UEM5Z1-800 – Molded Case Circuit Breaker 800 A 3P/4P

Molded Case Circuit Breaker 800 A 3P/4P

Molded Case Circuit Breakers

  • UEM5Z1
  • 800 A at 40 °C
  • 50 Hz
  • -40…70 °C
Manufacturer part number
UEM5Z1-800
Manufacturer
Hongfa
Range
UEM5Z1
Rated Current (In)
800 A at 40 °C

The Hongfa UEM5Z1-800 is an 800 A distribution molded case circuit breaker for AC networks, compliant with EN/IEC 60947-2, for protecting 400 V AC 50 Hz circuits.

Product overview

Hongfa UEM5Z1-800. distribution molded case circuit breaker (MCCB) rated 800 A at 40 °C, for 400 V AC 50 Hz networks, compliant with EN/IEC 60947-2.

Main characteristics. Rated insulation voltage 800 V AC 50 Hz, rated impulse withstand voltage 8 kV, utilisation category B, and suitability for isolation conforming to EN/IEC 60947-2. The LSIP thermal-magnetic trip unit provides overload long-time delay protection, short-circuit short-time delay and instantaneous protection, and pre-alarm protection.

Settings and protection. Long-time pick-up Ir adjustable from 450 A to 800 A, long-time delay tr of 12 s to 100 s or OFF, short-time pick-up Isd of 2 to 12 times Ir with delay tsd of 0.06 s to 0.3 s, instantaneous pick-up Ii of 3 to 12 times In or OFF, and pre-alarm Ip of 0.7 to 1.0 times Ir.

Breaking capacity. Icu of 65 kA (M version) or 85 kA (H version) at 400 V AC 50 Hz, Ics of 50 kA (M) or 65 kA (H) at 400 V AC 50 Hz, conforming to EN/IEC 60947-2. Electrical endurance of 500 cycles at 400 V In and mechanical endurance of 2500 cycles.

Mounting and accessories. Fixed, plug-in or withdrawable mounting, horizontal or vertical flat on the back. Connection pitch 70 mm, available in 3P (9.5 kg) or 4P (12.5 kg). Compatible accessories: shunt release, auxiliary contacts, alarm contact, undervoltage release, handle, motorized or rotary operating mechanism.

Operating environment. Operating ambient temperature -25 to 70 °C, storage -40 to 70 °C, relative humidity 0 to 95 % at 25 °C, operating altitude 0 to 2000 m without derating and 2000 to 4000 m with derating, pollution degree 3 conforming to IEC 60664-1. Arcing distance of 50 mm or less.

Typical use. Distribution circuit breaker for supplying and protecting outgoing feeders on 400 V AC networks, in electrical enclosures sized for an 800 A rating.

Certifications. CCC and CB. China RoHS declaration available, substance declaration provided for information.

See all specifications

Highlights

  • Ambient Air Temperature for Operation: -25…70 °C
  • Ambient Air Temperature for Storage: -40…70 °C
  • Arcing Distance (mm): ≤50mm
  • Breaking Capacity: M、H
  • Connection Pitch: 70 mm
  • Depth: 104 mm

See also

Technical questions

Ask a question

No published question about this part yet. Questions are reviewed before publication.