UEC1-80C
3-pole 80 A AC-3 contactor with AC coil

- Hold-in Power Consumption in VA
- 21 VA 50/60 Hz (at 25 °C)
- Minimum Switching Current
- 0.1A for signalling circuit
- Mounting Support
- Screw; 35mm or 75mm DIN Rail
- Number of Units in Package 1
- 1 pcs
3-pole 80 A AC-3 contactor with AC coil
The Hongfa UEC1-80C is a 3-pole, 3 NO contactor with an AC coil for switching motor loads, rated 80 A in AC-3 category at 400 V.
Hongfa UEC1-80C contactor. The UEC1-80C is a 3-pole (3P, 3 NO) contactor from Hongfa's UEC1 series, with an AC 50/60 Hz control coil, designed for switching power circuits up to 690 V AC.
Main characteristics. Rated operational current Ie of 80 A (at ≤ 60 °C) in AC-3 at ≤ 400 V, and 125 A (at ≤ 60 °C) in AC-1 at ≤ 690 V. Conventional free air thermal current Ith of 125 A for the power circuit and 10 A for the signalling circuit. Motor power of 22 kW at 220/230 V, 37 kW at 380/400 V and 45 kW at 660/690 V in AC-3. Electrical durability of 0.9 million cycles at 80 A AC-3 and mechanical durability of 3 million cycles.
Auxiliary circuits and interfaces. Auxiliary contact composition 1NO1NC and 2NO2NC, other combinations can be customized. Signalling contacts with a minimum switching current of 0.1 A at a minimum switching voltage of 24 V. Screw clamp terminals for the control circuit and bolt clamp terminals for the power circuit. Control circuit voltage Us available from 24 to 415 V AC.
Power supply and environment. Inrush power of 200 VA and hold-in power of 21 VA at 25 °C, without a built-in suppressor module in the coil. Ambient operating temperature from -40 to 60 °C in normal operation, IP20 degree of protection on the front face and operating altitude up to 3000 m without derating. Overvoltage category III and rated impulse withstand voltage Uimp of 8 kV.
Typical uses. Control of electric motors and power loads in electrical cabinets, mounted on 35 mm or 75 mm DIN rail or by screw fixing, conforming to IEC/EN 60947-4-1 and IEC/EN 60947-5-1.
Integration. The contactor is compatible with the CA1 range accessories (CA1R and CA1S auxiliary contacts, CA1URC and safety cover), which simplifies wiring and protection inside the cabinet. Available on quotation from Atlas Electronics.
No published question about this part yet. Questions are reviewed before publication.
Every characteristic recorded for UEC1-80C, with where it comes from. Use the filters to find one quickly.
| Characteristic | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 100 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO1NC,2NO2NC,other combinations can be customized |
| Average Impedance | 0.8 mΩ - Ith 50 Hz for power circuit |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Voltage Limits | 0.8...1.1 Us (-40…60 °C): operational AC 50 Hz; 0.85...1.1 Us (-40…60 °C): operational AC 60 Hz; 1...1.1 Us (60…70 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…70 °C): drop-out AC 50/60 Hz |
| Control Dircuit Type | AC at 50/60 Hz standard |
| Conventional Free Air Thermal Current [Ith] | 125 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Depth | 137.5 mm |
| Device Short Name | UEC1-80C |
| Electrical Durability | 0.9 M cycles 80 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 121 mm |
| Hold-in Power Consumption in VA | 21 VA 50/60 Hz (at 25 °C) |
| Inrush Power in VA | 200 VA 50/60 Hz (at 25 °C) |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| Maximum Operating Rate | Electrical: 400 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 3 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 7.5 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 15 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 15 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 25 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 30 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 60 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 75 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 22 kW at 220/230 V AC 50/60 Hz (AC-3); 37 kW at 380/400 V AC 50/60 Hz (AC-3); 45 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm or 75mm DIN Rail |
| Net weight | 1.4 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 10 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...26 ms closing, 6...20 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...19 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 15.0 cm |
| Package 1 Length | 13.0 cm |
| Package 1 Weight | 1.42 kg |
| Package 1 Width | 7.9 cm |
| Package 2 Height | 19.2 cm |
| Package 2 Length | 45 cm |
| Package 2 Weight | 15.50 kg |
| Package 2 Width | 30.6 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL (cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC1 |
| Rated operational current (Ie) | 80 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 125 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Rated Operational Voltage (Ue) | Power circuit: ≤ 690 V AC 50/60Hz |
| Rated Short-Time Withstand Current [Icw] | 640 A ≤40 °C - 10 s for power circuit; 990 A ≤40 °C - 1 s for power circuit; 135 A ≤40 °C - 10 min for power circuit; 320 A ≤40 °C - 1 min for power circuit |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 80 lb.in(9 N·m)- on bolt clamp terminals - with internal hexagon socket wrench 4 mm; Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 8 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 42 48 110 115 127 220 230 240 380 400 415 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 70 mm |
No specification matches.
