D30162 – Three-phase four-wire DIN rail energy meter with current transformers

Three-phase four-wire DIN rail energy meter with current transformers

DIN Rail Energy Meters

  • Operation:-25~55℃
  • 100~275V
  • <1VA
  • 100A
Manufacturer part number
272029049
Manufacturer
Reallin
Temperature range
Operation:-25~55℃
Voltage Range
100~275V

The Reallin D30162 is a three-phase four-wire DIN rail energy meter designed to measure active energy with external current transformers in three-phase circuits.

Product overview

Overview. The Reallin D30162 is a three-phase four-wire DIN rail energy meter designed for three-phase four-wire circuits with external current transformers. It installs on a standard 35 mm rail without complex screw fixing or wiring.

Main characteristics. Accuracy class B/1.0 for active energy, reference current Ib of 25 A and maximum current Imax of 100 A, minimum current Imin of 1.25 A, rated voltage Un of 230 V with a voltage range of 100 to 275 V, rated frequency Fn of 50 Hz ±1.75%. The pulse constant is 1000 imp/kWh, indicated by an LED.

Interfaces and connectivity. RS485-A/B communication interface with screw-type terminals.

Power and environment. Voltage circuit consumption of <2.4 W and <6 VA at Un, current circuit apparent power of <1 VA at Ib. Protection degree IP 20, insulation class II, operating temperature range -25 to 55 °C. Dimensions 36 × 66 × 110 mm, weight about 0.15 kg.

Standards. Compliant with EN 50470-3:2022 and IEC 62052-31:2015.

Typical uses. Measuring energy consumption of three-phase four-wire circuits, particularly high-load circuits where current transformers are required, and transmitting metering data to a supervision system via RS485.

See all specifications

Highlights

  • Accuracy: Class B/1.0 for active
  • Communication interface: RS485-A/B with screw type
  • Current circuit apparent power at Ib: <1VA
  • Dimension(LxWxD): 36×66×110mm
  • Insulation Class: II
  • Maximum current Imax: 100A

Typical applications

Derived from the part category, not a compatibility statement.

See also

Technical questions

Ask a question

No published question about this part yet. Questions are reviewed before publication.

Similar products

All DIN Rail Energy Meters
Request a quote