ZJWP400A – High-current DC contactor 400 A with magnetic blowout

High-current DC contactor 400 A with magnetic blowout

Power Contactors

  • -40°C to +60°C
  • 400A (100% Ith)
  • -40°C to +85°C
  • >100,000 cycles
Manufacturer part number
ZJWP400A
Manufacturer
HIITIO
Operating Temperature
-40°C to +60°C
Wide Operating Temperature
-40°C to +60°C

HIITIO ZJWP400A low voltage DC contactor rated 400 A for switching heavy DC loads, up to 96 V DC with magnetic blowout.

Product overview

Overview. The HIITIO ZJWP400A DC contactor, from the ZJWP series, is a low voltage contactor designed for switching high-current DC circuits. Its rated heating current is 400 A (100% Ith), and its maximum contact voltage is 48 V DC without blowout and 96 V DC with magnetic blowout.

Main characteristics. The contact voltage drop is below 40 mV at 100 A. Mechanical life exceeds 300,000 cycles and electrical life exceeds 100,000 cycles. Contact jitter time is below 4 ms for fast and stable switching. The unit weighs 1300 g and features strong terminals.

Coil power. Coil consumption is 30 to 40 W in intermittent operation and 15 to 30 W in continuous operation. Pick-up voltage is 60% Un intermittent and 66% Un continuous. Release voltage is 5 to 40% Un.

Environment. Operating temperature range is -40 °C to +60 °C, and storage temperature range is -40 °C to +85 °C.

Typical uses. This contactor suits large electric vehicles and commercial trucks, high-capacity solar and wind energy storage systems, advanced high-power battery management systems, industrial heavy machinery and DC power distribution, marine propulsion systems, and high-power charging stations and main disconnectors.

See all specifications

Highlights

  • Coil Power Consumption: Intermittent: 30-40W Continuous: 15-30W
  • Electrical Life: >100,000 cycles
  • Fast & Stable Switching: Contact jitter time <4ms
  • Heavy-Duty Build: Weight 1300g with strong terminals
  • Low Contact Voltage Drop: <40mV @ 100A
  • Max Contact Voltage: 48V DC (No Blowout) / 96V DC (With Blowout)

Good to know before integrating

  • Thermal: rated operating range -40°C to +60°C — check it against the installation environment.
  • Thermal: rated operating range -40°C to +60°C — check it against the installation environment.

See also

Technical questions

Ask a question