UEC3-09N
Three-pole power contactor 9 A AC-3 AC coil

- Average Hold-in Power Consumption in VA
- 9 VA 50/60 Hz (at 25 °C)
- Minimum Switching Current
- 0.1A for signalling circuit
- Mounting Support
- Screw; 35mm DIN Rail
- Number of Units in Package 1
- 1 pcs
Three-pole power contactor 9 A AC-3 AC coil
The Hongfa UEC3-09N is a 3-pole power contactor for switching motors and AC loads, with a 50/60 Hz AC control coil.
Hongfa UEC3-09N power contactor. The Hongfa UEC3-09N is a 3-pole power contactor (3 NO contacts) from the UEC3 series, designed for switching AC power circuits. It is listed in the power contactors category.
Main characteristics. Rated operational current Ie of 9 A in AC-3 at ≤ 400 V AC (≤ 60 °C), 7.5 A in AC-4 at ≤ 400 V AC, and 20 A in AC-1 at ≤ 690 V AC. Rated operational voltage Ue up to 690 V AC 50/60 Hz, rated insulation voltage Ui of 690 V, rated impulse withstand voltage Uimp of 6 kV. Conventional free air thermal current Ith of 20 A for the power circuit and 10 A for the signalling circuit. Average impedance of 2.7 mΩ for the power circuit. Electrical durability of 1.4 million cycles at 9 A AC-3 and mechanical durability of 10 million cycles. Maximum operating rate of 1,200 cycles/h electrical and 3,600 cycles/h mechanical.
Control circuit. AC 50/60 Hz coil without built-in suppressor module, standard control voltages of 24, 36, 48, 110, 220…230 and 380 V. Operational range 0.85 to 1.1 Us at -40…60 °C and drop-out at 0.2 to 0.75 Us. Average hold-in power consumption of 9 VA and inrush power of 70 VA at 50/60 Hz (25 °C). Auxiliary contacts 1 NO and 1 NC, minimum switching voltage 24 V and minimum switching current 0.1 A for the signalling circuit.
Motor power. 2.2 kW at 220/230 V AC (AC-3), 4 kW at 380/400 V AC (AC-3) and 5.5 kW at 660/690 V AC (AC-3). For single-phase motors, 1.5 hp at 110…120 V, 1 hp at 200…208 V and 220…240 V. For three-phase motors, 2 hp at 200…208 V, 3 hp at 220…240 V, 5 hp at 440…480 V and 7.5 hp at 550…600 V.
Mounting and environment. Screw or 35 mm DIN rail mounting, IP20 front face degree of protection per IEC 60529. Screw clamp terminals with 1.2 N·m tightening torque. Ambient operating temperature -40 to 60 °C, 60 to 70 °C with derating, storage -60 to 80 °C. Operating altitude up to 3,000 m without derating. Overvoltage category III. Dimensions 45 × 74 × 80 mm, weight 0.31 kg.
Standards and certifications. Conforms to IEC/EN 60947-4-1 and IEC/EN 60947-5-1, UL 60947-4-1 and UL 60947-5-1, and is certified CCC, CE, UKCA, VDE and UL (cULus). RoHS compliant for the EU and China, REACh conforming and mercury free.
Atlas Electronics offers this UEC3-09N contactor on quotation.
No published question about this part yet. Questions are reviewed before publication.
Every characteristic recorded for UEC3-09N, with where it comes from. Use the filters to find one quickly.
