ODOT DN-8031 network adapter connecting distributed I/O modules to a standard Modbus TCP network, with an OLED diagnostic screen and removable spring-clamp terminals.
Overview. The ODOT Automation DN-8031 is a Modbus TCP IO network adapter designed to connect distributed I/O modules to a standard Ethernet Modbus TCP network, acting as a Modbus TCP server.
Main characteristics. The unit has an OLED screen displaying the IP address, subnet mask and gateway for immediate verification on site. Its default IP address is 192.168.1.100, settable by dial switch or with the IO Config software. It supports Modbus function codes 01, 02, 03, 04, 05, 06, 15, 16 and 23, together with Modbus watchdog. The minimum cycle time is 0.6 ms and expansion reaches 32 modules. The maximum process data capacity is 8192 bytes of input and 8192 bytes of output.
Interfaces and connectivity. Two RJ45 ports with integrated switch capabilities provide Ethernet communication at 10/100 Mbit/s, full-duplex, with auto negotiation and automatic MDI/MDIX. The maximum segment length is 100 m between two sites. Spring-clamp terminals accept conductors from 0.2 mm² (AWG24) to 1.5 mm² (AWG16) and the whole wiring block can be removed without disconnecting individual wires.
Power and environment. The field power supply is 19.2 to 28.8 VDC (nominal 24 VDC) with anti-inversion protection, and the maximum field power current is 8 A. Module consumption is 78 mA at 24 VDC and the maximum internal bus supply current is 2 A at 5 VDC. The internal bus, system power and field power are isolated. Operating temperature is -35 °C to 60 °C in horizontal installation and -35 °C to 50 °C in vertical installation, storage temperature -40 °C to 85 °C, humidity 5% to 95% RH without condensation, installation altitude below 2000 m, pollution degree II and protection grade IP20. Mounts on 35 mm DIN rail. Dimensions 119 × 83 × 80 mm.
Typical uses. This adapter suits connecting distributed I/O to Modbus TCP client controllers such as PLCs over a standard Ethernet network, without specialised hardware.
Compliance. The product carries CE certification, and the manufacturer cites the electromagnetic compatibility standards IEC 61131-2 and IEC 61000-4, with ESD tests of ±6 kV contact and ±8 kV air discharge.
ODOT DN-8031 network adapter connecting distributed I/O modules to a standard Modbus TCP network, with an OLED diagnostic screen and removable spring-clamp terminals.
Communication diagnostics, extended module status diagnostics
Dimension
119*83*80mm
EMC Performance
Comply with IEC61131-2, IEC61000-4; (ESD: Contact discharge±6kV, Air discharge±8kV, Performance; level A
Environment Humidity
5%~95%RH (No condensation)
Field Power
19.2~28.8VDC (Nominal: 24VDC)
Field Power Current
Max. DC 8A
Horizontal Installation Operating Temperature
-35℃~60℃
Installation
35mm DIN-Rail
Installation Altitude
<2000m
Insulation Withstand
Comply with IEC61131-2
Interface
2*RJ45, integrated switch capabilities
Internal Bus Supply Current
Max.2A@5VDC
IP Address Setting
Dial switch or IO Config software
Line Length
Maximum 100m (segment length) between 2 sites
Maximum Number of; Input/Output Bytes
Input: 8192 Bytes; Output: 8192 Bytes; The maximum number of input and output: 8192 Bytes
Mechanical properties
Comply with IEC60068-2-6, IEC6008-2-27
Modbus Function Code
01/02/03/04/05/06/15/16/23
Modbus Watchdog
Support
Module Consumption
78mA@24VDC
Pollution Degree
Ⅱ
Product Certification
CE Certification
Protection Grade
IP20
Protocol
Modbus TCP server
Redundancy Mode
Not supported
Storage Temperature
-40℃~85℃
System — Power
19.2~28.8VDC (Nominal: 24VDC); Anti-inversion protection: support
TCP Timed; Maintenance
Support
Terminal Pluggable
Support
Transmission Speed
10/100 Mbit/s, full-duplex
Vertical Installation Operating Temperature
-35℃~50℃
Wirring Diameter
Min.0.2mm²(AWG24); Max.1.5mm²(AWG16)
Integration
Points to check before using DN-8031 in a design. They are derived from the recorded characteristics, not from the manufacturer's application circuits.
1Thermalrated operating range -35℃~60℃ — check it against the installation environment.
2Thermalrated operating range -35℃~50℃ — check it against the installation environment.
Power and communication
Field Power
19.2~28.8VDC (Nominal: 24VDC)
Field Power Current
Max. DC 8A
Internal Bus Supply Current
Max.2A@5VDC
Module Consumption
78mA@24VDC
System — Power
19.2~28.8VDC (Nominal: 24VDC); Anti-inversion protection: support
Check the exact pin assignment and the application circuit in the datasheet, or ask our experts.
Implementation checklist
Thermal : rated operating range -35℃~60℃ — check it against the installation environment.
Thermal : rated operating range -35℃~50℃ — check it against the installation environment.
Technical FAQ
Answers to the questions that the recorded characteristics of DN-8031 can answer. A question is not asked when nothing is recorded to answer it.
1Does it support Modbus?
Yes — recorded under "Modbus Function Code": 01/02/03/04/05/06/15/16/23.