Product overview
Overview. The IAMMETER WEM3080TD is a three-phase energy meter designed for 3-phase 3-wire Delta networks, which have no neutral wire. It measures power and energy on phases A and C, with phase B used as the reference.
Main characteristics. The meter accepts a line-to-line input voltage of 140 to 480 VAC. It is supplied with current transformers of 16 mm diameter for 150 A, 24.5 mm for 250 A and 35 mm for 500 A. The housing measures 90.2 × 71 × 57.5 mm and occupies two DIN poles. Weight ranges from 0.62 kg (150 A model) to 1.40 kg (500 A model).
Connectivity. The meter is configured through the mobile app or a browser and connects to the site's Wi-Fi network, allowing remote data monitoring through the IAMMETER Cloud.
Integration. In the standard wiring, UA, UB and UC connect to phases A, B and C, with a CT on phase A and a CT on phase C; the phase B CT is not used. Each CT direction (K to L) must follow phase A to phase B for CT A and phase C to phase B for CT C. Negative power readings usually indicate reversed CTs or incorrect phase order. For a 3-phase 4-wire WYE/Star system, the documentation recommends the WEM3080T instead.