UEC3-06C
3-pole power contactor 6 A AC-3 AC 50/60 Hz coil

- Hold-in Power Consumption in VA
- 9 VA 50/60 Hz (at 25 °C)
- Minimum Switching Current
- 0.1A for signalling circuit
- Mounting Support
- Screw; 35mm DIN Rail
- Number of Units in Package 1
- 1 pcs
3-pole power contactor 6 A AC-3 AC 50/60 Hz coil
Hongfa UEC3-06C three-pole contactor for switching AC loads, rated 6 A in AC-3 utilisation category with a 1NO+1NC auxiliary contact.
Overview. The Hongfa UEC3-06C is a three-pole power contactor with three normally open main contacts (3 NO) from the UEC3 series, designed for switching AC power circuits.
Main characteristics. The conventional free air thermal current is 20 A at 60 °C for the power circuit, and the rated operational current reaches 6 A in AC-3 and 5 A in AC-4 at 400 V AC, and 20 A in AC-1 at 690 V AC. The rated insulation voltage is 690 V according to IEC 60947-4-1 and the rated impulse withstand voltage is 6 kV. Electrical durability is 1.0 million cycles in AC-3 at 6 A, and mechanical durability is 10 million cycles. The maximum operating rate is 1200 cycles/h electrical and 3600 cycles/h mechanical.
Coil supply. The coil is designed for an AC 50/60 Hz control voltage, with operational limits of 0.85 to 1.1 Us and drop-out limits of 0.2 to 0.75 Us. Inrush power is 70 VA and hold-in power 9 VA at 25 °C. The coil has no built-in suppressor module. Available control voltages are 24, 36, 48, 110, 220…230 and 380 V.
Auxiliary contacts. The contactor provides one NO and one NC auxiliary contact, with a conventional free air thermal current of 10 A at 60 °C for the signalling circuit, a minimum switching voltage of 24 V and a minimum switching current of 0.1 A.
Connection and mounting. Screw clamp terminals accept a tightening torque of 1.2 N·m. The contactor mounts on a 35 mm DIN rail or by screws, with a width of 45 mm, a height of 74 mm and a depth of 80 mm. The front face degree of protection is IP20 according to IEC 60529.
Environment. The permissible ambient temperature for normal operation is -40 to 60 °C and the operating altitude is 0 to 3000 m without derating. The overvoltage category is III and the fire resistance of current-carrying parts is 850 °C according to IEC 60695-2-11.
Compliance. The product conforms to IEC/EN 60947-4-1 and IEC/EN 60947-5-1, is certified CCC, CE, UKCA, VDE and UL (cULus), and complies with EU and China RoHS and the REACh regulation.
Typical use. This contactor suits the control of three-phase and single-phase motors, with a rating of 1.5 kW at 220/230 V AC and 2.2 kW at 380/400 V AC in AC-3.
Available on quotation from Atlas Electronics.
No published question about this part yet. Questions are reviewed before publication.
Every characteristic recorded for UEC3-06C, with where it comes from. Use the filters to find one quickly.
| Characteristic | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 32 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO,1NC |
| Average Impedance | 2.7 mΩ - Ith 50 Hz for power circuit |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Voltage Limits | 0.85...1.1 Us (-40…60 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…60 °C): drop-out AC 50/60 Hz |
| Control Dircuit Type | AC at 50/60 Hz standard |
| Depth | 80 mm |
| Device Short Name | UEC3-06C |
| Electrical Durability | 1.0 M cycles 6 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 74 mm |
| Hold-in Power Consumption in VA | 9 VA 50/60 Hz (at 25 °C) |
| [Icw] Rated Short-time Withstand Current | 80 A ≤40 °C - 10 s for power circuit; 45 A ≤40 °C - 1 min for power circuit; 20 A ≤40 °C - 10 min for power circuit |
| [Ie] Rated Operational Current | 6 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 5 A (at ≤60 °C) at ≤ 400 V AC AC-4 for power circuit; 20 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Inrush Power in VA | 70 VA 50/60 Hz (at 25 °C) |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| [Ith] Conventional Free Air Thermal Current | 20 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Maximum Operating Rate | Electrical: 1200 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 10 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 1.5 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 0.75 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 1 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 2 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 2 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 5 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 5 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 1.5 kW at 220/230 V AC 50/60 Hz (AC-3); 2.2 kW at 380/400 V AC 50/60 Hz (AC-3); 3 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm DIN Rail |
| Net weight | 0.31 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 50 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...22 ms closing, 4...22 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...22 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 8.3 cm |
| Package 1 Length | 7.8 cm |
| Package 1 Weight | 0.36 kg |
| Package 1 Width | 4.8 cm |
| Package 2 Height | 19.5 cm |
| Package 2 Length | 41.0 cm |
| Package 2 Weight | 17.3 kg |
| Package 2 Width | 26.0 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL (cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC3 |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 10.7 lb.in (1.2 N·m) - on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 10.7 lb.in (1.2 N·m) - on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 10.7 lb.in (1.2 N·m) - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 10.7 lb.in (1.2 N·m) - on screw clamp terminals - with screwdriver Philips No 2 |
| [Ue]Rated Operational Voltage | Power circuit: ≤ 690 V AC 50/60Hz |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 48 110 220…230 380 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 45 mm |
No specification matches.
