Reallin single-phase energy meter for DIN rail mounting, measuring active energy at 230 V with an RS485 communication output for remote meter reading.
Temperature rangeOperation:-25~55℃
Voltage Range100~275V
Communication interfaceRS485-A/B with screw type
Current circuit apparent power at Ib<1VA
Maximum current Imax100A
Minimum Current (Imin)1.25A
Product overview
Reallin single-phase meter. the Single Phase Din Rail Meter is a single-phase energy meter designed for DIN rail mounting in electrical cabinets and distribution boxes.
Main characteristics. Rated voltage of 230 V, voltage range of 100 to 275 V, rated frequency of 50 Hz, reference current Ib of 25 A and maximum current Imax of 100 A, with a minimum current Imin of 1.25 A. Accuracy class B/1.0 for active energy, pulse constant of 1000 imp/kWh indicated by a pulsating LED. Dimensions of 18.5 × 66 × 110 mm for a weight of about 0.1 kg.
Interfaces and connectivity. RS485-A/B communication interface with screw terminals, allowing connection to a centralized meter reading system for remote reading and data monitoring.
Power and environment. Voltage circuit consumption below 2.4 W and 6 VA at Un, current circuit apparent power below 1 VA at Ib. Protection degree IP 20, insulation class II, operating temperature range of -25 to 55 °C.
Standards. Compliant with EN 50470-3:2022 and IEC 62052-31:2015.
Typical uses. Single-phase energy measurement in distribution installations and consumption management, with data transmission to a supervision system via RS485.
Integration. Direct mounting on a 35 mm DIN rail without a dedicated fixing bracket. Available on quotation from Atlas Electronics.
Reallin single-phase energy meter for DIN rail mounting, measuring active energy at 230 V with an RS485 communication output for remote meter reading.
Temperature rangeOperation:-25~55℃
Voltage Range100~275V
Communication interfaceRS485-A/B with screw type
Current circuit apparent power at Ib<1VA
Maximum current Imax100A
2. Datasheet extract (recorded values)
Parameter
Value
Accuracy
Class B/1.0 for active
Communication interface
RS485-A/B with screw type
Current circuit apparent power at Ib
<1VA
Dimension(LxWxD)
18.5×66×110mm
Insulation Class
II
Maximum current Imax
100A
Minimum Current (Imin)
1.25A
Protection degree
IP 20
Pulsating Indicator
LED
Pulsating(meter constant)
1000imp/kWh
Rated Frequency Fn
50Hz±1.75%
Rated Voltage Un
230V
Reference current Ib
25A
Standards
EN 50470-3:2022,IEC 62052-31:2015
Temperature range
Operation:-25~55℃
Voltage circuit active/apparent power at Un
<2.4W/6VA
Voltage Range
100~275V
Weight Of Meter
About 0.1kg
Applications and use cases
Architectures in which 273700405 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
A building’s energy, comfort and occupancy data sit in separate systems. Sensors, meters and gateways feed one model of the building, room by room, to compare scenarios and steer the installations
To check
Data model and building plans available
Software platform hosting the twin
Sensor density needed for a useful model
Associated system blocks
SensorsMetersGateways
Need a complete solution?
Send a request for 273700405 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details