UEC3-12N
3-pole power contactor 12 A AC coil 50/60 Hz

- Average Hold-in Power Consumption in VA
- 9 VA 50/60 Hz (at 25 °C)
- Minimum Switching Current
- 0.1A for signalling circuit
- Mounting Support
- Screw; 35mm DIN Rail
- Number of Units in Package 1
- 1 pcs
3-pole power contactor 12 A AC coil 50/60 Hz
Hongfa UEC3-12N 3P power contactor with AC 50/60 Hz coil, designed for switching motors and power loads up to 690 V.
Overview. The Hongfa UEC3-12N is a 3-pole (3 NO contacts) power contactor from the UEC3 series, with an AC 50/60 Hz control coil, designed for switching loads on the power circuit.
Main characteristics. Rated operational current Ie of 12 A (at ≤ 60 °C) in AC-3 at ≤ 400 V, 10 A in AC-4 and 25 A in AC-1 at ≤ 690 V. Conventional free air thermal current Ith of 25 A (at ≤ 60 °C) for the power circuit. Rated insulation voltage Ui of 690 V conforming to IEC 60947-4-1, rated impulse withstand voltage Uimp of 6 kV. Auxiliary contact composition 1NO+1NC, conventional thermal current of 10 A for the signalling circuit. Electrical durability of 1.4 million cycles at 12 A AC-3 at ≤ 400 V and mechanical durability of 10 million cycles. Maximum operating rate of 1200 cycles/h electrical and 3600 cycles/h mechanical.
Control voltage and motor power. Control circuit voltages Us of 24, 36, 48, 110, 220…230 and 380 V AC 50/60 Hz, operational range 0.85 to 1.1 Us. Motor power of 3 kW at 220/230 V AC (AC-3), 5.5 kW at 380/400 V AC (AC-3) and 7.5 kW at 660/690 V AC (AC-3). Average hold-in power consumption of 9 VA and inrush power of 70 VA at 25 °C.
Environment and safety. Operating ambient temperature from -40 to 60 °C, operating altitude up to 3000 m without derating, IP20 degree of protection on the front face conforming to IEC 60529, overvoltage category III. Fire resistance of current-carrying parts at 850 °C conforming to IEC 60695-2-11. Conforming to EU and China RoHS, mercury free.
Mounting and connection. Screw or 35 mm DIN rail mounting, screw clamp terminals with tightening torque of 1.2 N·m. Dimensions 45 × 74 × 80 mm, net weight 0.31 kg. Associated fuse of 32 A gG coordination type 2 for the power circuit and 10 A gG for the signalling circuit.
Standards and certifications. Conforms to IEC/EN 60947-4-1 and IEC/EN 60947-5-1 standards, certified CE, UKCA, VDE, UL (cULus) and CCC.
No published question about this part yet. Questions are reviewed before publication.
Every characteristic recorded for UEC3-12N, with where it comes from. Use the filters to find one quickly.
| Characteristic | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 32 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO,1NC |
| Average Hold-in Power Consumption in VA | 9 VA 50/60 Hz (at 25 °C) |
| Average Impedance | 2.7 mΩ - Ith 50 Hz for power circuit |
| Average Inrush Power in VA | 70 VA 50/60 Hz (at 25 °C) |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Type | AC at 50/60 Hz standard |
| Control Circuit Voltage Limits | 0.85...1.1 Us (-40…60 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…60 °C): drop-out AC 50/60 Hz |
| Depth | 80 mm |
| Device Short Name | UEC3-12N |
| Electrical Durability | 1.4 M cycles 12 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 74 mm |
| [Icw] Rated Short-time Withstand Current | 105 A ≤40 °C - 10 s for power circuit; 61 A ≤40 °C - 1 min for power circuit; 30 A ≤40 °C - 10 min for power circuit |
| [Ie] Rated Operational Current | 12 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 10 A (at ≤60 °C) at ≤ 400 V AC AC-4 for power circuit; 25 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| [Ith] Conventional Free Air Thermal Current | 25 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Maximum Operating Rate | Electrical: 1200 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 10 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 0.75 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 2 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 2 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 3 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 3 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 7.5 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 10 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 3 kW at 220/230 V AC 50/60 Hz (AC-3); 5.5 kW at 380/400 V AC 50/60 Hz (AC-3); 7.5 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm DIN Rail |
| Net weight | 0.31 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 50 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...22 ms closing, 4...22 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...22 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 8.3 cm |
| Package 1 Length | 7.8 cm |
| Package 1 Weight | 0.36 kg |
| Package 1 Width | 4.8 cm |
| Package 2 Height | 19.5 cm |
| Package 2 Length | 41.0 cm |
| Package 2 Weight | 17.3 kg |
| Package 2 Width | 26.0 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL (cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC3 |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ue]Rated Operational Voltage | Power circuit: ≤ 690 V AC 50/60Hz |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 48 110 220…230 380 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 45 mm |
No specification matches.
