Overview. The Sungrow MVS3200-US is a turnkey medium-voltage transformer station designed to connect SG350HX-US 1500 Vdc string inverters to the grid. It is delivered pre-assembled at the factory in a standard 20-foot ISO container, with only the AC cable wiring to be completed on site.
Main characteristics. AC output power of 3200 kVA at 40 ℃ and 3520 kVA at 30 ℃, efficiency of 99 % at 100 % load (3200 kVA), frequency of 60 Hz. Oil-immersed transformer with KNAN / ONAN cooling, LV / MV voltages of 0.8 kV / 12.47 kV to 34.5 kV, HV tapping of 0, ± 2 × 2.5 %, vector group Dy1 / Dy11 / YNy0 or customized, to be confirmed with Sungrow. Aluminium windings (Al / Al), two-winding impedance of approximately 5.75 % ± 7.5 % for 34.5 kV. Approximate weight 14000 kg, dimensions 6058 mm × 2896 mm × 2438 mm.
Protection and safety. Transformer protection by expulsion fuse and backup fuse, Type II surge protection, disconnectors 275 A / 800 Vac / 3P (10 pcs), fuses 350 A / 800 Vac / 1P (30 pcs). Transformer alarm contacts: oil temperature alarm and trip, oil level trip, pressure trip. Compliant with IEEE C57.12.00, C57.12.90 and C57.12.28, low-voltage cabinet UL891, auxiliary power cabinet UL508. Degree of protection Type 3R.
Auxiliary power and environment. Auxiliary power supply of 5 kVA, 120 Vac, optional 40 kVA (35 kVA / 480 V, 5 kVA / 120 V). Operating ambient temperature range from -30 ℃ to 60 ℃, allowable relative humidity from 0 % to 95 % non-condensing, operating altitude of 1000 m as standard, above that on request.
Communication and operation. RS485 and Ethernet communication interfaces, online monitoring for fault analysis, modular design with easy replacement of the main device and front access for maintenance.
Integration. Suited to grid-tied photovoltaic installations with SG350HX-US string inverters. Available on quotation from Atlas Electronics.