Hexing HXE34K three-phase energy meter for measuring active and reactive energy on two-phase or three-phase supplies, in direct or indirect connection.
Temperature — Operating Temperature-40℃~70℃
Operating Voltage Range70%-120%Un
Storage & Transport Temp. Range-40℃~70℃
Communication Interfaces — Optical Port CommunicationIEC62056-21C or IEC62056-21E (DLMS)
Current Circuit≤0.1VA
Power Consumption — Voltage Circuit (Active)≤1 W
Product overview
Hexing HXE34K three-phase energy meter. The HXE34K is a direct-connected or transformer-rated polyphase static energy meter designed to measure active and reactive energy on two-phase or three-phase power supply systems. It is offered as the Three-Phase Energy Meter.
Measurement. Class 1 for direct connection and 0.5S for indirect connection for active energy, Class 2 or Class 1 for reactive energy. Base current 5A direct and 1A indirect, maximum current 100A or 120A direct and 10A indirect. Rated voltage 3 x 57.7/100V to 3x240/415V and 2x120/208V, operating voltage range 70%-120%Un, frequency 50Hz or 60Hz.
Communication. IEC62056-21C or IEC62056-21E (DLMS) optical port, optional RS485 port with IEC62056-21C or HDLC (DLMS), and optional RF with IEC62056-21C.
Power and environment. Voltage circuit consumption of 1 W active and 2 VA apparent, current circuit at or below 0.1 VA. IP54 enclosure rating, operating temperature -40℃ to 70℃, humidity up to 95% relative humidity non-condensing.
Construction. Cool gray PC and glass fiber base and cover with transparent window, dimensions 216mm x 173mm x 65mm with extended cover, net weight approximately 1.1 kg for 3P4W direct-connected.
Standards and tests. Compliant with IEC62052-11 and IEC62053-21. Dielectric strength 4kV for 1 min, impulse voltage 1.2/50µs 6kV, electrostatic discharge 8kV contact and 15kV air, electrical fast transient/burst 4kV, surge immunity 4kV, radiated RF field immunity 10V/m.
Use. Suited to remote meter reading and consumption monitoring through its communication ports, for integration with systems compatible with IEC62056-21 or DLMS. Available on quotation from Atlas Electronics.
Points to check before using THREE-PHASE-STANDARD-METER-HXE34K in a design. They are derived from the recorded characteristics, not from the manufacturer's application circuits.
1Thermalrated operating range -40℃~70℃ — check it against the installation environment.
Check the exact pin assignment and the application circuit in the datasheet, or ask our experts.
Implementation checklist
Thermal : rated operating range -40℃~70℃ — check it against the installation environment.
Applications and use cases
Architectures in which THREE-PHASE-STANDARD-METER-HXE34K can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
Solar production, storage and charging points on one site are often managed separately. Inverters, batteries, MPPT controllers, meters and chargers form a local energy system that shares production between users
To check
Regulatory framework for collective self-consumption in the country
Energy management system steering storage and charging
Metering accuracy for sharing between participants
Associated system blocks
ProductionStorageMeteringCharging
Need a complete solution?
Send a request for THREE-PHASE-STANDARD-METER-HXE34K and the other parts of your project.
Answers to the questions that the recorded characteristics of THREE-PHASE-STANDARD-METER-HXE34K can answer. A question is not asked when nothing is recorded to answer it.
1Does it support RS-485?
Yes — recorded under "RS485 (Optional)": IEC62056-21C or HDLC (DLMS).
2What is the operating temperature range?
-40℃~70℃ (source: Temperature — Operating Temperature).
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productHexing
THREE-PHASE-STANDARD-METER-HXE34K
Direct or Transformer-Rated Three-Phase Energy Meter
Temperature — Operating Temperature
-40℃~70℃
Operating Voltage Range
70%-120%Un
Storage & Transport Temp. Range
-40℃~70℃
Communication Interfaces — Optical Port Communication
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.