UEC3-18C
3-pole power contactor 18 A AC-3, AC 50/60 Hz coil

- Hold-in Power Consumption in VA
- 9 VA 50/60 Hz (at 25 °C)
- Minimum Switching Current
- 0.1A for signalling circuit
- Mounting Support
- Screw; 35mm DIN Rail
- Number of Units in Package 1
- 1 pcs
3-pole power contactor 18 A AC-3, AC 50/60 Hz coil
The Hongfa UEC3-18C is a three-pole power contactor for switching AC loads, rated 18 A in AC-3 up to 400 V.
Overview. The Hongfa UEC3-18C is a three-pole power contactor from the UEC3 series, designed for switching AC power circuits. It has three normally open power poles and one 1 NO + 1 NC auxiliary contact for the signalling circuit.
Main characteristics. Rated operational current Ie of 18 A in AC-3 at 400 V AC, 15 A in AC-4 at 400 V AC and 32 A in AC-1 at 690 V AC, with a conventional free air thermal current Ith of 32 A at 60 °C. Rated insulation voltage Ui of 690 V and rated impulse withstand voltage Uimp of 6 kV. Electrical durability of 1.0 million cycles at 18 A AC-3 and mechanical durability of 10 million cycles. Maximum operating rate of 1200 cycles/h electrical and 3600 cycles/h mechanical.
Control. AC coil at 50/60 Hz, without built-in suppressor module. Standard control circuit voltages of 24, 36, 48, 110, 220…230 and 380 V AC. Inrush power of 70 VA and hold-in power of 9 VA at 25 °C. Operational range of 0.85 to 1.1 Us at -40…60 °C.
Connection and mounting. Screw clamp terminals, tightening torque of 1.2 N·m. Screw or 35 mm DIN rail mounting. IP20 degree of protection on the front face. Dimensions 45 × 74 × 80 mm, net weight 0.31 kg.
Operating conditions. Ambient operating temperature of -40 to 60 °C, operating altitude up to 3000 m without derating, overvoltage category III. Associated fuse protection of 32 A gG at 690 V coordination type 2 for the power circuit and 10 A gG for the signalling circuit.
Certifications. Conforms to IEC/EN 60947-4-1 and IEC/EN 60947-5-1 standards, certified CCC, CE, UKCA, VDE and UL (cULus). Conforms to EU and China RoHS directives, REACh, mercury free.
No published question about this part yet. Questions are reviewed before publication.
Every characteristic recorded for UEC3-18C, with where it comes from. Use the filters to find one quickly.
| Characteristic | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 32 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO,1NC |
| Average Impedance | 2.7 mΩ - Ith 50 Hz for power circuit |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Voltage Limits | 0.85...1.1 Us (-40…60 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…60 °C): drop-out AC 50/60 Hz |
| Control Dircuit Type | AC at 50/60 Hz standard |
| Depth | 80 mm |
| Device Short Name | UEC3-18C |
| Electrical Durability | 1.0 M cycles 18 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 74 mm |
| Hold-in Power Consumption in VA | 9 VA 50/60 Hz (at 25 °C) |
| [Icw] Rated Short-time Withstand Current | 145 A ≤40 °C - 10 s for power circuit; 84 A ≤40 °C - 1 min for power circuit; 40 A ≤40 °C - 10 min for power circuit |
| [Ie] Rated Operational Current | 18 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 15 A (at ≤60 °C) at ≤ 400 V AC AC-4 for power circuit; 32 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Inrush Power in VA | 70 VA 50/60 Hz (at 25 °C) |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| [Ith] Conventional Free Air Thermal Current | 32 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Maximum Operating Rate | Electrical: 1200 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 10 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 1 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 2 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 3 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 5 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 5 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 10 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 15 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 4 kW at 220/230 V AC 50/60 Hz (AC-3); 7.5 kW at 380/400 V AC 50/60 Hz (AC-3); 10 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm DIN Rail |
| Net weight | 0.31 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 50 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...22 ms closing, 4...22 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...22 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 8.3 cm |
| Package 1 Length | 7.8 cm |
| Package 1 Weight | 0.36 kg |
| Package 1 Width | 4.8 cm |
| Package 2 Height | 19.5 cm |
| Package 2 Length | 41.0 cm |
| Package 2 Weight | 17.3 kg |
| Package 2 Width | 26.0 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL (cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC3 |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ue]Rated Operational Voltage | Power circuit: ≤ 690 V AC 50/60Hz |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 48 110 220…230 380 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 45 mm |
No specification matches.
Last verification : 2026-11-02
Official documents and the technical data recorded for UEC3-18C. For a missing document or a specific revision, our experts send it to you.
The Hongfa UEC3-18C is a three-pole power contactor for switching AC loads, rated 18 A in AC-3 up to 400 V.
| Parameter | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 32 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO,1NC |
| Average Impedance | 2.7 mΩ - Ith 50 Hz for power circuit |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Voltage Limits | 0.85...1.1 Us (-40…60 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…60 °C): drop-out AC 50/60 Hz |
| Control Dircuit Type | AC at 50/60 Hz standard |
| Depth | 80 mm |
| Device Short Name | UEC3-18C |
| Electrical Durability | 1.0 M cycles 18 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 74 mm |
| Hold-in Power Consumption in VA | 9 VA 50/60 Hz (at 25 °C) |
| [Icw] Rated Short-time Withstand Current | 145 A ≤40 °C - 10 s for power circuit; 84 A ≤40 °C - 1 min for power circuit; 40 A ≤40 °C - 10 min for power circuit |
| [Ie] Rated Operational Current | 18 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 15 A (at ≤60 °C) at ≤ 400 V AC AC-4 for power circuit; 32 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Inrush Power in VA | 70 VA 50/60 Hz (at 25 °C) |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| [Ith] Conventional Free Air Thermal Current | 32 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Maximum Operating Rate | Electrical: 1200 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 10 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 1 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 2 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 3 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 5 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 5 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 10 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 15 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 4 kW at 220/230 V AC 50/60 Hz (AC-3); 7.5 kW at 380/400 V AC 50/60 Hz (AC-3); 10 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm DIN Rail |
| Net weight | 0.31 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 50 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...22 ms closing, 4...22 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...22 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 8.3 cm |
| Package 1 Length | 7.8 cm |
| Package 1 Weight | 0.36 kg |
| Package 1 Width | 4.8 cm |
| Package 2 Height | 19.5 cm |
| Package 2 Length | 41.0 cm |
| Package 2 Weight | 17.3 kg |
| Package 2 Width | 26.0 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL (cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC3 |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ue]Rated Operational Voltage | Power circuit: ≤ 690 V AC 50/60Hz |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 48 110 220…230 380 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 45 mm |
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
3-pole power contactor 18 A AC-3, AC 50/60 Hz coil




Describe your application and constraints in a request.
What is recorded about the regulatory status and the life of this part.
| Current status | Status not stated |
| Key dates | Not recorded |
| Manufacturer part number | UEC3-18C |
| Manufacturer | Hongfa |
Power Contactors
1 Pole + Shunt 20A-40A Definite Purpose Contactor · Ref. : SA-1.5P
Price on request
Power Contactors
Three-pole power contactor 38 A AC-3 AC coil 50/60 Hz
Price on request
Power Contactors
Technical article: relay versus contactor differences
Price on request
Power Contactors
EPS box with integrated contactors for 1-phase/3-phase inverters · Ref. : X1/X3-EPS
Price on request
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details