Last verification : 2026-11-02
Official documents and the technical data recorded for UEC3-12N. For a missing document or a specific revision, our experts send it to you.
Hongfa UEC3-12N 3P power contactor with AC 50/60 Hz coil, designed for switching motors and power loads up to 690 V.
| Parameter | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 32 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO,1NC |
| Average Hold-in Power Consumption in VA | 9 VA 50/60 Hz (at 25 °C) |
| Average Impedance | 2.7 mΩ - Ith 50 Hz for power circuit |
| Average Inrush Power in VA | 70 VA 50/60 Hz (at 25 °C) |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Type | AC at 50/60 Hz standard |
| Control Circuit Voltage Limits | 0.85...1.1 Us (-40…60 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…60 °C): drop-out AC 50/60 Hz |
| Depth | 80 mm |
| Device Short Name | UEC3-12N |
| Electrical Durability | 1.4 M cycles 12 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 74 mm |
| [Icw] Rated Short-time Withstand Current | 105 A ≤40 °C - 10 s for power circuit; 61 A ≤40 °C - 1 min for power circuit; 30 A ≤40 °C - 10 min for power circuit |
| [Ie] Rated Operational Current | 12 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 10 A (at ≤60 °C) at ≤ 400 V AC AC-4 for power circuit; 25 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| [Ith] Conventional Free Air Thermal Current | 25 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Maximum Operating Rate | Electrical: 1200 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 10 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 0.75 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 2 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 2 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 3 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 3 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 7.5 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 10 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 3 kW at 220/230 V AC 50/60 Hz (AC-3); 5.5 kW at 380/400 V AC 50/60 Hz (AC-3); 7.5 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm DIN Rail |
| Net weight | 0.31 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 50 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...22 ms closing, 4...22 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...22 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 8.3 cm |
| Package 1 Length | 7.8 cm |
| Package 1 Weight | 0.36 kg |
| Package 1 Width | 4.8 cm |
| Package 2 Height | 19.5 cm |
| Package 2 Length | 41.0 cm |
| Package 2 Weight | 17.3 kg |
| Package 2 Width | 26.0 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL (cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC3 |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ue]Rated Operational Voltage | Power circuit: ≤ 690 V AC 50/60Hz |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 48 110 220…230 380 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 45 mm |
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
3-pole power contactor 12 A AC coil 50/60 Hz




Describe your application and constraints in a request.
What is recorded about the regulatory status and the life of this part.
| Current status | Status not stated |
| Key dates | Not recorded |
| Manufacturer part number | UEC3-12N |
| Manufacturer | Hongfa |
Power Contactors
1 Pole + Shunt 20A-40A Definite Purpose Contactor · Ref. : SA-1.5P
Price on request
Power Contactors
Three-pole power contactor 38 A AC-3 AC coil 50/60 Hz
Price on request
Power Contactors
Technical article: relay versus contactor differences
Price on request
Power Contactors
EPS box with integrated contactors for 1-phase/3-phase inverters · Ref. : X1/X3-EPS
Price on request
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details