Reallin three-phase four-wire energy meter measuring active and reactive energy of three-phase circuits, with Modbus RTU communication, for 3x277/480 VAC networks.
Frequency Range0.98-1.02fn
Voltage Range0.8-1.15Un
Current Circuit<4VA at Ib
Maximum current Imax65A
Minimum Current (Imin)0.25 A
Reference current Irer=Ib=10Ir5A
Product overview
Overview. The Reallin three-phase four-wire energy meter measures the energy of three-phase AC circuits. It is designed for installations on 3x277/480 VAC networks at 60 Hz.
Main characteristics. It measures active and reactive energy in both directions, with class B according to DIN EN 50470-1/3 and class 1.0 according to IEC62053-21 for active energy, and class 2.0 according to IEC62053-23 for reactive energy. The maximum current Imax is 65 A, the reference current Ib is 5 A and the minimum current Imin is 0.25 A. The LCD display has 7 digits.
Interfaces and connectivity. The meter communicates over Modbus RTU at 9600, 19200 or 38400 bps with adjustable 8E1, 8N1 or 8O1 formats. It provides an LED output of 1000 imp/kWh and 1000 imp/kvarh and connects through two-screw terminals.
Power and environment. The voltage circuit consumes less than 2 W / 10 VA at Un and the current circuit less than 4 VA at Ib. The operating voltage range is 0.8 to 1.15 Un. It operates between -30 °C and +70 °C and can be stored between -40 °C and +85 °C. Its life cycle exceeds 12 years.
Typical uses and integration. With Modbus RTU, the meter can be connected to a PLC or a supervision system for energy management in industrial and commercial installations. It is available on quotation from Atlas Electronics.
Reallin three-phase four-wire energy meter measuring active and reactive energy of three-phase circuits, with Modbus RTU communication, for 3x277/480 VAC networks.
Frequency Range0.98-1.02fn
Voltage Range0.8-1.15Un
Current Circuit<4VA at Ib
Maximum current Imax65A
Minimum Current (Imin)0.25 A
2. Datasheet extract (recorded values)
Parameter
Value
Active
Class B in compliance with DIN EN 50470-1/3; Class 1.0 in compliance with IEC62053-21
Architectures in which 273552418 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
Solar production, storage and charging points on one site are often managed separately. Inverters, batteries, MPPT controllers, meters and chargers form a local energy system that shares production between users
To check
Regulatory framework for collective self-consumption in the country
Energy management system steering storage and charging
Metering accuracy for sharing between participants
Associated system blocks
ProductionStorageMeteringCharging
Need a complete solution?
Send a request for 273552418 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productReallin
273552418
Three-Phase Four-Wire Energy Meter with Modbus RTU Communication
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details