UEC1-18C
Three-pole AC power contactor 18 A

- Hold-in Power Consumption in VA
- 9.5 VA 50/60 Hz (at 25 °C)
- Minimum Switching Current
- 0.1A for signalling circuit
- Mounting Support
- Screw; 35mm DIN Rail
- Number of Units in Package 1
- 1 pcs
Three-pole AC power contactor 18 A
The Hongfa UEC1-18C is a three-pole power contactor rated 18 A AC-3 for switching motors and power loads up to 690 V AC.
Hongfa UEC1-18C. three-pole power contactor (UEC1 series) from the Hongfa IEC contactor range, designed for switching AC power circuits.
Main characteristics. Rated operational current Ie of 18 A at 60 °C in AC-3 up to 400 V and 32 A in AC-1 up to 690 V AC, rated operational voltage Ue of 690 V AC 50/60 Hz, rated insulation voltage Ui of 690 V conforming to IEC 60947-4-1, rated impulse withstand voltage Uimp of 6 kV, electrical durability of 1.0 million cycles at 18 A AC-3 and mechanical durability of 10 million cycles. Conventional free air thermal current Ith of 32 A at 60 °C for the power circuit and 10 A for the signalling circuit.
Motor power. 4 kW at 220/230 V, 7.5 kW at 380/400 V and 10 kW at 660/690 V in AC-3; single-phase motors up to 3 hp at 220-240 V, three-phase motors up to 15 hp at 550-600 V.
Control and coil. AC coil at 50/60 Hz without built-in suppressor module, control circuit voltages Us of 24 to 415 V, inrush power 75 VA and hold-in power 9.5 VA at 25 °C; operational range 0.8 to 1.1 Us at 50 Hz and 0.85 to 1.1 Us at 60 Hz, drop-out between 0.2 and 0.75 Us.
Auxiliary contacts. 3 NO poles, auxiliary contact composition 1NO1NC or 2NO2NC, other combinations on request; power circuit closing time 12 to 22 ms and opening time 4 to 19 ms.
Connection and mounting. Screw clamp terminals, tightening torque 1.5 N·m on the power circuit and 1.2 N·m on the control circuit; screw or 35 mm DIN rail mounting; IP20 front face protection conforming to IEC 60529; dimensions 45 x 90 x 96 mm, net weight 0.42 kg.
Environment and standards. Operation from -40 to 60 °C, 60 to 70 °C with derating, operating altitude up to 3000 m, overvoltage category III, fire resistance 850 °C conforming to IEC 60695-2-11. Conforms to IEC/EN 60947-4-1 and IEC/EN 60947-5-1, certified CCC, CE, UKCA, VDE and UL (cULus), RoHS and REACh compliant.
Typical uses. Control of three-phase and single-phase motors, resistive loads and power circuits in industrial control cabinets; the contactor is associated with the circuit breakers and accessories of the UEC1 series.
This product is available on quotation from Atlas Electronics.
No published question about this part yet. Questions are reviewed before publication.
Every characteristic recorded for UEC1-18C, with where it comes from. Use the filters to find one quickly.
| Characteristic | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 32 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO1NC,2NO2NC,other combinations can be customized |
| Average Impedance | 2.7 mΩ - Ith 50 Hz for power circuit |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Voltage Limits | 0.8...1.1 Us (-40…60 °C): operational AC 50 Hz; 0.85...1.1 Us (-40…60 °C): operational AC 60 Hz; 1...1.1 Us (60…70 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…70 °C): drop-out AC 50/60 Hz |
| Control Dircuit Type | AC at 50/60 Hz standard |
| Conventional Free Air Thermal Current [Ith] | 32 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Depth | 96 mm |
| Device Short Name | UEC1-18C |
| Electrical Durability | 1.0 M cycles 18 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 90 mm |
| Hold-in Power Consumption in VA | 9.5 VA 50/60 Hz (at 25 °C) |
| Inrush Power in VA | 75 VA 50/60 Hz (at 25 °C) |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| Maximum Operating Rate | Electrical: 750 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 10 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 1 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 2 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 3 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 5 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 5 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 10 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 15 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 4 kW at 220/230 V AC 50/60 Hz (AC-3); 7.5 kW at 380/400 V AC 50/60 Hz (AC-3); 10 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm DIN Rail |
| Net weight | 0.42 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 30 pcs |
| Operating Altitude | 0...3000 m |
| Operating Time | Power circuit: 12...22 ms closing, 4...19 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...19 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 10.4 cm |
| Package 1 Length | 9.5 cm |
| Package 1 Weight | 0.48 kg |
| Package 1 Width | 5.0 cm |
| Package 2 Height | 25.0 cm |
| Package 2 Length | 32.5 cm |
| Package 2 Weight | 14.40 kg |
| Package 2 Width | 29.0 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL (cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC1 |
| Rated operational current (Ie) | 18 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 32 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Rated Operational Voltage (Ue) | Power circuit: ≤ 690 V AC 50/60Hz |
| Rated Short-Time Withstand Current [Icw] | 145 A ≤40 °C - 10 s for power circuit; 240 A ≤40 °C - 1 s for power circuit; 40 A ≤40 °C - 10 min for power circuit; 84 A ≤40 °C - 1 min for power circuit |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 13 lb.in(1.5 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 13 lb.in(1.5 N·m)- on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 11 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 11 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 42 48 110 115 127 220 230 240 380 400 415 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 45 mm |
No specification matches.
