UEC1-25C
Three-pole 25 A AC-3 power contactor with AC coil

- Hold-in Power Consumption in VA
- 9.5 VA 50/60 Hz (at 25 °C)
- Minimum Switching Current
- 0.1A for signalling circuit
- Mounting Support
- Screw; 35mm DIN Rail
- Number of Units in Package 1
- 1 pcs
Three-pole 25 A AC-3 power contactor with AC coil
The Hongfa UEC1-25C power contactor is a three-pole contactor with an AC 50/60 Hz coil for switching motors and AC loads, rated 25 A in AC-3 utilisation category at 400 V.
Overview. The Hongfa UEC1-25C is a three-pole power contactor from the UEC1 series for switching AC power circuits. It has three NO main poles, an AC 50/60 Hz control coil without built-in suppressor module, and mounts by screw or on a 35 mm DIN rail.
Main characteristics. Rated operational current of 25 A (at ≤ 60 °C) in AC-3 at ≤ 400 V and 40 A in AC-1 at ≤ 690 V. Rated insulation voltage of 690 V conforming to IEC 60947-4-1, rated impulse withstand voltage of 6 kV conforming to IEC 60947, insulation resistance above 10 MΩ for the signalling circuit. Electrical durability of 1.0 million cycles at 25 A AC-3 and mechanical durability of 10 million cycles.
Motor power and switching. Motor power of 5.5 kW at 220/230 V AC, 11 kW at 380/400 V AC and 15 kW at 660/690 V AC in AC-3 category. Rated short-time withstand current of 240 A for 10 s at ≤ 40 °C for the power circuit. Maximum operating rate of 600 cycles/h electrical and 3600 cycles/h mechanical.
Supply and environment. Control voltage range of 0.8 to 1.1 Us at -40…60 °C for AC 50 Hz and 0.85 to 1.1 Us for AC 60 Hz, inrush power of 75 VA and hold-in power of 9.5 VA at 25 °C. IP20 front-face protection conforming to IEC 60529, operation up to 3000 m altitude without derating, and ambient temperature from -40 to 60 °C in normal operation.
Typical use. Control of three-phase and single-phase motors, resistive loads and power circuits in electrical cabinets, in accordance with IEC/EN 60947-4-1 and IEC/EN 60947-5-1.
Integration. Auxiliary contact compositions 1NO1NC and 2NO2NC available depending on configuration, screw clamp terminals with tightening torque of 2.5 N·m for the power circuit and 1.2 N·m for the control circuit.
No published question about this part yet. Questions are reviewed before publication.
Every characteristic recorded for UEC1-25C, with where it comes from. Use the filters to find one quickly.
| Characteristic | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 40 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO1NC,2NO2NC,other combinations can be customized |
| Average Impedance | 2 mΩ - Ith 50 Hz for power circuit |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Voltage Limits | 0.8...1.1 Us (-40…60 °C): operational AC 50 Hz; 0.85...1.1 Us (-40…60 °C): operational AC 60 Hz; 1...1.1 Us (60…70 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…70 °C): drop-out AC 50/60 Hz |
| Control Dircuit Type | AC at 50/60 Hz standard |
| Conventional Free Air Thermal Current [Ith] | 40 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Depth | 100 mm |
| Device Short Name | UEC1-25C |
| Electrical Durability | 1.0 M cycles 25 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 92.5 mm |
| Hold-in Power Consumption in VA | 9.5 VA 50/60 Hz (at 25 °C) |
| Inrush Power in VA | 75 VA 50/60 Hz (at 25 °C) |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| Maximum Operating Rate | Electrical: 600 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 10 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 2 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 3 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 3 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 7.5 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 7.5 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 15 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 20 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 5.5 kW at 220/230 V AC 50/60 Hz (AC-3); 11 kW at 380/400 V AC 50/60 Hz (AC-3); 15 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm DIN Rail |
| Net weight | 0.47 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 30 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...22 ms closing, 4...19 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...19 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 11.1 cm |
| Package 1 Length | 9.9 cm |
| Package 1 Weight | 0.50 kg |
| Package 1 Width | 5.0 cm |
| Package 2 Height | 26.4 cm |
| Package 2 Length | 33.7 cm |
| Package 2 Weight | 15.30 kg |
| Package 2 Width | 29.0 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL (cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC1 |
| Rated operational current (Ie) | 25 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 40 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Rated Operational Voltage (Ue) | Power circuit: ≤ 690 V AC 50/60Hz |
| Rated Short-Time Withstand Current [Icw] | 240 A ≤40 °C - 10 s for power circuit; 380 A ≤40 °C - 1 s for power circuit; 50 A ≤40 °C - 10 min for power circuit; 120 A ≤40 °C - 1 min for power circuit |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 22 lb.in(2.5 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 22 lb.in(2.5 N·m)- on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 42 48 110 115 127 220 230 240 380 400 415 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 45 mm |
No specification matches.
