Eastron Smart X96-5F. three-phase multifunction energy meter for panel mounting in electricity distribution, true RMS measurement including harmonics up to the 63rd.
Measurements. The meter measures and displays voltage, frequency, current, active, reactive and apparent power, active and reactive energy, power factor and total harmonic distortion (THD) up to the 63rd harmonic on three-phase 3P+N and 3P systems. Voltage measurement range is 50 V to 600 V in 3P4W and 50 V to 480 V in 3P3W, rated current 5 A, maximum current 9999 A.
Accuracy. Class 0.5S for active energy according to IEC 62053-22 and Class 1.0 according to IEC 62053-21, accuracy of 0.5% for current and voltage, 0.2% for frequency.
Communication. RS485 port with Modbus RTU, 2-wire half duplex, addresses from 1 to 247, baud rates from 2400 to 38400 bps, parity none, even or odd, one or two stop bits. The meter connects to a PLC or supervisory system for remote reading and configuration.
Power and environment. Auxiliary supply 230 V L-N AC or 120 V to 380 V DC. Operating temperature -25 °C to 55 °C, storage -40 °C to 70 °C, humidity below 95% RH non-condensing at 50 °C, altitude 2000 m. IP51 front display protection, self-extinguishing UL 94 V-0 case.
Installation. Dimensions 96 x 96 x 92 mm, weight 420 g, vertical panel cut-out, shrouded screw-clamp terminals.