Last verification : 2026-11-02
Official documents and the technical data recorded for UEC1-80C. For a missing document or a specific revision, our experts send it to you.
The Hongfa UEC1-80C is a 3-pole, 3 NO contactor with an AC coil for switching motor loads, rated 80 A in AC-3 category at 400 V.
| Parameter | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 100 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO1NC,2NO2NC,other combinations can be customized |
| Average Impedance | 0.8 mΩ - Ith 50 Hz for power circuit |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Voltage Limits | 0.8...1.1 Us (-40…60 °C): operational AC 50 Hz; 0.85...1.1 Us (-40…60 °C): operational AC 60 Hz; 1...1.1 Us (60…70 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…70 °C): drop-out AC 50/60 Hz |
| Control Dircuit Type | AC at 50/60 Hz standard |
| Conventional Free Air Thermal Current [Ith] | 125 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Depth | 137.5 mm |
| Device Short Name | UEC1-80C |
| Electrical Durability | 0.9 M cycles 80 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 121 mm |
| Hold-in Power Consumption in VA | 21 VA 50/60 Hz (at 25 °C) |
| Inrush Power in VA | 200 VA 50/60 Hz (at 25 °C) |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| Maximum Operating Rate | Electrical: 400 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 3 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 7.5 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 15 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 15 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 25 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 30 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 60 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 75 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 22 kW at 220/230 V AC 50/60 Hz (AC-3); 37 kW at 380/400 V AC 50/60 Hz (AC-3); 45 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm or 75mm DIN Rail |
| Net weight | 1.4 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 10 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...26 ms closing, 6...20 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...19 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 15.0 cm |
| Package 1 Length | 13.0 cm |
| Package 1 Weight | 1.42 kg |
| Package 1 Width | 7.9 cm |
| Package 2 Height | 19.2 cm |
| Package 2 Length | 45 cm |
| Package 2 Weight | 15.50 kg |
| Package 2 Width | 30.6 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL (cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC1 |
| Rated operational current (Ie) | 80 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 125 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Rated Operational Voltage (Ue) | Power circuit: ≤ 690 V AC 50/60Hz |
| Rated Short-Time Withstand Current [Icw] | 640 A ≤40 °C - 10 s for power circuit; 990 A ≤40 °C - 1 s for power circuit; 135 A ≤40 °C - 10 min for power circuit; 320 A ≤40 °C - 1 min for power circuit |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 80 lb.in(9 N·m)- on bolt clamp terminals - with internal hexagon socket wrench 4 mm; Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 8 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 42 48 110 115 127 220 230 240 380 400 415 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 70 mm |
Answers to the questions that the recorded characteristics of UEC1-80C can answer. A question is not asked when nothing is recorded to answer it.
Yes — recorded under "Auxiliary Contact Composition": 1NO1NC,2NO2NC,other combinations can be customized.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
3-pole 80 A AC-3 contactor with AC coil




Describe your application and constraints in a request.
What is recorded about the regulatory status and the life of this part.
| Current status | Status not stated |
| Key dates | Not recorded |
| Manufacturer part number | UEC1-80C |
| Manufacturer | Hongfa |
Power Contactors
1 Pole + Shunt 20A-40A Definite Purpose Contactor · Ref. : SA-1.5P
Price on request
Power Contactors
Three-pole power contactor 38 A AC-3 AC coil 50/60 Hz
Price on request
Power Contactors
Technical article: relay versus contactor differences
Price on request
Power Contactors
EPS box with integrated contactors for 1-phase/3-phase inverters · Ref. : X1/X3-EPS
Price on request
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details