Last verification : 2026-11-02
Official documents and the technical data recorded for UEC3-06C. For a missing document or a specific revision, our experts send it to you.
Hongfa UEC3-06C three-pole contactor for switching AC loads, rated 6 A in AC-3 utilisation category with a 1NO+1NC auxiliary contact.
| Parameter | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 32 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO,1NC |
| Average Impedance | 2.7 mΩ - Ith 50 Hz for power circuit |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Voltage Limits | 0.85...1.1 Us (-40…60 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…60 °C): drop-out AC 50/60 Hz |
| Control Dircuit Type | AC at 50/60 Hz standard |
| Depth | 80 mm |
| Device Short Name | UEC3-06C |
| Electrical Durability | 1.0 M cycles 6 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 74 mm |
| Hold-in Power Consumption in VA | 9 VA 50/60 Hz (at 25 °C) |
| [Icw] Rated Short-time Withstand Current | 80 A ≤40 °C - 10 s for power circuit; 45 A ≤40 °C - 1 min for power circuit; 20 A ≤40 °C - 10 min for power circuit |
| [Ie] Rated Operational Current | 6 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 5 A (at ≤60 °C) at ≤ 400 V AC AC-4 for power circuit; 20 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Inrush Power in VA | 70 VA 50/60 Hz (at 25 °C) |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| [Ith] Conventional Free Air Thermal Current | 20 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Maximum Operating Rate | Electrical: 1200 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 10 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 1.5 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 0.75 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 1 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 2 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 2 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 5 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 5 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 1.5 kW at 220/230 V AC 50/60 Hz (AC-3); 2.2 kW at 380/400 V AC 50/60 Hz (AC-3); 3 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm DIN Rail |
| Net weight | 0.31 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 50 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...22 ms closing, 4...22 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...22 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 8.3 cm |
| Package 1 Length | 7.8 cm |
| Package 1 Weight | 0.36 kg |
| Package 1 Width | 4.8 cm |
| Package 2 Height | 19.5 cm |
| Package 2 Length | 41.0 cm |
| Package 2 Weight | 17.3 kg |
| Package 2 Width | 26.0 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL (cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC3 |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 10.7 lb.in (1.2 N·m) - on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 10.7 lb.in (1.2 N·m) - on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 10.7 lb.in (1.2 N·m) - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 10.7 lb.in (1.2 N·m) - on screw clamp terminals - with screwdriver Philips No 2 |
| [Ue]Rated Operational Voltage | Power circuit: ≤ 690 V AC 50/60Hz |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 48 110 220…230 380 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 45 mm |
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
3-pole power contactor 6 A AC-3 AC 50/60 Hz coil




Describe your application and constraints in a request.
What is recorded about the regulatory status and the life of this part.
| Current status | Status not stated |
| Key dates | Not recorded |
| Manufacturer part number | UEC3-06C |
| Manufacturer | Hongfa |
Power Contactors
1 Pole + Shunt 20A-40A Definite Purpose Contactor · Ref. : SA-1.5P
Price on request
Power Contactors
Three-pole power contactor 38 A AC-3 AC coil 50/60 Hz
Price on request
Power Contactors
Technical article: relay versus contactor differences
Price on request
Power Contactors
EPS box with integrated contactors for 1-phase/3-phase inverters · Ref. : X1/X3-EPS
Price on request
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details