The MC115 is a Winsen catalytic flammable gas sensor measuring 0 to 100%LEL for industrial natural gas, LPG, coal gas and alkanes.
Detection range0-100%LEL
Working current(mA)105±10
Storage Environment-20 ~+70℃, less than 95%RH
Anti-explosion markExdibⅠ
Detection Principlecatalytic combustion
Linearity≤ 5%
Product overview
Overview. The Winsen MC115 catalytic flammable gas sensor measures 0 to 100%LEL. It targets combustible gases such as industrial natural gas, LPG, coal gas and alkanes.
Measuring principle. Catalytic combustion uses a test element and a compensation element forming two arms of a bridge. The resistance of the test element rises with combustible gas and the bridge output voltage changes in proportion to concentration, while the compensation element corrects for temperature and humidity.
Main characteristics. Sensitivity of 20 ~40 mV per 1% CH4, linearity ≤ 5%, response time (90%) ≤ 10s and recovery time ≤ 30s. The sensor is described as having linear bridge output voltage, fast response, good repeatability and selectivity.
Power and environment. Working voltage 3.0±0.1V with working current 105±10mA. Working environment -40 ~+70℃, less than 95%RH. Storage environment -20 ~+70℃, less than 95%RH.
Package and certification. Standard metal encapsulation, size Φ 6×6.5 mm. Anti-explosion mark ExdibⅠ.
The MC115 is a Winsen catalytic flammable gas sensor measuring 0 to 100%LEL for industrial natural gas, LPG, coal gas and alkanes.
Detection range0-100%LEL
Working current(mA)105±10
Storage Environment-20 ~+70℃, less than 95%RH
Anti-explosion markExdibⅠ
Detection Principlecatalytic combustion
2. Datasheet extract (recorded values)
Parameter
Value
Anti-explosion mark
ExdibⅠ
Characteristics
"Bridge output voltage in linear, fast response, good repeatability and selectivity "
Detection Principle
catalytic combustion
Detection range
0-100%LEL
Linearity
≤ 5%
Measuring range(%LEL)
0 ~ 100
Model
MC115
Recovery Time (90%)
≤ 30s
Response time (90%)
≤ 10s
Sensitivity (mV/1% CH4)
20 ~40
Sensor Type
Catalytic
Size
φ6×6.5
SIZE; mm
Φ 6×6.5
Standard Encapsulation
Metal
Storage Environment
-20 ~+70℃, less than 95%RH
Target
Combustible gases such as industrial natural gas,LPG, coal gas and alkanes
Working Conditions
Working voltage:3±0.1V; Working current:105±10mA
Working current(mA)
105±10
Working Environment
-40 ~+70℃, less than 95%RH
Working Voltage (V)
3.0±0.1
Applications and use cases
Architectures in which MC115 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Offices and classrooms get stuffy without anyone measuring why. Indoor air quality monitoring places CO2, VOC and particle sensors in the rooms and reports their values through a gateway, so ventilation can be adjusted to real occupancy
To check
Parameters to measure (CO2 alone or CO2, VOC and particles)
Battery-powered sensors or mains-powered sensors with display
Integration with the ventilation control or building management system
Associated system blocks
Air sensorsGateway
Need a complete solution?
Send a request for MC115 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details