| Characteristic | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 32 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO,1NC |
| Average Hold-in Power Consumption in VA | 9 VA 50/60 Hz (at 25 °C) |
| Average Impedance | 2.7 mΩ - Ith 50 Hz for power circuit |
| Average Inrush Power in VA | 70 VA 50/60 Hz (at 25 °C) |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Type | AC at 50/60 Hz standard |
| Control Circuit Voltage Limits | 0.85...1.1 Us (-40…60 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…60 °C): drop-out AC 50/60 Hz |
| Depth | 80 mm |
| Device Short Name | UEC3-09N |
| Electrical Durability | 1.4 M cycles 9 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 74 mm |
| [Icw] Rated Short-time Withstand Current | 105 A ≤40 °C - 10 s for power circuit; 61 A ≤40 °C - 1 min for power circuit; 30 A ≤40 °C - 10 min for power circuit |
| [Ie] Rated Operational Current | 9 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 7.5 A (at ≤60 °C) at ≤ 400 V AC AC-4 for power circuit; 20 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| [Ith] Conventional Free Air Thermal Current | 20 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Maximum Operating Rate | Electrical: 1200 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 10 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 1.5 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 1 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 1 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 2 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 3 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 5 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 7.5 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 2.2 kW at 220/230 V AC 50/60 Hz (AC-3); 4 kW at 380/400 V AC 50/60 Hz (AC-3); 5.5 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm DIN Rail |
| Net weight | 0.31 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 50 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...22 ms closing, 4...22 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...22 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 8.3 cm |
| Package 1 Length | 7.8 cm |
| Package 1 Weight | 0.36 kg |
| Package 1 Width | 4.8 cm |
| Package 2 Height | 19.5 cm |
| Package 2 Length | 41.0 cm |
| Package 2 Weight | 17.3 kg |
| Package 2 Width | 26.0 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL (cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC3 |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ue]Rated Operational Voltage | Power circuit: ≤ 690 V AC 50/60Hz |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 48 110 220…230 380 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 45 mm |
No specification matches.
Last verification : 2026-11-02
Official documents and the technical data recorded for UEC3-09N. For a missing document or a specific revision, our experts send it to you.
The Hongfa UEC3-09N is a 3-pole power contactor for switching motors and AC loads, with a 50/60 Hz AC control coil.
| Parameter | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 32 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO,1NC |
| Average Hold-in Power Consumption in VA | 9 VA 50/60 Hz (at 25 °C) |
| Average Impedance | 2.7 mΩ - Ith 50 Hz for power circuit |
| Average Inrush Power in VA | 70 VA 50/60 Hz (at 25 °C) |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Type | AC at 50/60 Hz standard |
| Control Circuit Voltage Limits | 0.85...1.1 Us (-40…60 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…60 °C): drop-out AC 50/60 Hz |
| Depth | 80 mm |
| Device Short Name | UEC3-09N |
| Electrical Durability | 1.4 M cycles 9 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 74 mm |
| [Icw] Rated Short-time Withstand Current | 105 A ≤40 °C - 10 s for power circuit; 61 A ≤40 °C - 1 min for power circuit; 30 A ≤40 °C - 10 min for power circuit |
| [Ie] Rated Operational Current | 9 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 7.5 A (at ≤60 °C) at ≤ 400 V AC AC-4 for power circuit; 20 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| [Ith] Conventional Free Air Thermal Current | 20 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Maximum Operating Rate | Electrical: 1200 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 10 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 1.5 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 1 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 1 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 2 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 3 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 5 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 7.5 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 2.2 kW at 220/230 V AC 50/60 Hz (AC-3); 4 kW at 380/400 V AC 50/60 Hz (AC-3); 5.5 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm DIN Rail |
| Net weight | 0.31 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 50 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...22 ms closing, 4...22 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...22 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 8.3 cm |
| Package 1 Length | 7.8 cm |
| Package 1 Weight | 0.36 kg |
| Package 1 Width | 4.8 cm |
| Package 2 Height | 19.5 cm |
| Package 2 Length | 41.0 cm |
| Package 2 Weight | 17.3 kg |
| Package 2 Width | 26.0 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL (cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC3 |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ue]Rated Operational Voltage | Power circuit: ≤ 690 V AC 50/60Hz |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 48 110 220…230 380 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 45 mm |
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Three-pole power contactor 9 A AC-3 AC coil




Describe your application and constraints in a request.
What is recorded about the regulatory status and the life of this part.
| Current status | Status not stated |
| Key dates | Not recorded |
| Manufacturer part number | UEC3-09N |
| Manufacturer | Hongfa |
Power Contactors
1 Pole + Shunt 20A-40A Definite Purpose Contactor · Ref. : SA-1.5P
Price on request
Power Contactors
Three-pole power contactor 38 A AC-3 AC coil 50/60 Hz
Price on request
Power Contactors
Technical article: relay versus contactor differences
Price on request
Power Contactors
EPS box with integrated contactors for 1-phase/3-phase inverters · Ref. : X1/X3-EPS
Price on request
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details