Last verification : 2026-11-02
Official documents and the technical data recorded for UEC1-18C. For a missing document or a specific revision, our experts send it to you.
The Hongfa UEC1-18C is a three-pole power contactor rated 18 A AC-3 for switching motors and power loads up to 690 V AC.
| Parameter | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 32 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO1NC,2NO2NC,other combinations can be customized |
| Average Impedance | 2.7 mΩ - Ith 50 Hz for power circuit |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Voltage Limits | 0.8...1.1 Us (-40…60 °C): operational AC 50 Hz; 0.85...1.1 Us (-40…60 °C): operational AC 60 Hz; 1...1.1 Us (60…70 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…70 °C): drop-out AC 50/60 Hz |
| Control Dircuit Type | AC at 50/60 Hz standard |
| Conventional Free Air Thermal Current [Ith] | 32 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Depth | 96 mm |
| Device Short Name | UEC1-18C |
| Electrical Durability | 1.0 M cycles 18 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 90 mm |
| Hold-in Power Consumption in VA | 9.5 VA 50/60 Hz (at 25 °C) |
| Inrush Power in VA | 75 VA 50/60 Hz (at 25 °C) |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| Maximum Operating Rate | Electrical: 750 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 10 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 1 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 2 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 3 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 5 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 5 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 10 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 15 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 4 kW at 220/230 V AC 50/60 Hz (AC-3); 7.5 kW at 380/400 V AC 50/60 Hz (AC-3); 10 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm DIN Rail |
| Net weight | 0.42 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 30 pcs |
| Operating Altitude | 0...3000 m |
| Operating Time | Power circuit: 12...22 ms closing, 4...19 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...19 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 10.4 cm |
| Package 1 Length | 9.5 cm |
| Package 1 Weight | 0.48 kg |
| Package 1 Width | 5.0 cm |
| Package 2 Height | 25.0 cm |
| Package 2 Length | 32.5 cm |
| Package 2 Weight | 14.40 kg |
| Package 2 Width | 29.0 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL (cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC1 |
| Rated operational current (Ie) | 18 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 32 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Rated Operational Voltage (Ue) | Power circuit: ≤ 690 V AC 50/60Hz |
| Rated Short-Time Withstand Current [Icw] | 145 A ≤40 °C - 10 s for power circuit; 240 A ≤40 °C - 1 s for power circuit; 40 A ≤40 °C - 10 min for power circuit; 84 A ≤40 °C - 1 min for power circuit |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 13 lb.in(1.5 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 13 lb.in(1.5 N·m)- on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 11 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 11 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 42 48 110 115 127 220 230 240 380 400 415 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 45 mm |
Answers to the questions that the recorded characteristics of UEC1-18C can answer. A question is not asked when nothing is recorded to answer it.
Yes — recorded under "Auxiliary Contact Composition": 1NO1NC,2NO2NC,other combinations can be customized.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Three-pole AC power contactor 18 A




Describe your application and constraints in a request.
What is recorded about the regulatory status and the life of this part.
| Current status | Status not stated |
| Key dates | Not recorded |
| Manufacturer part number | UEC1-18C |
| Manufacturer | Hongfa |
Power Contactors
1 Pole + Shunt 20A-40A Definite Purpose Contactor · Ref. : SA-1.5P
Price on request
Power Contactors
Three-pole power contactor 38 A AC-3 AC coil 50/60 Hz
Price on request
Power Contactors
Technical article: relay versus contactor differences
Price on request
Power Contactors
EPS box with integrated contactors for 1-phase/3-phase inverters · Ref. : X1/X3-EPS
Price on request
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details