Last verification : 2026-11-02
Official documents and the technical data recorded for UEC1-25C. For a missing document or a specific revision, our experts send it to you.
The Hongfa UEC1-25C power contactor is a three-pole contactor with an AC 50/60 Hz coil for switching motors and AC loads, rated 25 A in AC-3 utilisation category at 400 V.
| Parameter | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 40 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO1NC,2NO2NC,other combinations can be customized |
| Average Impedance | 2 mΩ - Ith 50 Hz for power circuit |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Voltage Limits | 0.8...1.1 Us (-40…60 °C): operational AC 50 Hz; 0.85...1.1 Us (-40…60 °C): operational AC 60 Hz; 1...1.1 Us (60…70 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…70 °C): drop-out AC 50/60 Hz |
| Control Dircuit Type | AC at 50/60 Hz standard |
| Conventional Free Air Thermal Current [Ith] | 40 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Depth | 100 mm |
| Device Short Name | UEC1-25C |
| Electrical Durability | 1.0 M cycles 25 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 92.5 mm |
| Hold-in Power Consumption in VA | 9.5 VA 50/60 Hz (at 25 °C) |
| Inrush Power in VA | 75 VA 50/60 Hz (at 25 °C) |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| Maximum Operating Rate | Electrical: 600 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 10 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 2 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 3 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 3 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 7.5 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 7.5 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 15 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 20 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 5.5 kW at 220/230 V AC 50/60 Hz (AC-3); 11 kW at 380/400 V AC 50/60 Hz (AC-3); 15 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm DIN Rail |
| Net weight | 0.47 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 30 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...22 ms closing, 4...19 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...19 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 11.1 cm |
| Package 1 Length | 9.9 cm |
| Package 1 Weight | 0.50 kg |
| Package 1 Width | 5.0 cm |
| Package 2 Height | 26.4 cm |
| Package 2 Length | 33.7 cm |
| Package 2 Weight | 15.30 kg |
| Package 2 Width | 29.0 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL (cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC1 |
| Rated operational current (Ie) | 25 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 40 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Rated Operational Voltage (Ue) | Power circuit: ≤ 690 V AC 50/60Hz |
| Rated Short-Time Withstand Current [Icw] | 240 A ≤40 °C - 10 s for power circuit; 380 A ≤40 °C - 1 s for power circuit; 50 A ≤40 °C - 10 min for power circuit; 120 A ≤40 °C - 1 min for power circuit |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 22 lb.in(2.5 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 22 lb.in(2.5 N·m)- on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 42 48 110 115 127 220 230 240 380 400 415 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 45 mm |
Answers to the questions that the recorded characteristics of UEC1-25C can answer. A question is not asked when nothing is recorded to answer it.
Yes — recorded under "Auxiliary Contact Composition": 1NO1NC,2NO2NC,other combinations can be customized.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Three-pole 25 A AC-3 power contactor with AC coil




Describe your application and constraints in a request.
What is recorded about the regulatory status and the life of this part.
| Current status | Status not stated |
| Key dates | Not recorded |
| Manufacturer part number | UEC1-25C |
| Manufacturer | Hongfa |
Power Contactors
1 Pole + Shunt 20A-40A Definite Purpose Contactor · Ref. : SA-1.5P
Price on request
Power Contactors
Three-pole power contactor 38 A AC-3 AC coil 50/60 Hz
Price on request
Power Contactors
Technical article: relay versus contactor differences
Price on request
Power Contactors
EPS box with integrated contactors for 1-phase/3-phase inverters · Ref. : X1/X3-EPS
Price on request
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details