Laser dust sensor module detecting PM1.0, PM2.5 and PM10 fine particles in air by laser scattering, for air quality monitoring and air purifiers.
Detection diameter range0.3~10μ m
Detection range0-1000μg/m³
Valid range0~1000μ g/m3
Dormancy current<20mA
Working current<120mA
Storage Temperature-30~70℃
Product overview
Overview. The Winsen ZH03B is a laser dust sensor module that detects PM1.0, PM2.5 and PM10 particles in air by laser scattering. It measures particle diameters from 0.3 to 10 µm over a detection range of 0 to 1000 µg/m³, with a detection interval of 1 s.
Main characteristics. The sensor offers good consistency and real-time response. Its PM2.5 detection accuracy is ±15 µg/m³ from 0 to 100 µg/m³ and ±15% of reading from 101 to 1000 µg/m³, under test conditions of 25±2 ℃ and 50±10% RH. The T90 response time is below 45 s and stabilization after power-on takes 30 s.
Interfaces and connectivity. The module provides a UART TTL output at 3.3 V level (default) and a PWM output at 3.3 V level.
Power and environment. Working voltage 4.9 V to 5.5 V DC, working current below 120 mA and dormancy current below 20 mA. It operates from -10 to 50 ℃ and 0 to 80% RH without condensation, and stores from -30 to 70 ℃. Dimensions 50 x 32.4 x 21 mm, weight below 38 g, MTTF continuous without interruption above 10000 h.
Typical uses. Air purifiers, ventilation systems, portable instruments, air quality monitoring equipment, air conditioners and smart home equipment.
Integration. The UART output allows connection to a microcontroller or PLC to exploit the measurements. The sensor has no built-in sleeping mode; it can be managed by program if needed.
Architectures in which ZH03B can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Offices and classrooms get stuffy without anyone measuring why. Indoor air quality monitoring places CO2, VOC and particle sensors in the rooms and reports their values through a gateway, so ventilation can be adjusted to real occupancy
To check
Parameters to measure (CO2 alone or CO2, VOC and particles)
Battery-powered sensors or mains-powered sensors with display
Integration with the ventilation control or building management system
Associated system blocks
Air sensorsGateway
Need a complete solution?
Send a request for ZH03B and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details