UT586
Digital RCD tester for residual current devices

- Rate trigger current — Fault trigger time — Accuracy; (current)
- Accuracy; (time)
- Storage Environment
- -20℃~60℃
- Package Dimension
- 585×380×335mm
- Standard package
- Carton box: 4pcs
Digital RCD tester for residual current devices
Installation and Earth Testers
The UT586+ from UNI-T is a digital RCD tester for single-phase and three-phase residual current devices, measuring trip current and trip time. It has a CAT III 600V safety rating.
Overview. The UT586+ from UNI-T is a digital RCD tester designed to verify the operation of single-phase and three-phase residual current protection devices. It measures the fault trip time and the current that triggers tripping.
Main characteristics. The tester offers several RCD test modes: AUTO, manual, X1, X1/2, X2 and X5, with trip currents from 10 to 1000 mA. The AUTO RAMP test measures trip current and trip time simultaneously. The 0° / 180° phase selector lets you start the test on the positive or negative half-cycle. A lock test function is also available with the power disconnected.
Voltage measurement. The L-PE voltage measurement displays 30 V to 480 V, with frequency display from 45 to 65 Hz. A wiring check signals missing wiring or an abnormal supply.
Safety and environment. The instrument complies with IEC61010-031 and IEC61557-1,6 and the CAT III 600V rating. It includes internal over-temperature detection, automatic power-off after 5 minutes without operation, a backlight and a low battery indicator. It operates between 0 °C and 40 °C and is stored between -20 °C and 60 °C. It is powered by 8 AA 1.5 V batteries.
Typical uses. This tester is suited to checking residual current devices in residential installations, educational buildings and electrical installations, as well as in manufacturing, metallurgical and chemical sectors. Available on quotation from Atlas Electronics.
No published question about this part yet. Questions are reviewed before publication.
Every characteristic recorded for UT586, with where it comes from. Use the filters to find one quickly.
| Characteristic | Value |
|---|---|
| Auto powwer off | After 5 minutes of no operation, it will automatically shut down. |
| AUTO RAMP test | You can test the trip action current and action time simultaneously. |
| Backlight | Yes, can be turn on/off |
| Lock test | With the power disconnected, press and hold the “0°/180°” button to activate the lock test function. Simply connect the test leads correctly to the test points, and the test will run automatically. |
| Low Battery Indication | yes |
| Over-temperature detection | If the internal components of the device become too hot, the LCD will display an over-temperature symbol, and the device will automatically disable RCD testing. |
| Package Dimension | 585×380×335mm |
| Phase angle selection | You can choose to initiate the test from the positive (0°) or the negative (180°) half-cycle. Press the “0°/180°” button to toggle phase. |
| Power | 8 * 1.5V AA |
| Product color | Red + gray |
| Product Dimension | 161*117*68mm |
| Product Weight | 725g |
| Rate trigger current — Fault trigger time — Accuracy; (current) | Accuracy; (time) |
| RCD test exceeds limit prompt | When the trip action time exceeds the maximum test duration and trips. |
| RCD test function — AUTO — 10/20/30/100/300/500mA/1000mA — 300ms @ 15 0°/180° — -10%~+10% | ±0.6%rdg±4dgt |
| RCD test function — Manual — 10/20/30/100/300/500mA/1000mA — 300ms @ 0°/180° — -10%~+10% | ±0.6%rdg±4dgt |
| RCD test function — X1 — 10/20/30/100/300mA — 0~2000mS @ 0°/180° — 0%~+10% | ±0.6%rdg±4dgt |
| RCD test function — X1/2 — 10/20/30/100/300/500mA/1000mA — 0~2000mS @ 0°/180° — -10%~0%” | ±0.6%rdg±4dgt |
| RCD test function — X1 — 500mA/1000mA — 0~200mS @ 0°/180° — 0%~+10% | ±0.6%rdg±4dgt |
| RCD test function — X2 — 10/20/30/100/200/300/500mA — 0~200mS @ 0°/180° — 0%~+10% | ±0.6%rdg±4dgt |
| RCD test function — X5 — 10/20/30/100/200mA — 0~200mS @ 0°/180° — 0%~+10% | ±0.6%rdg±4dgt |
| Safety rating | IEC61010-031; IEC61557-1,6; CAT III 600V |
| Standard Accessories | User manual 1pcs; Test lead 1 set(red/green); Alligator clips 2pcs(red/green); Test probe 2pcs(red/green); 1.5V AA * 8pcs; Test lead to EU plug 1pcs |
| Standard package | Carton box: 4pcs |
| Storage Environment | -20℃~60℃ |
| Voltage test — Frequency | yes, display the L-PE input frequency; when it is “volts”, press “VOLT/FREQ” key to switch “Voltage/Frequency” |
| Voltage test — L-PE | yes, display the L-PE input voltage; range: 30V~480V; No input and low voltage: “0V”; if less than 30V: <30V; if more than 4800v: >480V |
| Voltage test — Voltage range — 30~480V (Resolution: 1V) — 45~65Hz | ±3%rdg±3dgt |
