Pilot SPM73 multifunction three-phase energy meter for high and low voltage distribution systems, installed in distribution panels and switchgear.
Operating Temperature-25 ℃~+60 ℃
Rated input voltage3x 57.7/100V,3x 220/380V
Direct Current Connection5mA to 6.5A,Accuracy 0.2%
Rated Input Current1(1.2)A, 5(6)A,Configurable
Frequency40 to 70Hz, Accuracy 0.1%
EFT/B ImmunityIEC 61000-4-4:2012,level 4
Product overview
Overview. The Pilot SPM73 three-phase energy meter is a multifunction panel meter designed for high and low voltage distribution systems. The manufacturer presents it as the updated version of the SPM33.
Main characteristics. The meter measures current through direct input from 5 mA to 6.5 A with 0.2% accuracy, and voltage through direct input from 10 to 400 V (L-N) or 10 to 690 V (L-L) with the same 0.2% accuracy. Frequency is measured from 40 to 70 Hz with 0.1% accuracy. Rated input current is configurable as 1(1.2) A or 5(6) A, and the rated input voltage is 3x 57.7/100 V or 3x 220/380 V. Q functions include power quality analysis, multi-tariff energy measurement, SOE recording and extreme value recording. Depending on the configuration, the display is a segmented LCD (L02, L05) or a dot-matrix LCD (B02, B05), with Class 0.2S or 0.5S accuracy for active energy; options B02 and B05 require option modules E4, E5 or E6, and L05 is the default configuration.
Interfaces and connectivity. The RS-485 port operates from 4800 to 19200 bps and supports the Modbus-RTU protocol, allowing data exchange with PLCs or SCADA supervisory systems. The relay outputs have a rated contact capacity of 250 V AC / 5 A and 30 V DC / 5 A.
Power and environment. The auxiliary supply accepts 85 to 275 V AC or 100 to 300 V DC. The meter operates between -25 °C and +60 °C and has an IP54 protection rating on the panel front.
Electromagnetic compatibility. Immunity to electrical fast transients (EFT/B, IEC 61000-4-4:2012, level 4), electrostatic discharge (ESD, IEC 61000-4-2:2008, level 4), surge (IEC 61000-4-5:2014, level 4) and radiated RF fields (IEC 61000-4-3:2010, level 3) meets the cited standards. Electromagnetic emission complies with CISPR22:2006, class B.
Typical uses. The SPM73 is installed in distribution panels, switchgear and other power distribution applications, where it enables centralized metering and automated control through a supervisory system.
No published question about this part yet. Questions are reviewed before publication.
Complete specifications
Every characteristic recorded for SPM73, with where it comes from. Use the filters to find one quickly.
All specifications (20)
Characteristic
Value
B02
Dot-matrix LCD display, Class 0.2S(Active Energy), with scheduled data logging
B05
Dot-matrix LCD display, Class 0.5S(Active Energy), with scheduled data logging; Notes: L05 is the default configuration; B02 and B05 are available only when option modules E4, E5, or E6 are selected
Direct Current Connection
5mA to 6.5A,Accuracy 0.2%
Direct Voltage Connection
10 to 400V(L-N),10 to 690V(L-L),Accuracy 0.2%
EFT/B Immunity
IEC 61000-4-4:2012,level 4
EMI Emission
CISPR22:2006,level B
ESD Immunity
IEC 61000-4-2:2008,level 4
Frequency
40 to 70Hz, Accuracy 0.1%
IP Protection
IP54(Panel)
L02
Segmented LCD display, Class 0.2S(Active Energy)
L05
Segmented LCD display, Class 0.5S(Active Energy)
Operating Temperature
-25 ℃~+60 ℃
Power supply
85 to 275V AC,100 to 300V DC
Q
Power Quality Analysis, Multi-tariff Energy Measurement, SOE, Extreme value Recording; Notes:No extended function is included by default.
