| Analog Inputs | 2 switchable channels: 4–20 mA, 0–10 V or digital, 12-bit |
| Application — Instrument — Signal and power | Reporting |
| Boiler, steam and compressed air — Pressure and temperature transmitters — 4–20 mA | Trigger on the alarm limits, plus a periodic reading |
| Broken-wire detection — Yes: the reading drops below 4 mA — No: 0 V is also a valid reading | Depends on how the contact is wired |
| Choose it for | Scattered tanks, borewells, pipelines and plant rooms, with or without power, kilometres from the control room |
| Compare — 2-wire (loop powered) — 3-wire | 4-wire (self powered) |
| Compare — 4–20 mA current loop — 0–10 V voltage | Digital input |
| Criterion — Macnman MacSync LX1 — Dragino PS-LB-NA — Milesight UC501 / UC502 | Seeed SenseCAP S2100 |
| Diesel and chemical tank level — Level transmitter and a float switch — 4–20 mA and a digital input | Trigger on low level and on the float changing state |
| Electrical noise — Highly immune — More susceptible | Not an analog signal |
| HVAC and building services — Duct pressure, CO₂ and humidity transmitters — 0–10 V | Periodic, every few minutes on the 9–36 V DC variant |
| Loop current — Share of span — 0–10 bar pressure transmitter — 0–5 m level transmitter | What it means |
| Network | LoRaWAN® v1.0.4 through a gateway, or MacTalk device to device |
| On the MacSync LX1 — Either channel, 12-bit | Either channel, with state-change detection |
| Outputs | None: it measures and reports |
| Pipeline and pump pressure — Pressure transmitter — 2-wire 4–20 mA | Periodic, with a trigger outside the safe band |
| Power | 19 Ah battery or 9–36 V DC |
| Power and signal — The same two wires — A separate supply wire, with a shared return | A supply pair and a separate signal pair |
| Pump, DG set and panel status — Run and trip contacts — Digital inputs | Uplink on state change |
| Resolution — 12-bit — 0.001 mA resolution · 0.02 mA accuracy — 12-bit | Not on the page checked |
| SKUs | 83301 battery · 83300 DC · 83303 / 83302 MacTalk · 83304 BLE |
| What it carries — A measurement, sent as a current — A measurement, sent as a voltage | An on or off state |