| Wiring check | If there is no wiring, an abnormal power supply, or no electricity flowing, the LCD will display “L-PE” and flash. |
| Working Environment | 0℃~40℃ |
| Working voltage — 50/60Hz — 100V~440V; (Note: If > 450V, it will issue an alarm and stop the RCD test) | -15%~+10% |
No specification matches.
Last verification : 2026-11-02
Official documents and the technical data recorded for UT586. For a missing document or a specific revision, our experts send it to you.
The UT586+ from UNI-T is a digital RCD tester for single-phase and three-phase residual current devices, measuring trip current and trip time. It has a CAT III 600V safety rating.
| Parameter | Value |
|---|---|
| Auto powwer off | After 5 minutes of no operation, it will automatically shut down. |
| AUTO RAMP test | You can test the trip action current and action time simultaneously. |
| Backlight | Yes, can be turn on/off |
| Lock test | With the power disconnected, press and hold the “0°/180°” button to activate the lock test function. Simply connect the test leads correctly to the test points, and the test will run automatically. |
| Low Battery Indication | yes |
| Over-temperature detection | If the internal components of the device become too hot, the LCD will display an over-temperature symbol, and the device will automatically disable RCD testing. |
| Package Dimension | 585×380×335mm |
| Phase angle selection | You can choose to initiate the test from the positive (0°) or the negative (180°) half-cycle. Press the “0°/180°” button to toggle phase. |
| Power | 8 * 1.5V AA |
| Product color | Red + gray |
| Product Dimension | 161*117*68mm |
| Product Weight | 725g |
| Rate trigger current — Fault trigger time — Accuracy; (current) | Accuracy; (time) |
| RCD test exceeds limit prompt | When the trip action time exceeds the maximum test duration and trips. |
| RCD test function — AUTO — 10/20/30/100/300/500mA/1000mA — 300ms @ 15 0°/180° — -10%~+10% | ±0.6%rdg±4dgt |
| RCD test function — Manual — 10/20/30/100/300/500mA/1000mA — 300ms @ 0°/180° — -10%~+10% | ±0.6%rdg±4dgt |
| RCD test function — X1 — 10/20/30/100/300mA — 0~2000mS @ 0°/180° — 0%~+10% | ±0.6%rdg±4dgt |
| RCD test function — X1/2 — 10/20/30/100/300/500mA/1000mA — 0~2000mS @ 0°/180° — -10%~0%” | ±0.6%rdg±4dgt |
| RCD test function — X1 — 500mA/1000mA — 0~200mS @ 0°/180° — 0%~+10% | ±0.6%rdg±4dgt |
| RCD test function — X2 — 10/20/30/100/200/300/500mA — 0~200mS @ 0°/180° — 0%~+10% | ±0.6%rdg±4dgt |
| RCD test function — X5 — 10/20/30/100/200mA — 0~200mS @ 0°/180° — 0%~+10% | ±0.6%rdg±4dgt |
| Safety rating | IEC61010-031; IEC61557-1,6; CAT III 600V |
| Standard Accessories | User manual 1pcs; Test lead 1 set(red/green); Alligator clips 2pcs(red/green); Test probe 2pcs(red/green); 1.5V AA * 8pcs; Test lead to EU plug 1pcs |
| Standard package | Carton box: 4pcs |
| Storage Environment | -20℃~60℃ |
| Voltage test — Frequency | yes, display the L-PE input frequency; when it is “volts”, press “VOLT/FREQ” key to switch “Voltage/Frequency” |
| Voltage test — L-PE | yes, display the L-PE input voltage; range: 30V~480V; No input and low voltage: “0V”; if less than 30V: <30V; if more than 4800v: >480V |
| Voltage test — Voltage range — 30~480V (Resolution: 1V) — 45~65Hz | ±3%rdg±3dgt |
| Wiring check | If there is no wiring, an abnormal power supply, or no electricity flowing, the LCD will display “L-PE” and flash. |
| Working Environment | 0℃~40℃ |
| Working voltage — 50/60Hz — 100V~440V; (Note: If > 450V, it will issue an alarm and stop the RCD test) | -15%~+10% |
Answers to the questions that the recorded characteristics of UT586 can answer. A question is not asked when nothing is recorded to answer it.
Yes — recorded under "AUTO RAMP test": You can test the trip action current and action time simultaneously..
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Digital RCD tester for residual current devices

MODEL

KEW

KEW

Describe your application and constraints in a request.
What is recorded about the regulatory status and the life of this part.
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
| Current status | Status not stated |
| Key dates | Not recorded |
| Manufacturer part number | UT586 |
| Manufacturer | UNI-T |
Installation and Earth Testers
Single and three-phase ZigBee electrical metering module
Price on request
Installation and Earth Testers
Multifunction installation tester with loop and RCD testing · Ref. : KEW_6016
Price on request
Installation and Earth Testers
Advanced earth resistance and soil resistivity tester · Ref. : UT572
Price on request
Installation and Earth Testers
Residual current device (RCD) tester with trip time measurement · Ref. : KEW_5410
Price on request
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details