| Baud rate | Up to 115,200 bps |
| Baud rate — 1,200 to 115,200 bps | All slaves on the bus must use the same rate |
| Choose it for | Meters and panels spread over a site or a campus, with or without power, kilometres from the control room |
| Configuration | AT commands · downlink · RS485-LB adds Bluetooth |
| Data types — INT16 · UINT16 · INT32 · FLOAT32 | 32-bit values with the most or the least significant word first |
| Device — What it reads — Typical setup | Reporting |
| Devices and reads | RS485-LN: up to 32 RS485 devices · 15 commands per sampling |
| Enclosure | RS485-LB: IP67 · −40 to +85 °C · RS485-LN: not on the page checked |
| FPort — What it does — Typical use | Example payload |
| Frame — 8 data bits · none, even or odd parity · 1 stop bit | Parity can be changed by downlink |
| Function codes — 03 and 04 to read · 06 and 16 to write | Coils are written by downlink |
| LoRaWAN | v1.0.3 · RS485-LN Class A and C, default C · RS485-LB Class A |
| Modbus | RTU master on 1 × RS485 · function codes 03, 04, 06, 16 |
| Modbus role | RS485 with Modbus support · quick command for function codes 01 to 04 |
| Modbus role — RTU master | Your meter, drive or PLC stays a slave; nothing changes on its side |
| Network | LoRaWAN® v1.0.4 through a gateway, or MacTalk device to device |
| Other inputs | RS485-LB: UART, I²C, 1-Wire and one digital pin |
| Outputs | None: it reads and reports |
| PLC or RTU — Holding registers the PLC exposes as a slave — No change to the PLC program beyond its Modbus map | Periodic, with triggers on alarm values |
| Port — 1 × RS485, half-duplex | Several slaves share the same two wires |
| Power | 19 Ah battery or 9–36 V DC |
| Powers the connected device | RS485-LB: 3.3 V and 5 V outputs; RS485W-LB adds 12 V |
| Register address — 0 to 65,535 | Protocol addresses count from zero; many manuals print 40001-style numbers |
| Registers per read — 1 to 125 in one group | For example 2 registers for one FLOAT32 value |
| Setting — MacSync LX1 | Notes |
| SF10–SF12 (longest range) — 51 bytes — up to 25 — up to 12 | about 15 × 16-bit, or 9 × 32-bit |
| SF7–SF8 (shortest range) — 222 bytes — up to 111 — up to 55 | about 70 × 16-bit, or 40 × 32-bit |
| SF9 — 115 bytes — up to 57 — up to 28 | about 35 × 16-bit, or 20 × 32-bit |
| SKUs | 83301 battery · 83300 DC · 83303 / 83302 MacTalk · 83304 BLE |
| Slave ID — 1 to 247 | One ID per device on the bus |
| Spreading factor — Max payload — 16-bit registers — 32-bit values | Plan for |
| US915 at its slowest rate — 11 bytes — up to 5 — up to 2 | 1 value |