| Acceleration and deceleration curve | Linear acceleration and deceleration, S curve acceleration and deceleration |
| Allowable fluctuation range | Voltage: ±15%; frequency fluctuation: ±5%; Distortion rate: meet the requirements of IEC 61800-2 |
| Analog setting | maximum frequency×±0.2% |
| Automatic current limit | Automatically limit the current during operation to prevent frequent over-current fault trips |
| Automatic energy-saving operation | According to the load condition, the output voltage is automatically optimized to realize energy-saving operation |
| Carrier frequency range | 2.0~8.0kHz(Model determination) |
| Closing surge current | Less than rated current |
| Cooling Method | Forced air cooling, liquid cooling |
| Corporate | Corporate products and information |
| Digital setting | maximum speed×±0.01% |
| Energy Storage Solution | Residential, C&I energy storage system solutions. |
| Error alarm | Self-learning abnormality, sensor feedback disconnection, motor overheating, driver overheating, encoder failure, communication failure, overvoltage, undervoltage, overcurrent, short circuit,Phase loss, overload, stall, current limit, data protection damaged, current fault operating status, historical fault. |
| Exhibitions | VEICHI exhibitions, bringing you first-hand information. |
| External output signal | 2 relay outputs; 1 transistor output; 2 analog outputs, voltage output range: 0~10V/0~10V, current output range: 0~20mA/0~20mA |
| Feedback input channel | Voltage/current terminal AI1, voltage/current terminal AI2, voltage/current terminal P-AI, communication setting |
| Input command signal | Start, stop, forward and reverse rotation, jog, multi-speed, free stop, reset, acceleration and deceleration time selection, speed setting channel selection, external fault alarm |
| Installation Method | Wall-mounted, vertical cabinet |
| Installation site: | Indoor, the altitude is not more than 1000m, no corrosive gas and direct sunlight |
| Inverter Efficiency | ≥ 96% |
| LED Display | Single line 5-digit digital tube display: Can monitor 1 status |
| Modulation | SVPWM |
| Output frequency accuracy | ±0.1% |
| Output frequency range | Maximum output frequency: 320HZ |
| Overload Capacity | 150% rated current 60s, 180% rated current 5s, maximum 2.5 times |
| Power Factor | ≥ 0.94(With DC reactor) |
| Protection Level | IP20 |
| Run command channel | Operation panel setting, external terminal setting, communication setting |
| Servo System | Servo motor drive system products and solutions. |
| Solar Irrigation System | Solar irrigation system products and solutions. |
| Speed Resolution | Digital setting: 1rpm; Analog setting: maximum speed×0.05% |
| Speed setting channel | Keyboard digital setting, analog voltage/current terminal AI1, analog voltage/current terminal AI2, analog voltage/current terminal P-AI, communication setting and multi-channel terminal selection, combination of main and auxiliary channels. |
| Standard function | Oil pressure closed loop control, speed control, RS485, analog output |
| Status monitoring | Pressure command, pressure feedback, speed setting, speed feedback, flow command, output current, output voltage, output torque, output power, bus voltage, module temperature, motor temperature, input terminal X connected state, output terminal Y connected Status etc. |
| Storage Temperature | From -25℃ to +60℃ |
| Temperature and humidity | From -10°C to +40°C; 5% ~ 95%RH(No condensation) |
| The output voltage | Output under rated conditions: 3-phase, 0~input voltage, error less than 5% |
| Vibration | Less than 0.5g |
| Voltage and frequency | Three-phase 380V 50/60HZ |