MH-411D – Miniature NDIR infrared CO2 sensor with UART output

Miniature NDIR infrared CO2 sensor with UART output

CO2 Sensors

  • 0~10% Vol optional
  • 3.0V
  • <85mA
  • Note
Manufacturer part number
MH-411D
Manufacturer
Winsen
Detection range
0~10% Vol optional
Interface Level
3.0V

Miniature NDIR infrared sensor measuring CO2 concentration in air, with UART and analog voltage output, for HVAC, industrial process control and safety protection.

Product overview

Overview. The Winsen MH-411D is a miniature non-dispersive infrared (NDIR) CO2 sensor that measures carbon dioxide concentration in air. It is independent of oxygen and offers good selectivity, stable performance and a long service life of more than 5 years.

Main characteristics. The sensor combines high sensitivity, high resolution, low power consumption and fast response time, with a T90 response time below 30 s and a warm-up time of 3 min. Its built-in temperature compensation provides excellent linear output. It is resistant to poisons and vapour interference.

Measuring ranges. Several ranges are available: 0 to 2000 ppm, 0 to 6000 ppm, 0 to 1% VOL, 0 to 3% VOL and 0 to 5% VOL, with an accuracy of ±(50 ppm + 5% of reading value) and an optional detection range of 0 to 10% Vol.

Interfaces and connectivity. The sensor provides a UART output and an analog voltage output, with an interface level of 3.0 V.

Power and environment. It operates from 3.6 to 5 V DC and must be powered through a safety barrier (Ui = 7.5 VDC, Ii = 265 mA, Pi = 0.5 W). Its average current is below 85 mA. Working temperature is -20 °C to 60 °C and working humidity 0 to 95% RH without condensation. Defense grade IP54. Size Φ20 mm × 22.2 mm, weight 35 g.

Typical uses. HVAC refrigeration, industrial process control, safety protection, agriculture and animal husbandry.

Integration. The sensor must be integrated into a system able to read a UART output or an analog voltage, powered through a safety barrier. Available on quotation from Atlas Electronics.

See all specifications

Highlights

  • Response time: T90 < 30 s
  • Average Current: <85mA
  • CO2 — 0~1% VOL — ±(50ppm + 5% of Read Value): Temperature compensation
  • CO2 — 0~2000 ppm — ±(50ppm + 5% of Read Value): Temperature compensation
  • CO2 — 0~3% VOL — ±(50ppm + 5% of Read Value): Temperature compensation
  • CO2 — 0~5%VOL — ±(50ppm + 5% of Read Value): Temperature compensation

Typical applications

Derived from the part category, not a compatibility statement.

See also

Technical questions

Ask a question

No published question about this part yet. Questions are reviewed before publication.