Three-phase four-wire energy meter operated with current and voltage transformers, measuring active, reactive and apparent energy, with DLMS/COSEM communication.
Operating Temperature-25~70℃
Voltage Range80%Un~115%Un
Current Circuit Power Consumption<1VA
Maximum Current6A or 10A
Minimum current0.01A
Reference Current1A, 1.5A or 5A
Product overview
Overview. The Reallin E3016-SE is a three-phase four-wire energy meter of CT/CT-VT type, manufactured by Reallin. It measures active, reactive and apparent energy.
Main characteristics. Accuracy is class C/0.5S for active energy and class 2.0 for reactive energy. The reference current Ib is 1 A, 1.5 A or 5 A, with a maximum current of 6 A or 10 A and a minimum current of 0.01 A. The rated voltage Un is 57.7 V to 240 V, with an operating voltage range of 80% Un to 115% Un. The rated frequency is 50/60 Hz. The LED pulse output provides 10000 imp/kWh and 10000 imp/kvarh. The 8-digit LCD display has a configurable decimal place and supports backlight.
Interfaces and connectivity. The meter provides two RS485 ports (RJ45 type) with a 12 V (300 mA) power output, one RS485 port for RS485 group daisy chain, and one optical port. The communication protocol is DLMS/COSEM. It also has one signal input, two signal outputs and one control output.
Power and environment. Voltage circuit consumption is below 2 W / 10 VA and current circuit consumption is below 1 VA. Backup power is provided by a replaceable battery and an internal super capacitor. The RTC clock accuracy complies with IEC 62054-21. Operating temperature ranges from -25 to 70 °C, and storage temperature from -40 to 85 °C. The ingress protection is IP 54. The weight is about 1.8 kg.
Typical uses. This meter suits three-phase energy measurement and billing on current and voltage transformers, thanks to its active, reactive and apparent energy measurement and its DLMS/COSEM communication.
Integration. The meter complies with EN 50470-1, EN 50470-3, IEC 62052-11, IEC 62053-22/23, IEC 62056-21, IEC 62056-61 and IEC 62059-32-1. It is available on quotation from Atlas Electronics.
Three-phase four-wire energy meter operated with current and voltage transformers, measuring active, reactive and apparent energy, with DLMS/COSEM communication.
Operating Temperature-25~70℃
Voltage Range80%Un~115%Un
Current Circuit Power Consumption<1VA
Maximum Current6A or 10A
Minimum current0.01A
2. Datasheet extract (recorded values)
Parameter
Value
Accuracy
Class C/0.5S for active; Class 2.0 for reactive
Backup power supply
Replaceable battery and Internal super capacitor
Communication Protocol
DLMS/COSEM
Current Circuit Power Consumption
<1VA
Ingress Protection
IP 54
LCD display
8 digits with configurable decimal place, backlight supported
Maximum Current
6A or 10A
Minimum current
0.01A
Operating Temperature
-25~70℃
Pulsating Indicator
LED 10000imp/kWh;10000imp/kvarh
Rated Frequency
50/60Hz
Rated Voltage
57.7V~240V
Reference Current
1A, 1.5A or 5A
Starting Current
0.1%Ib
Storage Temperature
-40~85℃
Type
Three Phase Four Wire CT/CT-VT Operated Meter
Voltage Circuit Power Consumption
<2W/10VA
Voltage Range
80%Un~115%Un
Weight
About 1.8kg
Integration
Points to check before using 195163390 in a design. They are derived from the recorded characteristics, not from the manufacturer's application circuits.
1Thermalrated operating range -25~70℃ — check it against the installation environment.
Power and communication
Backup power supply
Replaceable battery and Internal super capacitor
Current Circuit Power Consumption
<1VA
Maximum Current
6A or 10A
Minimum current
0.01A
Rated Voltage
57.7V~240V
Reference Current
1A, 1.5A or 5A
Starting Current
0.1%Ib
Voltage Circuit Power Consumption
<2W/10VA
Voltage Range
80%Un~115%Un
Check the exact pin assignment and the application circuit in the datasheet, or ask our experts.
Implementation checklist
Thermal : rated operating range -25~70℃ — check it against the installation environment.
Applications and use cases
Architectures in which 195163390 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
Solar production, storage and charging points on one site are often managed separately. Inverters, batteries, MPPT controllers, meters and chargers form a local energy system that shares production between users
To check
Regulatory framework for collective self-consumption in the country
Energy management system steering storage and charging
Metering accuracy for sharing between participants
Associated system blocks
ProductionStorageMeteringCharging
Need a complete solution?
Send a request for 195163390 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details