Radiated RF Immunity
IEC 61000-4-3:2010,level 3
Rated Contact Capacity of Relay Output
250V AC/5A,30V DC/5A
Rated Input Current
1(1.2)A, 5(6)A,Configurable
Rated input voltage
3x 57.7/100V,3x 220/380V
RS-485
4800 to 19200bps
Surge Immunity
IEC 61000-4-5:2014,level 4
No specification matches.
Last verification : 2026-11-03
Technical documentation
Official documents and the technical data recorded for SPM73. For a missing document or a specific revision, our experts send it to you.
Pilot SPM73 multifunction three-phase energy meter for high and low voltage distribution systems, installed in distribution panels and switchgear.
Operating Temperature-25 ℃~+60 ℃
Rated input voltage3x 57.7/100V,3x 220/380V
Direct Current Connection5mA to 6.5A,Accuracy 0.2%
Rated Input Current1(1.2)A, 5(6)A,Configurable
Frequency40 to 70Hz, Accuracy 0.1%
2. Datasheet extract (recorded values)
Parameter
Value
B02
Dot-matrix LCD display, Class 0.2S(Active Energy), with scheduled data logging
B05
Dot-matrix LCD display, Class 0.5S(Active Energy), with scheduled data logging; Notes: L05 is the default configuration; B02 and B05 are available only when option modules E4, E5, or E6 are selected
Direct Current Connection
5mA to 6.5A,Accuracy 0.2%
Direct Voltage Connection
10 to 400V(L-N),10 to 690V(L-L),Accuracy 0.2%
EFT/B Immunity
IEC 61000-4-4:2012,level 4
EMI Emission
CISPR22:2006,level B
ESD Immunity
IEC 61000-4-2:2008,level 4
Frequency
40 to 70Hz, Accuracy 0.1%
IP Protection
IP54(Panel)
L02
Segmented LCD display, Class 0.2S(Active Energy)
L05
Segmented LCD display, Class 0.5S(Active Energy)
Operating Temperature
-25 ℃~+60 ℃
Power supply
85 to 275V AC,100 to 300V DC
Q
Power Quality Analysis, Multi-tariff Energy Measurement, SOE, Extreme value Recording; Notes:No extended function is included by default.
Radiated RF Immunity
IEC 61000-4-3:2010,level 3
Rated Contact Capacity of Relay Output
250V AC/5A,30V DC/5A
Rated Input Current
1(1.2)A, 5(6)A,Configurable
Rated input voltage
3x 57.7/100V,3x 220/380V
RS-485
4800 to 19200bps
Surge Immunity
IEC 61000-4-5:2014,level 4
Integration
Points to check before using SPM73 in a design. They are derived from the recorded characteristics, not from the manufacturer's application circuits.
1Thermalrated operating range -25 ℃~+60 ℃ — check it against the installation environment.
Power and communication
Direct Current Connection
5mA to 6.5A,Accuracy 0.2%
Direct Voltage Connection
10 to 400V(L-N),10 to 690V(L-L),Accuracy 0.2%
Power supply
85 to 275V AC,100 to 300V DC
Rated Input Current
1(1.2)A, 5(6)A,Configurable
Rated input voltage
3x 57.7/100V,3x 220/380V
Check the exact pin assignment and the application circuit in the datasheet, or ask our experts.
Implementation checklist
Thermal : rated operating range -25 ℃~+60 ℃ — check it against the installation environment.
Applications and use cases
Architectures in which SPM73 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
Solar production, storage and charging points on one site are often managed separately. Inverters, batteries, MPPT controllers, meters and chargers form a local energy system that shares production between users
To check
Regulatory framework for collective self-consumption in the country
Energy management system steering storage and charging
Metering accuracy for sharing between participants
Associated system blocks
ProductionStorageMeteringCharging
Need a complete solution?
Send a request for SPM73 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productPilot
SPM73
Three-Phase Multifunction Energy Meter for Panel Mounting
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details