: 106.4*25.7*72.3mm
  • Alarm: Supported
  • Bus connection method: Spring-Clamp contact
  • Channel Indicator: Green LED
  • Data transmission medium: X-bus backplane bus
  • Diagnostics: Supported

Good to know before integrating

  • Thermal: rated operating range -20℃~+60℃ — check it against the installation environment.